10. Final Check and Test Run
After installing the unit, perform the final check
and running test as follows:
Final check points
¤
Is the unit securely mounted?
¤Ł
Is the installation location adequate?
¤Ø
Is the water piping work adequately and
without leakage?
¤Œ
Are trapped drain lines installed at
condensate drain connections?
¤º
Has the refrigeration cooling cycle been
kept sealed?
¤
Is the electrical wiring adequate and are
the screws tightened on terminals?
After the above final checkings, prepare the
running test as follows:
¤
Connect compound gauges to the check
joints at discharge and suction sides of
the compressor.
¤Ł
Turn all switches "OFF".
¤Ø
Turn the main switch "ON".
Running test should be accomplished as follows:
¤
Set operation switch at "FAN" and the fan
will start. Check to ensure that the fan
sounds normal.
¤Ł
Next, set it at "COOL" and the compressor
will start. Check to ensure that the
compressor sounds normal.
¤Ø
Check discharge and suction pressure on
the compound gauges.
¤Œ
Check working voltage, phase balance and
running current.
¤º
Check to ensure that the thermistor
functions properly.
¤
Check to ensure that the high pressure
control switch functions correctly.