Chapter 3. MOUNTING AND WIRING
■
Wiring
CAUTION
Prevent the load connected to the output terminal from exceeding the rating
indicated in the specifications. Failure to do so might cause damage.
Be sure to check that the wiring is correct before you turn the power ON.
Incorrect wiring might cause damage or malfunction.
The following table describes the meaning of symbols indicated on the terminal layout label on the
CMG
:
Symbol
Meaning
Direct current
●
Removing the operation panel/display
Required tool: Phillips screwdriver
(1)
Loosen the four screws on the operation panel/display using the Phillips
screwdriver.
(2)
Gently lift up the operation panel/display, and disconnect its power lead
connectors.
●
Wiring
Internal circuit
CN1
Terminal 1:
Terminal 2:
24Vdc
+
-
COM
Terminal 3:
OUTPUT
4 to 20mAdc output
Terminal 4:
Terminal 5:
Terminal 6:
EVENT2
RELAY
RELAY
Open collector output
*
*: A DC power supply can also be
used for the load that is wired to
terminals 5 and 6.
d
Relay output
Terminal No.
Signal Name
Description
1
24Vdc
Power supply
2
COM
Common
3
OUTPUT
Analog output 4 to 20mAdc
4
EVENT2
Event output 2 NPN open collector, integrated pulse
5
RELAY
Event output 1 contact output (relay output)
6
RELAY
Event output 1 contact output (relay output)
9
d
Loa
Loa