AVENTICS

 | ED05 | R414010201–BAL–001–AA | English

19

Setting the set point

O

Stipulate the desired set point with the controller.

Control

You can continually adjust the pressure once you have 
connected the pneumatic and electrical supply on the 
ED05 pressure regulator. To do this, the ED05 pressure 
regulator is controlled via a controller using a set point. 
The electronics compare the set point with the outlet 
pressure, which is measured by a pressure sensor, and 
generate a control variable that is used to control the 3/3 
directional valve with U/I converters and a proportional 
solenoid. This sets the stipulated pressure.

Function block diagram for a ED05 pressure regulator 

See Fig.

Selecting the correct supply pressure

A permanent deviation will occur if the supply pressure is 
less than the outlet pressure stipulated by the electrical 
set point. The electronics will reduce the power 
consumption and thus the max. nominal width to prevent 
the ED05 pressure regulator from heating up.

O

Always select a supply pressure that is higher than the 
outlet pressure.

Displays

The ED05 pressure regulator has two LEDs: 

W

Green LED “POWER” (

9

)

W

Red LED “STATUS” (

8

)

CAUTION

Danger of burns caused by hot coils

Touching the valve coils during operating may lead to 
burns.

O

Let the device cool off before disassembling it.

O

Do not touch the device during operation.

5

1

Meaning of the “POWER” LED

Meaning of the LED “STATUS”

If the green “POWER” LED (

9

) is illuminated and the red 

“STATUS” LED (

8

) is not illuminated, the ED05 pressure 

regulator is operating correctly and the supply voltage is 
within the tolerance range.

8

Disassembly and Exchange

LED status

Meaning

LED is off

The supply voltage is less than 8 V.

Flashes
(frequency 
approx. 
0.5 Hz)

The supply voltage is less than 14.4 V, 
the standard function is switched off. 
The adjusted pressure is 0 bar.

Flashes 
(frequency 
approx. 
1 Hz)

The supply voltage is less than 16.8 V, 
the device operates with reduced 
performance.

Flashes 
(frequency 
approx. 
20 Hz)

The supply voltage is larger than 33.6 V 
and larger than the permitted range. 
The device operates with reduced 
performance.

LED is 
illuminated

Device is ready for operation.
Full performance in the supply voltage 
range from 16.8 V ... 33.6 V.

LED status

Meaning

LED is off

The device operates correctly.

Flashes

Error during the self-test , the device 
does not function.

NOTICE

Disconnecting plugs when under voltage will damage 
the device

Large differences in potential occur when disconnecting 
plugs under voltage, which could damage the device.

O

Make sure the relevant system component is not 
under voltage before disassembling the device.

1

1

Содержание ED05 Series

Страница 1: ...Betriebsanleitung Operating instructions Notice d instruction R414010201 2017 12 Replaces DE EN FR Druckregelventil Pressure regulator R gulateur de pression ED05 Rail...

Страница 2: ...A R414010527 11 bar 0 6 bar 0 10 V 0 10 V R414010528 11 bar 0 6 bar 4 20mA 4 20 mA Darstellung von Informationen Warnhinweise In dieser Dokumentation stehen Warnhinweise vor einer Handlungsabfolge bei...

Страница 3: ...Produkte in sicherheitsrelevanten Anwendungen eingebaut oder verwendet werden k nnen unbeabsichtigte Betriebszust nde in der Anwendung auftreten die Personen und oder Sachsch den verursachen k nnen S...

Страница 4: ...nlagenteil drucklos und spannungsfrei bevor Sie das Ger t montieren bzw Stecker anschlie en oder ziehen Sichern Sie die Anlage gegen Wiedereinschalten O Stellen Sie vor dem Einschalten sicher dass die...

Страница 5: ...nd 1 2 3 4 Bevor Sie mit der Montage beginnen O Schalten Sieden relevanten Anlagenteil spannungsfrei und drucklos O Lassen Sie das ED05 Druckregelventil vor dem Einbau einige Stunden akklimatisieren d...

Страница 6: ...erbelegung den Einbaustecker XPC M12 aufgef hrt ist 3 3 1 Einbaubedingungen Einbaulage Siehe Abb Auf Montageplatte montieren und Pneumatik anschlie en 1 Setzen Sie die beiden Schrauben 14 z B M6 x 75...

Страница 7: ...Verschl sse der Steckverbindungen dicht sind O ffnen Sie niemals das Ger t Fehlfunktion durch lhaltige Atmosph re l kann die Geh usebel ftungs ffnung verschlie en Dadurch verschiebt sich die Kennlini...

Страница 8: ...Ventilspulen Ber hren der Ventilspulen im laufenden Betrieb kann zu Verbrennungen f hren O Lassen Sie das Ger t abk hlen bevor Sie es ausbauen O Ber hren Sie das Ger t nicht im Betrieb 5 1 Bedeutung...

Страница 9: ...ruckregelventil ist keine besondere Pflege erforderlich Wenn Sie das Ger t reinigen wollen m ssen Sie Folgendes beachten ED05 Druckregelventil warten Bei normalen Umgebungsbedingungen Das ED05 Druckre...

Страница 10: ...Entl f tung offen ist Luft entweicht h rbar Dichtung an Eingangs oder Ausgangsanschluss fehlt oder ist besch digt Dichtung ber pr fen und ggf austauschen Undichtigkeit zwischen ED05 Druckregelventil...

Страница 11: ...onskoordination 12 Technische Daten Allgemeine Daten Die kompletten technischen Daten entnehmen Sie bitte dem Online Katalog unter www aventics com pneumatics catalog Pneumatik Lineare Kennlinie von S...

Страница 12: ...h ISO 228 1 2000 und 1 4 27 NPTF Beschreibung Max Anzugsmomente 1 Befestigungsschrauben Geh usedeckel 2 Ventilspule 3 Ausgangsanschluss 2 G1 4 1 10 Nm 4 Eingangsanschluss 1 G1 4 1 10 Nm 5 Abluftanschl...

Страница 13: ...ung Max Anzugsmomente 3 Ausgangsanschluss 2 G1 4 10 Nm 4 Eingangsanschluss 1 G1 4 10 Nm 5 Abluftanschluss 3 G1 4 10 Nm 14 Befestigungsschrauben 00122945 16 15 3 Auf Grundplatte montieren und Pneumatik...

Страница 14: ...itionen auf Anfrage 5 24 23 25 M N O 00125308 CONTROLLER 24 V U P U I Funktionsplan ED05 Druckregelventil 1 Eingangsanschluss f r Versorgungsdruck 2 Ausgangsanschluss 3 Abluftanschluss Beschreibung 23...

Страница 15: ...nal width 5 DC Direct current English 1 About this Documentation Documentation validity This documentation applies in principal to all pressure regulators of the series ED05 Rail and thus for the foll...

Страница 16: ...red improper and is not permitted If unsuitable products are installed or used in safety relevant applications this may result in unintended system operating states that may lead to injuries and or eq...

Страница 17: ...ake sure the relevant system component is not under pressure or voltage before assembling or when connecting and disconnecting plugs Protect the system against being restarted O Ensure personnel safet...

Страница 18: ...orming work on the system O Connect or disconnect plug connectors only if all relevant system parts are without voltage 1 2 3 4 Before assembly O Make sure the relevant system part is not under voltag...

Страница 19: ...able containing the plug assignment of the integrated XPC plug M12 for this 3 3 1 Installation conditions Mounting orientation See Fig Assemble on a mounting plate and connect the pneumatics 1 Insert...

Страница 20: ...characteristic curve O Never operate the device in an atmosphere containing oil 00125293 5 1 2 3 4 Switching on the pneumatic and electrical supplies Commissioning the ED05 pressure regulator 1 Switc...

Страница 21: ...he valve coils during operating may lead to burns O Let the device cool off before disassembling it O Do not touch the device during operation 5 1 Meaning of the POWER LED Meaning of the LED STATUS If...

Страница 22: ...er pressure or voltage before assembling or when connecting and disconnecting plugs Protect the system against being restarted O Ensure personnel safety before switching on the device 1 Maintaining th...

Страница 23: ...open Air is audibly escaping Seal at the inlet connection or outlet connection is missing or damaged Check the seal and exchange if necessary Leaks between the ED05 pressure regulator and connected pr...

Страница 24: ...s Isolation coordination 12 Technical Data General data Full technical data can be found in our online catalog at www aventics com pneumatics catalog Pneumatics Linear characteristic curve of set poin...

Страница 25: ...ing to ISO 228 1 2000 and 1 4 27 NPTF Description Max tightening torques 1 Housing cover mounting screws 2 Valve coil 3 Outlet connection 2 G1 4 1 10 Nm 4 Inlet connection 1 G1 4 1 10 Nm 5 Exhaust air...

Страница 26: ...e pneumatics Description Max tightening torques 3 Outlet connection 2 G1 4 10 Nm 4 Inlet connection 1 G1 4 10 Nm 5 Exhaust air connection 3 G1 4 10 Nm 14 Mounting screws Assemble on the base plate and...

Страница 27: ...ounting orientation 1 Top 2 Vertical Other positions on request Function block diagram ED05 pressure regulator 1 Inlet connection for supply pressure 2 Outlet connection 3 Exhaust air connection Descr...

Страница 28: ...0 10 V 0 10 V R414009095 11 bar 0 3 5 bar 4 20 mA 4 20 mA R414010527 11 bar 0 6 bar 0 10 V 0 10 V R414010528 11 bar 0 6 bar 4 20 mA 4 20 mA Pr sentation des informations Consignes de danger Dans la p...

Страница 29: ...ations qui rel vent de la s curit des tats d exploitation incontr l s peuvent survenir dans ces applications et entra ner des dommages corporels et ou mat riels Par cons quent utiliser des produits da...

Страница 30: ...cern e de l installation hors tension et hors pression avant de monter l appareil ou de le brancher ou d brancher Prot ger l installation de toute remise en marche O Avant la mise sous tension s assur...

Страница 31: ...es pi ces concern es de l installation sont hors tension 1 2 3 4 Avant de commencer le montage O Mettre la partie pertinente de l installation hors tension et hors pression O Avant la pose laisser le...

Страница 32: ...r incorpor XPC M12 3 3 1 Conditions de pose Position de montage Voir fig Montage sur plaque de montage et raccordement pneumatique 1 Introduire les deux vis 14 p ex M6 x 75 selon DIN EN ISO 4762 ancie...

Страница 33: ...caler la courbe caract ristique O Ne jamais faire fonctionner l appareil dans une atmosph re charg e en huile 00125293 5 1 2 3 4 Mise en marche de l alimentation pneumatique et lectrique Mise en servi...

Страница 34: ...pareil 1 1 AVENTICS ED05 R414010201 BAL 001 AA Fran ais 31 R glage de la valeur consigne O Indiquer la valeur consigne souhait e l aide de la commande Commande Lorsque les alimentations pneumatique et...

Страница 35: ...toute remise en marche O Avant la mise sous tension s assurer que la s curit du personnel est garantie 1 Maintenance du r gulateur de pression ED05 En cas de conditions ambiantes normales En fonction...

Страница 36: ...ent d air audible Le joint sur le raccord d entr e ou de sortie est manquant ou endommag V rifier le joint et le remplacer le cas ch ant Fuite entre le r gulateur de pression ED05 et la conduite de pr...

Страница 37: ...ques Donn es g n rales Toutes les donn es techniques sont disponibles dans notre catalogue en ligne l adresse www aventics com pneumatics catalog Syst me pneumatique Courbe caract ristique lin aire de...

Страница 38: ...et 1 4 27 NPTF Description Couple de serrage max 1 Vis de fixation couvercle de bo tier 2 Bobine de distributeur 3 Raccord de sortie 2 G1 4 1 10 Nm 4 Raccord d entr e 1 G1 4 1 10 Nm 5 Orifice d chappe...