7
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!!
Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!!
Do not apply any anti-oxidant substance on the terminals before the terminals are
connected tightly.
CAUTION!!
Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).
AC Input/Output Connection
CAUTION!!
Before connecting to AC input power source, please install a
separate
AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 40A
for 5KVA.
CAUTION!!
There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING!
All wiring must be performed by the qualified personnel.
WARNING!
The AC input N wire must be connected, Otherwise, the inverter will NOT detect AC input;
WARNING!
It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the recommended cable size as below.
Suggested cable requirement for AC wires
Model Gauge
Torque
Value
5KVA
10 AWG
1.4~ 1.6Nm
There are three applications for different AC input as shown in the figure below. For phase angle operation,
please refer to LCD #28