Prerequisites for installing the Avaya Virtual Services Platform 4000 in an equipment rack:

• Ensure that you have a space of 1.75 inches (4.45 centimeters) in height for each switch in an

EIA or IEC-standard 19-inch (48.2-centimeter) equipment rack.

• The rack is bolted to the floor and braced if necessary.

• The rack is grounded to the same grounding electrode used by the power service in the area.

The ground path must be permanent and must not exceed 1 Ohm of resistance from the rack
to the grounding electrode.

1. Attach the L-bracket to each side of the switch using a #2 Phillips screwdriver as illustrated

below.

2. Slide the switch into the rack as illustrated.

3. Insert and tighten the rack-mount screws.

July 2015

Installation Job Aid for Avaya VSP 4000 4450GSX series     

5

Содержание VSP 4000GSX Series

Страница 1: ...or or reseller Notices Notice paragraphs alert you about issues that require your attention The following paragraphs describe the types of notices used in this guide Note Notes provide tips and useful...

Страница 2: ...dio interference in which case the user may be required to take appropriate measures Caution When mounting this device in a rack do not stack units directly on top of one another in the rack Each unit...

Страница 3: ...upply At least 2 inches 5 08 cm on all sides of the switch unit for ventilation Adequate space at the front and rear of the switch for access to cables If you are installing a single VSP 4000 switch o...

Страница 4: ...le or shelf as illustrated below Allow at least 2 inches 5 1 centimeters on each side for proper ventilation and at least 5 inches 12 7 centimeters at the back for power cord clearance Installing the...

Страница 5: ...ced if necessary The rack is grounded to the same grounding electrode used by the power service in the area The ground path must be permanent and must not exceed 1 Ohm of resistance from the rack to t...

Страница 6: ...ustrated below 3 Slide the transceiver from the module slot 4 If the transceiver does not slide easily from the module slot use a gentle side to side rocking motion while firmly pulling the transceive...

Страница 7: ...hich is lower Table 2 DC power specifications 4450GSX DC Input Current 25A Input Voltage 12VDC Power Consumption Typical 116W Maximum 164 6W Thermal Rating 508 BTU Hr Power supply power specifications...

Страница 8: ...W on 12 ports 835W with one power supply 1835W with two power supplies 17 8W or 32 4W 802 3 at 1 power supply The VSP 4450GSX PWR can support 802 3af 17 8W or 32 4W on each port with one power supply...

Страница 9: ...ceable power supplies 1 If a blanking plate covers the required power supply slot remove the blanking plate before attempting to insert the power supply 2 Insert each power supply into a rear power su...

Страница 10: ...5P male plug UL recognized UL stamped on cord jacket CSA certified CSA label secured to the cord 100 or 120VAC 50 60 Hz Single phase United Kingdom BS1363 male plug with fuse Harmonized cord 240VAC 50...

Страница 11: ...Figure 3 DC power cable Figure 4 DC power cord housing unit with terminals July 2015 Installation Job Aid for Avaya VSP 4000 4450GSX series 11...

Отзывы: