2

Connecting the Equipment

This chapter explains how to rack mount and connect the system hardware. 

Rack Mounting Guidelines and Requirements

Avid recommends installing the Avid NEXIS hardware in a rack, using the following guidelines:

If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack 
environment might be greater than room ambient. Make sure the rack environment is compatible 
with the maximum ambient temperature (Tma) specified by the manufacturer.

Avoid uneven mechanical loading. 

Make sure your rack enclosure is stable enough to prevent tipping over if using extending sliding 
rails.

Follow the equipment nameplate ratings to avoid overloading the circuits.

Maintain reliable grounding of rack-mounted equipment, especially regarding supply 
connections other than direct connections to the branch circuit (for example, power strips).

Avid airflow is from the front of the enclosure to the rear. Make sure nothing blocks airflow to 
the front panel surface and the rear.

For normal operation, maintain approximately 2 feet (0.6 meters) of open space in front of and 
behind the rack. This allows free access to the components in the rack for operating changes or 
adjustments. For service, maintain approximately 3 feet (1 meter) of open space in front of the 
rack and 2 feet (0.6 meters) of open space behind the rack. This allows for the removal of any 
component that needs to be replaced.

Allow at least 0.5 in (1.3 cm) clearance on top of the enclosure for cover removal.

w

To ensure the stability of the rack enclosure, install the heaviest equipment in the lower sections 
of the rack enclosure. Install lighter equipment in the middle and upper sections.

c

For information about power specification and dimensions see 

“Specifications and Notices” on 

page 64

Mounting the Engine or System Director Appliance

The Avid NEXIS Engines are designed for 19-inch (483-mm) rack configurations and need the 
following amounts of space in the rack:

Avid NEXIS Model

Rack Units 
Needed

Avid NEXIS | E2, Avid NEXIS | E2 SSD, Avid NEXIS | PRO, System Director 
Appliance

2

Содержание NEXIS E2

Страница 1: ...Avid NEXIS Setup and Maintenance Guide December 2019...

Страница 2: ...fic prior written permission of Sam Leffler and Silicon Graphics THE SOFTWARE IS PROVIDED AS IS AND WITHOUT WARRANTY OF ANY KIND EXPRESS IMPLIED OR OTHERWISE INCLUDING WITHOUT LIMITATION ANY WARRANTY...

Страница 3: ...the following notice applies JCifs Copyright 2004 The JCIFS Project is licensed under LGPL http jcifs samba org See the LGPL txt file in the Third Party Software directory on the installation CD Avid...

Страница 4: ...upplies 22 Chapter 2 Connecting the Equipment 28 Rack Mounting Guidelines and Requirements 28 Mounting the Engine or System Director Appliance 28 Installing the Media Packs 2U and 4U Chassis 32 Instal...

Страница 5: ...Ds 55 Replacing a Power Supply 2U and 4U 55 Replacing a Cooling Module 5U only 55 Replacing a Power Supply 5U 56 Installing a Redundant Controller 57 Dual Controller Connection Diagrams 58 About Contr...

Страница 6: ...f Conformity 69 Disposal of Waste Equipment by Users in the European Union 71 Argentina Conformity 71 Australia and New Zealand EMC Regulations 71 Japan EMC Regulations 71 Class A Equipment 71 Korean...

Страница 7: ...ndicates menu commands and subcommands in the order you select them For example File Import means to open the File menu and then select the Import command This symbol indicates a single step procedure...

Страница 8: ...ours per day 7 days per week Search this online Knowledge Base to find answers to view error messages to access troubleshooting tips to download updates and to read or join online message board discus...

Страница 9: ...ontroller two 764W power supply cooling modules PCMs two solid state system drives and one Media Pack 10 drives of either 2TB drives yielding a 20TB Media Pack or 4TB drives yielding a 40TB Media Pack...

Страница 10: ...Media Packs four Avid NEXIS PRO Engines Avid NEXIS PRO cannot be combined with Avid NEXIS E series Enterprise class Engines or the System Director Appliance Supports up to 30 connected clients 24 of...

Страница 11: ...ector Appliance and at least three of the following in the same Storage Group Avid NEXIS E2 Engines Avid NEXIS E2 SSD Engines Avid NEXIS E4 Engines Avid NEXIS E5 Engines All the Engines in the configu...

Страница 12: ...chassis serial number is printed on a label attached to the left rear chassis mounting ear The following figure shows the location of the serial number label Serial Number Label Location 2U Chassis D...

Страница 13: ...0 and 1 Drive slot numbering for storage engines is shown below In the System Director Appliance the empty slots are covered with blank plates for proper airflow and cooling 2U Chassis Rear Views and...

Страница 14: ...nd the Host Fabric section is purple Avid NEXIS PRO with 4TB SATA Drives In an Avid NEXIS PRO with a Media Pack of 4TB SATA drives the Controller is always located in slot 1 bottom and is installed up...

Страница 15: ...rives in the Avid NEXIS E4 Engine are numbered from top left 0 to bottom right 23 as shown Component Notes Power Supply Cooling Modules PCM 764W power supply and cooling fan modules The left power sup...

Страница 16: ...ot 2 as shown Rear View Features of Avid NEXIS E4 Component Notes Power Cooling Module PCM Four 580W PCMs as viewed from the rear PCM 0 top left PCM 1 top right PCM 2 bottom left PCM 3 bottom right St...

Страница 17: ...Details The following systems use a 5U chassis Avid NEXIS E5 Avid NEXIS E5 NL Description Status Purpose System Power LED Green when system is on operational Amber when system is in standby mode not o...

Страница 18: ...e has failed indicating the drawer and slot of the drive For details see 5U Chassis Drive Drawer and Sideplane Status Panel on page 11 Engine status and control panel Indicates the overall status and...

Страница 19: ...ve has failed To determine the location of the failed drive see the drive status indicator panels on the Engine Top Drawer fault indicator When amber indicates a fault in the top drawer drive cable or...

Страница 20: ...etails The rear of the Avid NEXIS E5 and Avid NEXIS E5 NL provides access to the Controllers power supplies and fans In a single Controller configuration the Controller can be in either slot but Avid...

Страница 21: ...1 Power supply modules identified in error and status messages as 0 left and 1 right Controller Typea Label Technical Details Used in and Supported Slots Avid NEXIS PRO Controller No label Four cores...

Страница 22: ...only upside down Avid NEXIS E2 SSD G2 Six cores with 32GB memory USM version 1 37 factory installed Supports a 40GbE switch connection Avid NEXIS E2 SSD Slot 1 bottom only upside down Controller 20 SD...

Страница 23: ...er Features Controller E5 NL Twelve cores with 128GB memory Supports a 10GbE switch connection Avid NEXIS E5 NL Both slots left and right Avid NEXIS E5 NL G2 Twelve cores with 128GB memory USM version...

Страница 24: ...he Avid NEXIS implementation Do not connect anything to unidentified ports POST LEDs Shown for reference only Serial Port Shown for reference only Not used Management Interface Port left port only 1Gb...

Страница 25: ...reen Network activity Left side Network speed Yellow 1000Mb s Green 100Mb s Off 10Mb s The Interconnect Interface port is used to connect two Controllers See Installing a Redundant Controller on page...

Страница 26: ...s Workspaces in an existing Cloudspaces configuration System Director Functionality The System Director maintains all information about the file system The System Director is either embedded on a Cont...

Страница 27: ...ght to send a replacement of a size that meets or exceeds the minimum partition requirements c Avid NEXIS SSD system drives cannot be removed from one system and used as a replacement in another syste...

Страница 28: ...NEXIS E5 and Avid NEXIS E5 NL the system drives are typically in slots 28 top drawer and 70 bottom drawer However there is no technical requirement for system drives to occupy any particular slots Dri...

Страница 29: ...he following figure and table Drives in the 5U Chassis The drives in the Avid NEXIS E5 and Avid NEXIS E5 NL Media Packs have one LED that indicates a drive failure 2U and 4U Drive Features Feature Sta...

Страница 30: ...one PCM fails For maximum protection from power loss both PCMs must be plugged in to separate electrical circuits or separate UPS devices and turned on With both PCMs plugged in and turned on the sys...

Страница 31: ...Power Supplies 23 764W PCM All 2U Chassis including System Director Appliance n The bottom two LEDs marked with battery icons are not used...

Страница 32: ...ower Supply LED States AC Fault Fan Fault Power Module OK DC Fault Definition n For readability a series of dashes means the LED is OFF No AC power on any PCM On On No AC power on this PCM On AC prese...

Страница 33: ...Fail Amber Power OK Green Status Off Off Off No AC power to either PSU On On Off PSU present but not supplying power Off Off On Mains AC present switch on This PSU is providing power Off Off Flashing...

Страница 34: ...on standby other PSU is OK On On On GEM software has lost communication with PSU On Off PSU has failed 2200W PSU LED Status PSU Fail Amber AC Fail Amber Power OK Green Status Fan OK Green Battery fau...

Страница 35: ...Power Supplies 27 c Leave failed power supply or cooling modules in place until you have a replacement so you maintain the proper airflow Obtain a replacement as soon as possible...

Страница 36: ...ar Make sure nothing blocks airflow to the front panel surface and the rear For normal operation maintain approximately 2 feet 0 6 meters of open space in front of and behind the rack This allows free...

Страница 37: ...o the rack using the two supplied screws 4 Insert the Media Pack drives into the empty drive slots see Installing the Media Packs 2U and 4U Chassis on page 32 5 Remove the plastic end cap covers from...

Страница 38: ...h 5 to install the other bracket rail on the opposite side of the rack 7 Make sure that the media drives are not installed in the Engine 8 With an assistant lift the Engine and place the rear of the E...

Страница 39: ...to the front of the rack through top and bottom holes of the plastic end caps as shown in the following figure 11 Using the screws from the rack mount kit or screws you supply secure the rear stabiliz...

Страница 40: ...viewing window Installing Media Pack Drives 5U Chassis The Avid NEXIS E5 or Avid NEXIS E5 NL comes with at least four Media Packs The system drives are preinstalled in the Engine in slots 28 top draw...

Страница 41: ...reseller or support depot suitable for your locale The Avid NEXIS E5 or Avid NEXIS E5 NL Engine comes with two C19 to C20 power cables in the shipping box The C19 end is a female connector which plugs...

Страница 42: ...Director Appliance to supported switches which must be networked together You cannot set up the Engine or the System Director Appliance until they are connected to suitable switches in your network C...

Страница 43: ...ork Connection from Dell N3024 Switch to Avid NEXIS E Series Controller E2 Shown 40 Gb Network Connections from Cisco Nexus 9372PX Switch to Avid NEXIS E5 n Avid NEXIS E5 NL connects to a 10GbE switch...

Страница 44: ...s are present it is enabled on both The Ethernet ports on all installed Controllers must be connected to one or more supported switches The Avid NEXIS implementation follows the Link Aggregation Contr...

Страница 45: ...Enabling Link Aggregation 37 Dual Network Connections from 40Gb Switch to Avid NEXIS E5 for LACP...

Страница 46: ...nce if applicable that belong to the same Avid NEXIS system See Understanding the Shared Name Space on page 39 Names can be up to 64 English alphanumeric characters long can contain a dash or hyphen m...

Страница 47: ...ce is present or on the System Director Appliance Specifically the System Director runs on one of the Controllers in the Engine or System Director Appliance The System Director is a service that can f...

Страница 48: ...NEXIS Engine and System Director Appliance if applicable consists of the following overall steps 1 Rack mount the hardware connect the hardware to power and to a switch and turn on the power supplies...

Страница 49: ...ersion bin Configuring the Computer s IP Address To communicate with the Avid NEXIS hardware the computer must use an IP address in the same subnet as the default IP address on the Controller 169 254...

Страница 50: ...cting to an Avid NEXIS E2 SSD Connecting to an Avid NEXIS PRO 20TB Connecting to an Avid NEXIS PRO 40TB with Purple Fascia Controller 2 Open the Windows Control Panel Network and Sharing Center then d...

Страница 51: ...ties d Click Use the following IP address and enter 169 254 10 20 with a subnet mask of 255 255 255 0 then click OK n By default the Controller IP address on every Avid NEXIS system is set to 169 254...

Страница 52: ...ame space and see Types of Controllers on page 13 for systems that support redundant controllers g If you are deploying a System Director Appliance configure it first then configure the Engines This p...

Страница 53: ...ted the Avid NEXIS software kit contents b Select the file named AvidNEXISSetup_ version bin c Click Submit The Engine installs the software and reboots displaying messages about the installation prog...

Страница 54: ...the Engine The Engine name is used to generate the hostnames for the Controllers which appear in the fields below for Top and Bottom Controllers in the Avid NEXIS E2 Avid NEXIS E4 and System Director...

Страница 55: ...ironment c In the DNS Search List field you can enter alternate DNS names separated by spaces that are used in your environment These will be used to help resolve the System Director name in a browser...

Страница 56: ...hat will belong to the same Avid NEXIS system have the same Storage System Name 13 When you have configured all the Engines disconnect the computer from the Engine You can optionally restore the compu...

Страница 57: ...e all conventional ESD precautions when handling plug in modules and components You can replace most hardware components without disrupting the system operation Collecting Logs for Customer Care To he...

Страница 58: ...ive as soon as possible If both system drives in the same Engine fail the Engine stops operating because no metadata for writes can be recorded If the Engine is part of a multi Engine configuration th...

Страница 59: ...ystem Director Appliance as a replacement The system drives operate as a pair and contain metadata from the original system they belonged to Using a system drive from another chassis even if new and n...

Страница 60: ...The red arrows on the locks point inwards if the locks are disengaged Unlock them if necessary by rotating them counterclockwise using a screwdriver with a Torx T20 bit 4 Push the drive carrier latch...

Страница 61: ...ive into the slot with the drive capacity label facing towards you 3 Push the drive downwards and hold it down while sliding the drive carrier plate in the direction shown in the following figure This...

Страница 62: ...Two drive slots are reserved for the system drives If your Avid NEXIS E4 contains only one Media Pack you can add another inserting the drives in any order in any available slots The system combines...

Страница 63: ...s on page 22 for more information Replacing a Power Supply 2U and 4U The power supplies in the 2U and 4U chassis include cooling fans as well as supplying power to the system The power supplies are bi...

Страница 64: ...on the right hand side 2 Slide the cooling module into its slot until the latch clicks in place The Engine will automatically detect and make use of the new unit Replacing a Power Supply 5U In Avid N...

Страница 65: ...ngine is not supported For highest availability install a redundant Controller in all Engines and System Director Appliance if applicable in the entire shared storage system However you can install a...

Страница 66: ...is installed in the right hand slot See 5U Chassis Rear View Details on page 12 c Slide the replacement Controller into its slot until it will go no further d Close the lever until it clicks in place...

Страница 67: ...Installing a Redundant Controller 59 Connecting Two Controllers in a 2U Chassis Connecting Two Controllers in a 4U Chassis Connecting Two Controllers in a 5U Chassis...

Страница 68: ...e information In particular make sure that both Controllers in an Engine have the same amount of memory Installing Controllers with different memory capacities in the same Engine is not supported n Ma...

Страница 69: ...erform a Remove Redistribution of the failed Engine to recreate the mirrored Workspaces assuming there is enough free space on the remaining Engines See the Avid NEXIS Administration Guide for informa...

Страница 70: ...re using a Controller in the same shared storage system the IP address and software is recognized by the System Director and needs no reconfiguration 4 Connect all Ethernet and power cables to the new...

Страница 71: ...assis reboots 7 After the chassis restarts reopen the Agent and configure the new system with the following information a Enter the same Storage System Name as the existing shared storage system it is...

Страница 72: ...PRO 483 mm 19 in 630 mm 24 8 in 88 9 mm 3 5 in 26 kg 57 2 lb with drives Avid NEXIS E4 483 mm 19 in 630 mm 24 8 in 177 8 mm 7 in 46 kg 101 41 lb with drives Avid NEXIS E5 Avid NEXIS E5 NL 483 mm 19 i...

Страница 73: ...m 0 to 10 000 ft 300 to 12 192 m 1000 to 40 000 ft Component Operational Shock Operational Vibration Non operational Shock Non operational Vibration Relocation Vibration Acoustics System Director Appl...

Страница 74: ...t country state and local electrical codes Component EMC Safety System Director Appliance FCC pt15B Class A EN55022 Class A CISPR 22 Class A EN 55024 CISPR24 EN61000 3 2 3 CNS13438 EN IEC UL 60950 1 C...

Страница 75: ...he main power switch should remain accessible after installation Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer and birth defects or other repr...

Страница 76: ...erence to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television rece...

Страница 77: ...xceed the exposure limit of the eye and cannot cause harm Standard to which conformity is declared Class 1 LED Product per IEC 60825 1 2007 European Union Declaration of Conformity Declaration of conf...

Страница 78: ...ta declaraci n es conforme a la s norma s u otro s documento s normativo s waarnaar deze verklaring verwijst aan de volende norm en of richtlijn en beantwoordt a cui si riferisce questa dichiarazione...

Страница 79: ...will help conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment For more information about where you can drop off your waste equipment fo...

Страница 80: ...use In the event that it has been mistakenly sold or purchased please exchange it for equipment certified for home use Taiwan EMC Regulations Taiwan EMC Regulations BSMI Class A EMC Warning Warning St...

Страница 81: ...rovision of marking to warn USERS where access to hot parts is unavoidable High temperature warning marking you may use the following high temperature warning marking 4 Mechanical hazards Injury may r...

Страница 82: ...ors and fumes Examples of measures to reduce risks include Avoiding the use of constructional and consumable materials likely to cause injury by contact or inhalation during intended and normal condit...

Страница 83: ...nt there shall be a marking close to the battery or a statement in the servicing instructions The marking or statement shall include the following or similar text 11 Warning to service persons Suitabl...

Страница 84: ...Taiwan EMC Regulations 76 The following or similar wording is regarded as suitable...

Страница 85: ...trol panel 9 front view 9 rear view 12 sideplane panel 11 Avid NEXIS platforms overview 1 Avid NEXIS PRO Control panel 9 drive numbering 4 front view 4 rear view 4 Avid NEXIS SDA Control panel 9 front...

Страница 86: ...tion 32 replacement size 52 type 19 E EIA rack units 28 Enabling link aggregation 36 Engine adding to existing storage system 62 configuring 44 connecting to switch 34 cooling modules 22 front view 2U...

Страница 87: ...IC teaming 34 See Link aggregation NTP servers IP addresses 38 O Online support viii P Port trunking See Link aggregation Power supplies Engines 22 LEDs 22 location 4 7 12 removing 55 replacing 55 sta...

Страница 88: ...e about 39 allowed characters 38 defined 38 length 38 Supported configurations Media Mirroring Engine protection for Workspaces 2 with embedded System Director 2 with System Director Appliance 2 Switc...

Страница 89: ...twork Drive Burlington MA 01803 2756 USA Technical Support USA Visit the Online Support Center at www avid com support Product Information For company and product information visit us on the web at ww...

Отзывы: