recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken

in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical

power is available before the task is commenced.

a) Become familiar with the equipment and its operation.

b) Isolate system electrically.

c) Before attempting the procedure ensure that :mechanical handling equipment is available, if

required, for handling refrigerant cylinders; all personal protective equipment is available and

being used correctly; the recovery process is supervised at all times by a competent person;

recovery equipment and cylinders conform to the appropriate standards.

d) Pump down refrigerant system,if possible.

e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various

parts of the system.

f) Make sure that cylinder is situated on the scales before recovery takes place.

g) Start the recovery machine and operate in accordance with manufacturer's instructions.

h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

i) Do not exceed the maximum working pressure of the cylinder,even temporarily.

j) When the cylinders have been filled correctly and the process completed, make sure

that the cylinders and the equipment are removed from site promptly and all isolation

valves on the equipment are closed off.

k) Recovered refrigerant shall not be charged into another refrigeration system

unless it has been cleaned and checked.

10 LABELLING

Equipment shall be labelled stating that it has been de-commissioned and emptied of refri-

gerant.The label shall be dated and signed.

Ensure that there are labels on the equipment stating the equipment contains flammable

refrigerant.

11 RECOVERY

When removing refrigerant from a system, either for servicing or decommissioning, it is

recommended good practice that all refrigerants are removed safely. When transferring

refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are

employed. Ensure that the correct number of cylinders for holding the total system charge are

available.All cylinders to be used are designated for the recovered refrigerant and labelled for that

refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with

pressure relief valve and associated shut-off valves in good working order. Empty recovery

cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the

equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.In

addition,a set of calibrated weighing scales shall be available and in good working order. Hoses

shall be complete with leak-free disconnect couplings and in good condition. Before using the

recovery machine, check that it is in satisfactory working order, has been properly maintained

and that any associated electrical components are sealed to prevent ignition in the event of a

refrigerant release. Consult manufacturer if in doubt.

The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery

cylinder,and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery

units and especially not in cylinders.

If compressors or compressor oils are to be removed, ensure that they have been evacuated to

Содержание A007E-10C

Страница 1: ...Portable Air conditioner User s Manual R290 For Model A007E 10C Please read this user s manual carefully to ensure proper use maintenance and installation...

Страница 2: ...me of Parts 12 3 Accessories 12 4 Appearance and Function of Control Panel 13 5 Appearance and Function of Remote Control 14 6 Operation Introduction 15 7 Installation Explanations 17 8 Maintenance Ex...

Страница 3: ...urces for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain an odour Appliance shall be installed operated...

Страница 4: ...n accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry Repairs must be performed based on the recommen...

Страница 5: ...ldren shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 13 The appliance shall be installed in accordance with national wiring regulatio...

Страница 6: ...nder the supervision of the person competent in the use of flammable refrigerants 22 Do not operate or stop the unit by inserting or pulling out Die power plug it may cause electric shock or fire due...

Страница 7: ...der or CO 2 fire extinguisher adjacent to the charging area 1 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contain...

Страница 8: ...to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation...

Страница 9: ...with inert gas open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to render the unit safe This pr...

Страница 10: ...bel shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 11 RECOVERY When removing refrigerant from a system either for servicin...

Страница 11: ...that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened Ventilated enclosure see Clause GG 4 Safety of the appliance depend...

Страница 12: ...before putting into service d Decommissioning If the safety is affected when the equipment is putted out of service the refrigerant charge shall be removed before decommissioning Ensure sufficient ve...

Страница 13: ...All required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions...

Страница 14: ...Power cord 2 Front panel 6 Drainage outlet 3 Louver 7 Air inlet 4 Castor 8 Air outlet 3 Accessories Part Description Quantity Exhaust hose 1 Window Connector 1 Housing adaptor 1 Remote Controller 1 2...

Страница 15: ...optional After unpacking please check whether the above mentioned accessories are included and check their purposes in the installation introduction in this manual 4 Appearance and Function of Contro...

Страница 16: ...on off 6 Dehumidifying G Signal receiver 7 Fan A Power on off 1 Water full B Temperature up 2 High fan speed C Temperature down 3 Low fan speed D Operation MODE 4 Timer on off E Fan speed 5 Cooling F...

Страница 17: ...rby 2 As shown in Fig 2 and Fig 2a install the exhaust hose and adjust the window position well Fig 2 Fig 2a 3 As shown in Fig 6 connect drain hose well only for using heating model 4 Insert the power...

Страница 18: ...le for a cold single unit Press the Mode button till the Heat icon appears Press the or button to select a desired room temperature 16 31 Press the Fan Speed button to select wind speed 6 Timer operat...

Страница 19: ...rain hose to the bottom drain hole Fig 6 the unit can also work well If splash motor is damaged intermittent drainage can also be used Under this condition when the water full indicator lights up plea...

Страница 20: ...Fig 4 B Window Kit Installation The installation manner of window slider kit is mostly in horizontal or vertical As shown Fig 5 and Fig 5a check the min and max size of the window before the installat...

Страница 21: ...r level safety switches it controls water level When water level reaches an anticipated height the water full indicator lamp lights up If water splash motor is damaged when the water is full please re...

Страница 22: ...clogged with dust dirt the air filter should be cleaned once every two weeks Dismounting Open the air inlet grille and take off air filter Cleaning Clean the air filter with neural detergent in lukew...

Страница 23: ...Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not level or not flat enough Place the unit o...

Отзывы: