Specifications

 

Item 

Description 

Application 

Batch-operated combustion systems burning gas, oil, or gas/oil mixture 

Compatible flame detector 

AUD100/ 100/ 120 series UV sensor, flame rod 
AFD100/110 series visible light flame detector , contact input 

Sequence 

Sequence timing 

 

Pre-purge 

Ignition 

standby 

Pilot ignition 

(main ignition) 

*1

 

Pilot only (Hi sole- 

noid valve ignition 

standby) 

*1

 

Main ignition (Hi 

solenoid valve 

ignition) 

*1

 

Main burner 

stabilization 

Low fire 

shutdown 

 

Postpurge 

35 s, 45 s, 60 s, 3 

min (select 

by model 

number)

*2

 

 

7.5±1 s 

 

4.5±0.5 s 

 

8.5±1 s 

 

4.5±0.5 s 

 

8.5±1 s 

 

45 s max. 

 

20±2 s 

Flame response 

AUD100/110/120 series UV 

sensor 

 

Flame rod 

AFD series visible 

light flame 

detector 

 

Contact input 

 

2 s max (nominally 1.5 s) 

(when flame voltage is 3 V) 

 

2 s max (nominally 1.5 s) 

(when flame voltage is 2 V) 

 

2 s max (nominally 1.5 s) 

(20 lx -> 0 lx) 

1 s max (nominally 0.8 s) 

3 s max. when combined with AUR300

 

series controller (with flame response 2s 

max.) for continuous operation 

Reset timing 

1 s or longer (main unit reset switch or contact reset input) 

*4

 

Warning detection 

timing 

 

False flame 

Airflow 

switch 

error 1 

Airflow 

switch 

error 2 

Interlock 

error 

Low  fire 

interlock 

error 1 

Low  fire 

interlock 

error 2 

High fire 

interlock 

error 

POC  (shutoff 

valve  closure 

check) error 

5 s 

1 s max. 

180 s 

1 s 

1 s max. 

180 s 

180 s 

3 s 

Airflow switch 

monitoring 

Yes (checks for switch error #1, error #2) 

Ignition failure 

Lockout 

Flameout 

Lockout 

Low fire shutdown 

*3

 

After confirming low combustion position when stopped, moves to postpurge (selected according to model). 

Electrical 

specifications 

Rated power 

supply voltage 

AUD100/110/120 series UV 

sensor 

Flame rod 

AFD series visible light 

flame detector 

Contact input 

100 Vac, 200 Vac, or 220 Vac, 50/60 Hz 

100 to 230 Vac, 50/60 Hz 

Allowable power supply 

voltage 

85 to 110 % of rated power supply 

Power consumption 

10 W or less 

Voltage resistance 

1,500 Vac for 1 min, or 1,800 Vac for 1s 
Between each terminal and ground, except for combustion sensor connection terminals (terminals 14, 15) 

Insulation resistance 

At least 50 M

Ω

, 500 Vdc megger 

Between each terminal and ground, except for combustion sensor connection terminals (terminals 13, 14) 

Contact rating 

Blower  motor 

(electromag- 

netic breaker) 

 

Ignition 

transformer 

Pilot valve 

(main valve Lo solenoid 

valve) 

*1

 

Main valve 

(main valve Hi solenoid 

valve) 

*1

 

 

Warning 

Control motor open 

output, 

close output, 

proportional output 

100 VA 

300 VA 

200 VA 

200 VA 

75 VA 

200 VA 

Monitor outputs 

4, maximum 30mA each 

Combustion detection 

level 

AUD100/110/120 series UV 

sensor 

Flame rod 

AFD100/110 series visible 

light flame detector 

Contact input 

When ignition is detected: 

1.5 to 4.5 Vdc 

When extinction is detected: 

0.2 to 0.6 Vdc 

When ignition is detected: 

1.5 to 4.5 Vdc 

When extinction is detected: 

0.0 to 0.2 Vdc 

When ignition is detected: 

1.3 Vdc or less 

When extinction is detected: 

0.5 Vdc or more 

When ignition is detected: 

Short between F and G 

When flame is not detected: 

Open between F and G 

Flame voltage 

output 

Recommended flame volt- 

age: must be stable at 
2 Vdc or above 
Flame voltage output range: 

0.2 to 4.5 Vdc 

Recommended flame volt- 

age: must be stable at 
2 Vdc or above 
Flame voltage output range: 

0.0 to 4.5 Vdc 

Flame voltage output range: 

0.2 to 4.8 Vdc 

When ignition is detected: 

4.0 Vdc or more 

When flame is not detected: 

0.5 Vdc or less 

Input 

Start input, lockout interlock input, contact reset input, airflow switch input, POC (shutoff valve closure check) input, high fire interlock, low fire 

interlock 
* Each input is a non-voltage contact input, with allowable conta

ct resistance up to 500 Ω

 

Lifespan 

10 years when used for eight hours per day, or 100,000 start/stop cycles (at 25 °C, room temperature, rated voltage) 

Host com- 

munication 

specifications 

Communications 

standard 

RS-485 

Transmission route 

3-wire system 

Transmission speed 

4800, 9600, 19200 bps 

Transmission distance 

Max. 500 m 

Communication method 

Semi-duplex 

Synchronization method 

Asynchronous 

Data format 

8 data bits, 1 stop bit, even parity, odd parity 8 data 

bits, 2 stop bits, even parity, odd parity 

Device address 

1 to 32 

Connection method 

1: N (max. 15 units) 

Miscellaneous 

Based on RS-485 

Содержание BC-R35 Series

Страница 1: ...ng codes PresstheDISPswitchtodisplaytheflamevoltage External statusoutput States such as ignition failure flame failure and combustiondetectedareoutputdigitally andusedas panel displays Warning reset...

Страница 2: ...or 1 800 Vac for 1s Between each terminal and ground except for combustion sensor connection terminals terminals 14 15 Insulation resistance At least 50 M 500 Vdc megger Between each terminal and gro...

Страница 3: ...R05 only Excess voltage cat egory II Pollution degree PD2 Case color Black Case material Denatured PPE resin UL94 V0 PTI materials group IIIa Structure Sub base and main unit Mounted orientation Vert...

Страница 4: ...n record with data Flame detector Visible light flame detector AFD100 110series I II III IV V VI VII Example BC R35A7G0500 I II III IV V VI VII Description Base model number Commu nications function F...

Страница 5: ...e rod holder Discontinued C7008A Flame rod assembly Discontinued Visible light flame detector Model number Name Notes AFD100A0700 Visible light flame detector Light reception direction front top view...

Страница 6: ...t for5secondstoensureoperationstability 2 During postpurge reset is disabled for 20 seconds Connector for front wiring 81447514 001 terminal layout Connectorforfrontwiring forrightsidewiring 81447514...

Страница 7: ...hreeminutesafterhighfire position output Low fire interlock error 1 The low fire interlock turned off between pilot ignition and main stabilization Low fire interlock error 2 The low fire interlock re...

Страница 8: ...nput in isolation It cannot be used in conjunction with other BC R contact reset inputs Outputcommon terminals4 5 andinputcommon terminal16 17 cannotbeusedinconjunctionwithotherBC Rcontactreset inputs...

Страница 9: ...44 70 10170 02 888 3472 08 08 170 170 02 888 3258 https www add furnace com E mail sales add furnace com For compliance with the standard on remote control of boilers Standards circular No 0331001 wh...

Страница 10: ...rew Model number A 81447514 001 10 6 81447514 002 14 6 Sub base BC R05A100 sold separately 61 Sub base sold separately 95 110 Connector for front wiring Sub base sold separately BC R main unit fasteni...

Страница 11: ...02 888 3472 08 08 170 170 02 888 3258 https www add furnace com E mail sales add furnace com Sideboard 81447515 001 sold separately Unit mm 30 7 Sub base Sub base 19 knockout hole Sideboard Sideboard...

Страница 12: ...BC R Main unit BC R Main unit Installation orientation Install the device in the orientation shown below Display area OK OK Do not install it in the orientations illustrated below Mounting in a Panel...

Страница 13: ...tion Flameout No ignition Lockout interlock Start check time Approximately 2 s Pre purge time Ignition standby time Main stabilization time Main ignition time Postpurge time Pilot ignition time Pilot...

Страница 14: ...ctromagnetic breaker Ignition transformer Main valve Lo solenoid valve Main valve Hi solenoid valve Warning output Control motor open Control motor closed Control motor proportional Monitor output Com...

Страница 15: ...etic breaker Ignition transformer Main valve Lo solenoid valve Main valve Hi solenoid valve Warning output Control motor open Control motor closed Control motor proportional Monitor output Combustion...

Страница 16: ...ector AFD100 series contact input For a UV sensor Write the model No With a visible light flame detector Write the model No Ignition method circle the applicable product Direct ignition type time limi...

Страница 17: ...ut notice 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan https www azbil com 13 1stEdition Oct 2014 3rd Edition Dec 2020 No part of this publication may be reproduced or duplicated without the prior w...

Отзывы: