3.2 Truck inbound-outbound operations
3.2.4 Using setpoints
Setpoints are values (weight) at which outputs are triggered automatically. Outputs can
control relays connected to valves, lights, other machinery, etc. Setpoint outputs can
be configured in the setpoint menu shown in
Figure 3.1
.
Figure 3.1 Setpoint menu
Follow these steps to configure the outputs:
1.
Press
SETUP
…
out1
is displayed. This is the weight value for setpoint 1. You can access
out2
or
out3
by pressing the
UNITS
key. The following instructions
apply to any of these three outputs.
2.
Press
SELECT
…
Edit X
is displayed.
X
being the number of output.
3.
Press
UNITS
…
ModE X
is displayed. This menu item sets the function of the output.
Mode selection must be made before entering the Out value.
Out1
Out2
Out3
Edit X
Mode X
Act Abv
Act Bel
Act In
Act Out
Outx Lo
Outx Hi
Setpnt
Key in
value
Key in
value
Press
SETUP
Key in
value
Mode selection:
Act Abv or Act Bel
Mode selection:
Act In or Act Out
Default Setpoint operation
Mode = Active Above
Outputs must be enabled for setpoints to operate. See the Service Manual:
Below Configured Value:
Outputs are OFF
Annunciators are OFF
Above Configured Value:
Outputs are ON
Annunciators are ON
The setpoint outputs and setpoint annunciators logic state can be inverted from their
default settings. Refer to details in the password protected menu settings in the section
titled
Setpoint on page 41
.