INSTALLATION
GB
7
Visit our website at Emerson.com/AVENTICS
10 V
20 mA
20 mA
0
0
4
5 V
10 mA
12 mA
50 mV
0.1 mA
4.08 mA
+50% PMR
-50% PMR
Setpoint span
The pressure span of the setpoint can be changed via the
DaS
software. Switch to "Custom" in the "Setpoint setting"
section. The span is b10 and +150 %.
CAUTION
: Outlet pressures above the maximum outlet pressure (PMR) are not controlled by the valve, i.e. the max.
outlet pressure is limited to the PMR.
In order to avoid damaging the sensor,
the supply pressure must always be less than the maximum inlet pressure
(MAP)
(see Table).
The span can be set to max. 100% of the maximum outlet pressure (PMR). It can only be decreased.
3.
ANALOG SETPOINT - OUTLET PRESSURE
Setpoint offset
The pressure setpoint zero can be changed via the
DaS
software. Switch to "Custom" in the "Setpoint setting" section.
The zero range is max. -50 ... +100 %.
Span adjustment
Offset adjustment
Max.
outlet pressure
PMR
SHUT-OFF
Max.
outlet pressure
PMR
(bar)
Max.
inlet pressure
MAP
(bar)
0 - 100 mbar
2
0 - 500 mbar
2
0 - 1 bar
2
0 - 2 bar
3
0 - 3 bar
8
0 - 5 bar
8
0 - 6 bar
12
0 - 10 bar
12
0 - 12 bar
14
0 - 16 bar
1)
18
0 - 20 bar
1)
22
0 - 30 bar
2
)
40
0 - 50 bar
2)
60
1)
For DN3 and DN6 only.
2)
For DN6, Ms, only.
10 V
20 mA
20 mA
0
0
4
50 mV
0.1 mA
4.08 mA
Fac
tor
y
se
tting
: 0%
Max. outlet
pressure
PMR
SHUT-OFF
Max. outlet
pressure
PMR
Fac
tor
y
se
tting
: 100%
50% s
etting