Pressure Independent Variable Air Volume ( Single Duct)
Electric heaters shall be factory mounted
to the terminal with the heating elements
located upstream of the air-flow control
damper to ensure uniform velocity profile
over the elements.
A power disconnect shall be furnished to
render the heater non-operational. Heater
shall be furnished with all controls necessary
for safe operation and full compliance
with UL 1996 and National Electric Code
requirements.
Heater shall have a single point electrical
connection. It shall include a primary disc
type automatic reset high temperature limit,
secondary high limit(s), airflow switch,
Ni-Chrome elements, and fusing per UL
and NEC. Heater shall have complete
wiring diagram with label indicating power
requirement and kw output.
Electrical Heater Components
Stainless Steel Finned Tubular
Elements
Hinged Weather proof Control Panel
Airflow Switch
Control Transformer (optional)
Magnetic Contactors
Fuse
SCR Power Controllers / On-Off
Controller
Miniature Circuit Breaker (MCB)
Bimetal Linear Manual Resettable
Thermal Cut out
Automatic Thermal cut out.
Electric Heater Details