Configure and Wire Data
Follow the steps below to configure and wire the ACM Embedded Controller:
1. Set Port 1 terminating jumper (P6 Port 1 TERM Resistor) to IN position.
2. Verify Port 2, 3, 4 terminating jumpers are in the OUT position.
3. Connect the white enclosure tamper wires to /- on the ACM Embedded Controller. Polarity
does not matter.
ACM
EMBEDDED
CONTROLLER
4. Using 18 AWG wires (red for + and black for -), wire the 12-24VDC input to +Out1- on the D8P board’s
terminal block.
ACM
Embedded
Controller
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12-24VDC
IN
D8P
OUT
8
7
6
5
4
3
2
1
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
+
5. On the FPO250’s SYSFLT terminal block:
l
Wire C to Batt Fail + (22AWG).
l
Wire NO to Batt Fail - (22AWG).
ACM
Embedded
Controller
Tamper
(Input 5)
+
-
+
+
-
-
-
+
AC
Fail
(Input 6)
Batt
Fail
(Input 7)
+12-24VDC
IN
FPO250
SYS FLT
AC FLT
FAI INPUT
C NC NO
C NC NO
Configure and Wire Data