4. Operation check

When verifying the function of the tube unit, use the flame-

voltage output terminals of the 

AUR

.


AUR output terminals

Black

Red

0 to 7.5 Vdc range 

input 100 k

Ω or more

FSP136A100

or equivalent

(1)  Connect a analog flame meter (

FSP136A100

) to the flame 

voltage output terminals of the 

AUR

.

(2)  Light a lighter in front of the ultraviolet ray receiving part 

of this unit to check that the voltage is output correctly.

 

Handling Precautions

When using an open flame, check that there is no 

flammable gas around this unit.

(3)  Mount the 

AUD300C

 onto the monitoring pipe.

(4)  Start the combustion of the burner.

(5)  Measure the flame voltage between terminals 9 and 10 of 

the 

AUR

 with a tester.

Recommended flame voltage

Inspection item

Stable 2.0 Vdc or more
(The flame voltage may fluctuate 

in a range of 0.1 to 0.3V 

synchronized with the shutter 

operation of this unit.)

Check that the flame is 

monitored correctly.

Check that the light receiving 

lens of this unit is not 

contaminated.

Check that foreign matter, such 

as soot is not caught in the 

monitoring pipe.

5. Inspection and adjustment

After replacing the tube unit, perform a pilot turndown test, an 

ignition spark response test and a safety shutoff test to verify 

proper functioning of the tube unit.

  The AUR300C Advanced Ultraviolet Burner Controller 

with Communications User's Manual (CP-SP-1142E),  

the AUR350C Advanced Ultraviolet Burner Controller 

User's Manual (CP-SP-1175E),  the AUR450C 

Dynamic Self-Checking Burner Controller User's 

Manual (CP-SP-1264E) (

for details on each test)

3. Replacement of tube unit

 

Handling Precautions

When replacing, handle the shutter unit gently, 

• 

taking care not to jar it.
 When transporting or storing the AUD10C1000, be 

• 

sure to package it in the same packaging that it was 

in when it was received.
The upper limit of the operating temperature range 

• 

of this unit is 120˚C. If the 120˚C-part of the thermo 

label of the AUD10C1000 tube unit becomes black, 

check the ambient temperature and cool the unit 

using air purging or the like.
After the replacement work, be sure to carefully 

• 

mount the O-ring on the flange unit before 

reattaching the cover. Otherwise the Ultraviolet 

flame detector will not be properly sealed.
Tighten the terminal screws and mounting screws 

• 

with a tightening torque of 0.7N•m.

(1)  Turn OFF the power to the 

AUR 

Burner Controller.

(2)  Loosen the mounting nut after at least one minute has 

passed, then remove the 

AUD300C

 Ultraviolet flame 

detector from the monitoring pipe.

(3)  Remove the cover by unscrewing the four (4) mounting 

screws that secure it to the 

AUD300C

.

(4)  Remove 2 tube unit retaining screws on the rear of the tube 

unit.

(5)  Hold the rear of the tube unit and gently raise it upward to 

remove it.

(6)  Insert the top part of the new tube unit into the round hole 

in the upper portion of the shutter unit and push the bottom 

part of the tube unit down into place.

Mounting nut

O-ring

Flange unit

Cable guide

Cover mounting screws (4)

Tube unit

Tube unit retaining screws (2)

G-terminal (yellow lead wire)

F-terminal (blue lead wire)

 

Handling Precautions

The tube unit has a specific polarity. To mount it 

correctly, match the polarity with the F and G label 

on the upper portion of the AUD50A1000 shutter 

unit. Also, the shutter unit and tube unit have a 

matching difference in level designed so that the 

tube unit cannot be mounted the wrong way. Do 

not attempt to forcibly mount the tube unit in the 

wrong direction.

(7)  Tighten 2 tube unit retaining screws.

(8)  Make sure that the O-ring is not disengaged from the flange 

unit.

(9)  Secure the cover with 4 cover mounting screws.