Installation 

Note: It is recommended that only qualified, experienced personnel, familiar with this type of equipment, who have read 
and understood all the instructions in this manual should install, operate, and maintain the system. 

Mounting 

The unit should be permanently wall mounted on a hard, level surface. Use provided mounting holes located on the back 
plate for proper fastening (Refer to mechanical drawing(s) for Mounting Hole Diameter). Ensure the system is level and 
secure, enabling water to be more accurately sensed in the primary filter’s sump. Be sure to secure the system in a 
location that allows all piping and electrical wiring to be safely routed to the system. This unit is designed for well-
ventilated indoor use within the specified temperature range and should be located as close to the tank as possible. 

Electrical 

!WARNING! To avoid the risk of electric shock, make sure that the power supply to the system is disconnected 
and ensure that the system is at zero volts, before working on any of the system’s electrical parts. 

 
Make sure that the system’s power requirements and rated voltage/frequency match your electrical system (see wiring 
diagram). The system may only be connected to properly grounded power sources for operator safety. Connect all 
components to the ground studs provided as shown on the provided drawings.  The system connects to either 12VDC or 
24VDC with the positive lead from your power source to the red wire and the negative lead to the gray wire. After the 
initial wiring of the system check operation to ensure that it is running in the correct direction. If the motor is running in the 
wrong direction, contact AXI International immediately. 
 

!WARNING! The whole system (enclosure, doors, plumbing, motor, electric sub panel) must be properly 
grounded for operator safety. 
 

Depending on length of run, use wiring according to specification in wiring diagram and connect system to a separate UL 
listed breaker (not included) appropriate for branch circuit protection. Connect the System Controller to the filtration unit 
with the provided plugs and wiring harnesses. 
 

Note: Wiring and electrical installation must be in accordance with all applicable federal, state, and local rules, laws, 
standards, and regulations. 

Plumbing 

Note: Please ensure to check all of the plumbing (joints, unions, miscellaneous fittings) for tightness prior to completion.  

 
Use proper quality approved fuel line materials with similar inner diameter (ID) to the inlet/outlet of the system. For 
extended suction side plumbing runs, it is recommended to install oversized pipe, (1/4” to 1/2” increased ID) (Ref.: Page 4 
– Suction Capability). 

It is imperative that external, manual inlet and outlet ball valves be installed on each side of 

the filtration system. That will enable it to be isolated from the external piping apparatus, eliminating the 
possibility of the system to be damaged by over-pressurization of said plumbing during initial start-up testing 
(IST).

 

 

Note: Flexible plumbing is strongly recommended for system inlet and outlet connections to external plumbing in order to 
avoid issues with thermal expansion, prevent putting any stress on the internal fittings of the system, and enable ease of 
maintenance/installation. Install manual inlet and outlet ball valves prior inlet flexible plumbing and post outlet flexible 
plumbing respectively. 
 

The pick-up tube/line(s) should originate from the lowest point of the tank to ensure all water is removed. Also, it should 
be connected directly to the system’s inlet port (located on the left-hand side of the system) and be kept as short as 
possible. It is recommended that an oversized, low restriction foot valve be installed to keep the system primed, especially 

Содержание FPS Compact Series

Страница 1: ...on Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com FPS FPS Compact Instruction Operating Maintenance Manual COMPACT FUEL MAINTENANCE SYSTEM REV030...

Страница 2: ...REV0302COM010120 1...

Страница 3: ...ly 8 Important Installation Precautions 8 Controller 9 Setting the Current Date and Time 9 Programming the Timer 9 Priming the System 10 Priming Procedure 10 Commissioning Initial Start Up 11 Gauge Ve...

Страница 4: ...ose Barb System Back Plate Powder Coated Aluminum Operating Temperature 41 104 F 5 40 C Electrical 12VDC 10A or 24VDC 5A Pump DC Gear Pump Suction Capability Primed 10 ft 304 8 cm Total Dynamic Head T...

Страница 5: ...tch Water Detection Alarm Module Vacuum Switch Leak Detection Float Switch Pump Motor DC Gear Pump Primary Filter Water Separator Fuel Filter o Standard issue back flushable 30 micron hydrophobic filt...

Страница 6: ...tion o Activated when the Float Switch in the system s drip tray detects a raised liquid level The system will go into an alarm state and the pump will not be allowed to be run until the alarm is addr...

Страница 7: ...ectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that could...

Страница 8: ...r electric sub panel must be properly grounded for operator safety Depending on length of run use wiring according to specification in wiring diagram and connect system to a separate UL listed breaker...

Страница 9: ...90 degree connectors or other plumbing accessories For continuous optimal performance make sure suction and discharge lines are free of contamination nothing is blocking the flow of fuel and the sucti...

Страница 10: ...OUR and MIN respectively to set desired start time for 1ON 4 Press TIMER to switch to 1OFF 5 Press DAY as often as required to select the same combinations of days as in step 2 must be consistent 6 Pr...

Страница 11: ...will not eliminate the necessity to prime the complete system The system is primed through the primary filter as well as the suction line s have to be completely filled with fuel no trapped air prior...

Страница 12: ...ust the Wrench Key turn at a time CCW to increase the vacuum alarm s set point 5 After adjusting the settings perform the testing procedure s for the switch es as outlined in the commissioning section...

Страница 13: ...rator s Note All filter elements should be replaced at least every six 6 months Servicing the Primary Filter Water Separator Clogged filter elements restrict the flow of fuel resulting in the system s...

Страница 14: ...Note Disposal of fuel associated waste and filters must be in accordance with all applicable federal state and local rules laws standards and regulations WARNING Some fuels may have been treated with...

Страница 15: ...w filter element installed 1 Heavily contaminated fuel excessive water in tank 2 Restriction in plumbing on inlet side too high 3 Excessive lift 4 Inoperative foot valve 5 Inlet ball valve not fully o...

Страница 16: ...limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by a...

Страница 17: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Страница 18: ...required part numbers and quantity The drawings parts list included in this manual are the most accurate source of part numbers for your FPS COMPACT Replacement Filter Elements Primary Filter Water S...

Отзывы: