9
Chapter 4. WIRING
●
Wiring of the limit switch
CAUTION
To wire the limit switch correctly, refer to the user’s manual or the product specification sheet.
•
Tighten terminal screws to the torque shown below.
Screw size
Tightening torque
M4 (pan head screw with square washer)
1.3 to 1.7
N·m
Wire routing
•
Pull-out strength of the terminal
After wiring, do not pull the wire or cable with excessive force (≥ 30 N).
30 (N) max.
Cable
Handling Precautions
•
Do not exceed the values given for pulling force, which is the same for both
single wire and two-ply or more stranded wires.
●
Attaching the cover
Be sure to attach the cover after wiring is complete.
Tighten the four cover mounting screws evenly in a diagonal pattern.
Tighten the screws to the torque shown below.
Screw size
Tightening torque
M5 (hexagon socket bolt with spring washer)
5 to 6
N·m
Handling Precautions
•
When mounting the cover, make sure that it does not touch electrical wires or
terminals, and does not pinch the wiring insulation.
•
Do not tighten beyond the specified torque. Overtightening may damage
screw threads of the housing.
●
Continuity tester
For a continuity check for the limit switch, use a tester whose measuring current
is 100 mA or less.