Specifications
Item
Description
Application
Batch-operated combustion systems burning gas, oil, or gas/oil mixture
Compatible flame detector
AUD100/ 100/ 120 series UV sensor, flame rod
AFD100/110 series visible light flame detector , contact input
Sequence
Sequence timing
Pre-purge
Ignition
standby
Pilot ignition
(main ignition)
*1
Pilot only (Hi sole-
noid valve ignition
standby)
*1
Main ignition (Hi
solenoid valve
ignition)
*1
Main burner
stabilization
Low fire
shutdown
Postpurge
35 s, 45 s, 60 s, 3
min (select
by model
number)
*2
7.5±1 s
4.5±0.5 s
8.5±1 s
4.5±0.5 s
8.5±1 s
45 s max.
20±2 s
Flame response
AUD100/110/120 series UV
sensor
Flame rod
AFD series visible
light flame
detector
Contact input
2 s max (nominally 1.5 s)
(when flame voltage is 3 V)
2 s max (nominally 1.5 s)
(when flame voltage is 2 V)
2 s max (nominally 1.5 s)
(20 lx -> 0 lx)
1 s max (nominally 0.8 s)
(
3 s max. when combined with AUR300
)
series controller (with flame response 2s
max.) for continuous operation
Reset timing
1 s or longer (main unit reset switch or contact reset input)
*4
Warning detection
timing
False flame
Airflow
switch
error 1
Airflow
switch
error 2
Interlock
error
Low fire
interlock
error 1
Low fire
interlock
error 2
High fire
interlock
error
POC (shutoff
valve closure
check) error
5 s
1 s max.
180 s
1 s
1 s max.
180 s
180 s
3 s
Airflow switch
monitoring
Yes (checks for switch error #1, error #2)
Ignition failure
Lockout
Flameout
Lockout
Low fire shutdown
*3
After confirming low combustion position when stopped, moves to postpurge (selected according to model).
Electrical
specifications
Rated power
supply voltage
AUD100/110/120 series UV
sensor
Flame rod
AFD series visible light
flame detector
Contact input
100 Vac, 200 Vac, or 220 Vac, 50/60 Hz
100 to 230 Vac, 50/60 Hz
Allowable power supply
voltage
85 to 110 % of rated power supply
Power consumption
10 W or less
Voltage resistance
1,500 Vac for 1 min, or 1,800 Vac for 1s
Between each terminal and ground, except for combustion sensor connection terminals (terminals 14, 15)
Insulation resistance
At least 50 M
Ω
, 500 Vdc megger
Between each terminal and ground, except for combustion sensor connection terminals (terminals 13, 14)
Contact rating
Blower motor
(electromag-
netic breaker)
Ignition
transformer
Pilot valve
(main valve Lo solenoid
valve)
*1
Main valve
(main valve Hi solenoid
valve)
*1
Warning
Control motor open
output,
close output,
proportional output
100 VA
300 VA
200 VA
200 VA
75 VA
200 VA
Monitor outputs
4, maximum 30mA each
Combustion detection
level
AUD100/110/120 series UV
sensor
Flame rod
AFD100/110 series visible
light flame detector
Contact input
When ignition is detected:
1.5 to 4.5 Vdc
When extinction is detected:
0.2 to 0.6 Vdc
When ignition is detected:
1.5 to 4.5 Vdc
When extinction is detected:
0.0 to 0.2 Vdc
When ignition is detected:
1.3 Vdc or less
When extinction is detected:
0.5 Vdc or more
When ignition is detected:
Short between F and G
When flame is not detected:
Open between F and G
Flame voltage
output
Recommended flame volt-
age: must be stable at
2 Vdc or above
Flame voltage output range:
0.2 to 4.5 Vdc
Recommended flame volt-
age: must be stable at
2 Vdc or above
Flame voltage output range:
0.0 to 4.5 Vdc
Flame voltage output range:
0.2 to 4.8 Vdc
When ignition is detected:
4.0 Vdc or more
When flame is not detected:
0.5 Vdc or less
Input
Start input, lockout interlock input, contact reset input, airflow switch input, POC (shutoff valve closure check) input, high fire interlock, low fire
interlock
* Each input is a non-voltage contact input, with allowable conta
ct resistance up to 500 Ω
Lifespan
10 years when used for eight hours per day, or 100,000 start/stop cycles (at 25 °C, room temperature, rated voltage)
Host com-
munication
specifications
Communications
standard
RS-485
Transmission route
3-wire system
Transmission speed
4800, 9600, 19200 bps
Transmission distance
Max. 500 m
Communication method
Semi-duplex
Synchronization method
Asynchronous
Data format
8 data bits, 1 stop bit, even parity, odd parity 8 data
bits, 2 stop bits, even parity, odd parity
Device address
1 to 32
Connection method
1: N (max. 15 units)
Miscellaneous
Based on RS-485