background image

 

 

 
 

Reader Description 

Revision E

 

June 18, 2006

 

The Sentinel-Prox KP-6840 Reader is a radio-frequency proximity reader with integrated keypad for Access Control 
Systems.  The Reader consists of a 12-key keypad, transmit/receive antenna, and reader electronics, in a polycarbonate 
housing.  The reader electronics are potted with epoxy resin to protect against the environment.  The KP-6840 Reader       
may be mounted like a cover plate on a single-gang electrical utility box, or on any surface (wall, cabinet, etc). 

      

Parts List 

(a) 

Installation Sheet, P/N 005-98-A  

Qty=1 

(b) 

Sentinel-Prox KP-6840 Reader, P/N 005-20-A  

Qty=1 

(c) 

#6-32 x 1” machine screw, P/N 0616MPP 

Qty=2   

 

 

 

Installation Procedure

 

1.

 

Install a single-gang electrical utility box, or drill two no. 27 (0.144 inch) clearance holes for the reader screws            
and one hole for the cable, at the desired location.  Observe ADA height requirements. 

2.

 

Snap open the reader’s top cover by inserting a wide screwdriver blade into the slot at the bottom edge of the cover,   
then twisting the blade gently (see Figure 1).  

Do not remove

 the keypad from the reader. 

3.

 

Clip off the white inline connector from the end of the reader’s cable.  Keep the wires as long as possible. 

4.

 

Connect the reader’s cable to the access control panel as shown in Figure 2.  Connect the 

yellow

 wire only if used for 

Beeper control by the panel.  In steps 9 and 10, let the yellow wire 

float

.  Connect the 

blue

 wire only if used for Hold 

control by the panel.   

Do not connect

 the 

orange

 and 

violet

 wires to anything.   

Tape or cap all unused wires singly.

 

5.

 

Use a linear regulated DC power supply, between 5 volts (60 mA peak) and 12 volts DC (120 mA peak). 

6.

 

Install the reader on the electrical utility box or other surface.  Attach the reader to the electrical box with supplied 
screws (item c in the Parts List). 

7.

 

Hold the reader’s top cover over the base reader, and snap the cover closed securely. 

8.

 

Power up the reader.  The beeper sounds a single 

Short

 beep.  The LED should be steady amber. 

9.

 

While the LED is amber, enter the 10-digit password (

914 369 8800

).  There is a short beep with each keystroke.       

(For security, record this password and store it in a safe place.) 

10.

 

Immediately enter the 5-character code 

#ABC#

 for the site code (or facility code) that you will program into the host 

system to identify keypad PIN entry.  “ABC” represents the 3-digit site code.  There is a short beep with each keystroke. 

·

 

Program the host system for 26-bit Wiegand format from keypad entry.  The site code must be between 000 and 255. 

·

 

If you do not enter the keypad’s site code, the KP-6840 Revision E Reader-Keypad enters a default site code of 000. 

·

 

The site code for the keypad may be the 

same as

 or 

different from

 the site code of the credentials (cards, keytags      

or wafers), depending on requirements of the host system or application. 

11.

 

If programming is successful, the beeper sounds 1 long beep.  Then the LED is red to indicate standby mode. 

12.

 

If the beeper doesn’t sound and the LED doesn’t change to red, remove power from the reader, then repeat steps 8 to 11, 
above.  Enter the password and the site-code selection code with a steady hand, pressing each key for at least 

0.5 second

.  

Do not pause between the password and the 5-character code.  Also, be sure that the 

yellow

 wire is disconnected from  

the panel and floating. 

13.

 

The LED color in standby mode may be changed from red to green, or from green to red, using a 

Color Changer

 card, 

available from AWID.  Remove power from the reader for a few seconds; then restore power.  While the LED is amber, 
present the Color Changer card to toggle the LED color at standby. 

 

Operation Modes

  The KP-6840 Revision E Reader supports the following operation modes of the host system: 

Proximity plus PIN

......Present proximity card first, then enter PIN on keypad.

  

Proximity Only

.............Present proximity card only. 

PIN plus Proximity

......Enter PIN on keypad first, then present proximity card. 

PIN Only

.......................Enter PIN on keypad only. 

Notes for Operation Modes: 

(a)

 

For 26-bit Wiegand format, enter between 1 and 5 keystrokes.  The PIN must be between 0 and 65535. 

(b)

 

To cancel keypad PIN entry before completing the number, press the 

*

 key. 

(c)

 

To terminate keypad PIN entry after all keys have been pressed, press the 

#

 key. 

 

 

 

     (continued) 

Installation Sheet (Wiegand Interface) 

(Part No. 005-98-A)

 

Sentinel-Prox KP-6840 Reader with Keypad 