Service Guide MINI SPEED
Service Guide MINI SPEED
High Performans servo Drives
AXOR
High Performans servo Drives
AXOR
Fuses dimensioning
fuses on primary slow types
fuses on secondary slow type
Power supply fuses for MS 60,MS 140,MS 200.
Using the interconnections modules ,the fuses are on board.
P (VA) = (Pass M1 + Pass M2 +.........) x 1,25
F 1° = P (VA) transf. x 1,1
V (Primary) ac
F 2° = P (VA) transf. x 1,1
V1 (secondary)
CHAPTER 3 - Installation
CHAPTER 3 - Installation
Power: nominal transformer power is referred to each motor
power sum,on pluriaxes applications.
where
Usually, if motors donʼt work together,we can declass the
transformer of 30/40%.
If the power of the transformer sur-
plus 7KVA call AXOR.
Pabs = Vmotor x In (Pabs M = absorbed motor power)
FUSES
FDC x MS 2/4 = 10A super rapid
x MS 4/8 = 10A super rapid
x MS 8/16 = 10A super rapid
x MS 10/20 = 10A super rapid
x MS 14/28 = 16A super rapid
x MS 20/40 = 20A super rapid
x MS 25/50 = 20A super rapid
Connections examples
Here we found some examples about input reference.
The numerations are referred to rack and mother board interconnections.
Input reference shield should be connect at ground isolated bar. (see ground connections)
Examples for analogue input connection.
Velocity Control
“C.N.C” differential
mode.
Velocity Control
“C.N.C” common
mode.
Connection of
velocity reference
input using internal
amplifier voltage.
Connection of
velocity reference
input using external
voltage.
Dimensioning single phase power supply