12.21
15
Hot water coils with electronic controls - heating mode (SIDE MODULE) 2 pipes
Electric post heater with electronic controls (FACTORY FITTED)
Chilled water coils with electronic controls - cooling mode (SIDE MODULE) 2 pipes
Size
Item ref. number
Supply
Capacity
[kW]
Air 20°C
80 HR
Water
7/12°C
Pres-
sure
drop
Water
[kPa]
Water
connection
(female)
Electric
power
intake
[W]
Current
[A]
Air flow rate
[m3/h]
47
ICWD
AHDCOLCWC131
230V - 50Hz
3.84 kW
0.4
3/4”
50
0.4
350
77
AHDCOLCWC 132
5.40 kW
0.5
3/4”
87
0.7
550
127
AHDCOLCWC 133
9.21 kW
0.7
3/4”
150
1.2
950
Size
Item ref. number
Supply
Capacity
[kW]
Current
[A]
∆T [°C]
Air flow
rate
[m3/h]
47
IEHD
AELEH000808
230V - 50Hz
0.75
6,5
11
400
77
6
700
127
AELEH000809
2
13
7
1200
Size
Item ref. number
Supply
Capacity
[kW]
Air 18°C
20 HR
Water
80/70°C
Pres-
sure
drop
Water
[kPa]
Water
connection
(female)
Electric
power
intake
[W]
Current
[A]
Air flow
rate [m3/h]
47
IHWD
AHDCOLHWC131
230V - 50Hz
6
14,6
3/4”
50
0.4
350
77
AHDCOLHWC132
8.9
12.4
3/4”
87
0.7
550
127
AHDCOLHWC133
15.4
16.4
3/4”
150
1.2
950
Size
Item ref. number
Supply
Capacity
[kW]
Current
[A]
Air flow
rate [m3/h]
47
IPEHD
AELEH000807
230V - 50Hz
0.9
7.8
400
77
700
127
AELEH000810
1,5
9,7
1200
Electric preheater with electronic controls (FACTORY FITTED)
9.1 INTERNAL ACCESSORIES
A special execution is with internal heating/cooling accessories possible on request. Due to the continuous effort to
enlarge the accessory range this list might be not complete/updated. For more details see specific IOM of accessories
on internet site.
Size
Item ref. number
Supply
Capacity
[kW]
Current
[A]
Air flow
rate
[m3/h]
47
IDXD
AHDGASDXD18
230V - 50Hz
2,7
0.4
400
77
AHDGASDXD20
4.5
0.7
700
127
AHDGASDXD22
6,1
1.2
1200
Direct expansion coil with electronic controls (SIDE MODULE)
Avensys srl reserves the right to make changes without prior notice