F 1° = P (VA) transf. x 1,1
V (primary) 1,73
F 2° = P (VA) transf. x 1,1
V1 (secondary) 1,73
FDC x MS 2/4 = 10A super rapid
x MS 4/8 = 10A super rapid
x MS 8/16 = 10A super rapid
x MS 10/20 = 10A super rapid
x MS 14/28 = 16A super rapid
x MS 20/40 = 20A super rapid
x MS 25/50 = 20A super rapid
CHAPTER 3 - Installation
CHAPTER 3 - Installation
Dimensioning with three phase power supply
TRANSFORMER
Voltage: See single phase section same parameters
can be used.
Power: See single phasesection same parameters can
be used.
F U S E S
Rack board interconnections
Fuses dimensioning
Fuses on primary slow types
Fuses on secondary slow types
Power supply fuses MS 60, MS 140, MS 200
Using the interconnections modules , fuses are on board.
ATTENZIONE:
Axor reccomend, to connect the drive at the power net using
a transformers with triangle connection in the secondary wiring. If the
secondary wiring is star connection, you MUSTN'T connect the neutral to
ground.