DC FUSE REPLACEMENT
The DC fuses may be replaced by inserting the tip of a flat-head screwdriver into the
fuse holder slot, and rotating the slot counter-clockwise. The fuse and its carrier will
then pop out.
FUSE RATINGS
The following table lists the required fuses for standard units:
Fuses
Nominal
Mains
Voltage
Rating
Case Size
Recommended Replacement Part
Littelfuse Part
Number
Digi-Key Stock
Number
#1, #2 (AC)
115 V
1.6A, 250V,
Time-Delay
5×20 mm
021801.6HXP
F2424-ND
230 V
0.8A, 250V,
Time-Delay
5×20 mm
0218.800HXP
F2418-ND
#3 (DC)
N/A
1.0A, 250V,
Time-Delay
5×20 mm
0218001.HXP
F2419-ND
#4 (DC)
N/A
6.3A, 250V,
Time-Delay
5×20 mm
021806.3HXP
F2428-ND
Units with the -XP2 option require different fuses:
Fuses
Nominal
Mains
Voltage
Rating
Case Size
Recommended Replacement Part
Littelfuse Part
Number
Digi-Key Stock
Number
#1, #2 (AC)
115 V
3.15A, 250V,
Time-Delay
5×20 mm
02183.15HXP
F2430-ND
230 V
1.6A, 250V,
Time-Delay
5×20 mm
021801.6HXP
F2424-ND
#3 (DC)
N/A
1.0A, 250V,
Time-Delay
5×20 mm
0218001.HXP
F2419-ND
#4 (DC)
N/A
10A, 250V,
Time-Delay
5×20 mm
0218010.HXP
F2425-ND
The recommended fuse manufacturer is Littelfuse (http://www.littelfuse.com).
Replacement fuses may be easily obtained from Digi-Key (http://www.digikey.com/) and
other distributors.