Axi FPS Compact Series Скачать руководство пользователя страница 4

 

REV0302COM010120 

General Overview 

 

FPS Compact Specifications 

 
Flow Rate……………………………………………………….  1.3 GPM/80 GPH (5 LPM/302.8 LPH) 

640 gallons (2,423liters) per 8-hour shift 
1,920 gallons (7,268 liters) per 24 hours 

Primary Filter……………………………………………………  10 or 30

μ

 Particulate or 60

μ

 Stainless Steel 

Screen with Centrifugal Water Separator 

Fuel Conditioner………………………………………………..  LG-X 500 Inline Magnetic Conditioner 

Plumbing………………………………………………………...  Stainless Steel 

Inlet Port…………………………………………………………  1/2” Hose Barb 

Outlet Port…….…………………………………………………  1/2” Hose Barb 

System Back Plate……………………………………………..  Powder Coated Aluminum 

Operating Temperature………………………………………. 

41 - 104°F (5 - 40°C

)

 

Electrical……………………………………………………….. 

12VDC/10A or 24VDC/5A 

Pump…………………………………………………………… 

DC Gear Pump 

Suction Capability (Primed)………………………………….. 

10 ft. (304.8 cm) Total Dynamic Head 

Timer………………………………………………………….... 

Programmable Digital Timer 

Maximum Fluid Viscosity…………………………………….. 

5 cSt 

Outline Dimensions………………………………..………….. 

 14” x 10” x 8” (36 x 25 x 20 cm) (H x W x D) 

Weight…………………………………………………………… 

 20lbs. (9.1kg) 

 

 

!WARNING! This system is not meant for use with gasoline or any other flammable liquids having a flash point 
less than 100°F (37.8° C). Use with gasoline or any flammable liquids at a temperature exceeding their flash point 
presents an immediate explosion and fire hazard. 

 

 

Содержание FPS Compact Series

Страница 1: ...on Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com FPS FPS Compact Instruction Operating Maintenance Manual COMPACT FUEL MAINTENANCE SYSTEM REV030...

Страница 2: ...REV0302COM010120 1...

Страница 3: ...ly 8 Important Installation Precautions 8 Controller 9 Setting the Current Date and Time 9 Programming the Timer 9 Priming the System 10 Priming Procedure 10 Commissioning Initial Start Up 11 Gauge Ve...

Страница 4: ...ose Barb System Back Plate Powder Coated Aluminum Operating Temperature 41 104 F 5 40 C Electrical 12VDC 10A or 24VDC 5A Pump DC Gear Pump Suction Capability Primed 10 ft 304 8 cm Total Dynamic Head T...

Страница 5: ...tch Water Detection Alarm Module Vacuum Switch Leak Detection Float Switch Pump Motor DC Gear Pump Primary Filter Water Separator Fuel Filter o Standard issue back flushable 30 micron hydrophobic filt...

Страница 6: ...tion o Activated when the Float Switch in the system s drip tray detects a raised liquid level The system will go into an alarm state and the pump will not be allowed to be run until the alarm is addr...

Страница 7: ...ectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that could...

Страница 8: ...r electric sub panel must be properly grounded for operator safety Depending on length of run use wiring according to specification in wiring diagram and connect system to a separate UL listed breaker...

Страница 9: ...90 degree connectors or other plumbing accessories For continuous optimal performance make sure suction and discharge lines are free of contamination nothing is blocking the flow of fuel and the sucti...

Страница 10: ...OUR and MIN respectively to set desired start time for 1ON 4 Press TIMER to switch to 1OFF 5 Press DAY as often as required to select the same combinations of days as in step 2 must be consistent 6 Pr...

Страница 11: ...will not eliminate the necessity to prime the complete system The system is primed through the primary filter as well as the suction line s have to be completely filled with fuel no trapped air prior...

Страница 12: ...ust the Wrench Key turn at a time CCW to increase the vacuum alarm s set point 5 After adjusting the settings perform the testing procedure s for the switch es as outlined in the commissioning section...

Страница 13: ...rator s Note All filter elements should be replaced at least every six 6 months Servicing the Primary Filter Water Separator Clogged filter elements restrict the flow of fuel resulting in the system s...

Страница 14: ...Note Disposal of fuel associated waste and filters must be in accordance with all applicable federal state and local rules laws standards and regulations WARNING Some fuels may have been treated with...

Страница 15: ...w filter element installed 1 Heavily contaminated fuel excessive water in tank 2 Restriction in plumbing on inlet side too high 3 Excessive lift 4 Inoperative foot valve 5 Inlet ball valve not fully o...

Страница 16: ...limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by a...

Страница 17: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Страница 18: ...required part numbers and quantity The drawings parts list included in this manual are the most accurate source of part numbers for your FPS COMPACT Replacement Filter Elements Primary Filter Water S...

Отзывы: