Modules on the VSP
9010
Module LED color
Alarm threshold
Shutdown threshold
alarm threshold by one
degree.
exceeds the shutdown
threshold by one degree.
Green
Alarm clears after the
temperatures of the
modules are at 68 °C.
—
Second generation I/O module sensors
Inlet and outlet sensors
Blinking red
79 °C
At 80 °C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
84 °C
At 85 °C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
Green
Alarm clears after the
temperatures of the
modules are at 78 °C.
—
Field Programmable Gate
Array (FPGA) sensors
Blinking red
90 °C
At 91 °C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
95 °C
At 96 °C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
Green
Alarm clears after the
temperatures of the
modules are at 89 °C.
—
Fabric Adapter (FA)
sensors
Blinking red
105°C
At 106°C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
110°C
At 111°C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
Green
Alarm clears after the
temperatures of the
modules are at 104°C.
—
Bringing the module online
If a module shuts down due to heat, you must intervene to bring the slot back online. After you
correct the temperature issue and the heat condition clears, you must bring the module back online.
The module does not go online again unless you re-enable the module. After CP, SF, or I/O
modules shut down, use the
sys power slot {slot[-slot][,...]}
command to bring the
module back online.
Virtual Services Platform 9010
March 2015
Installing Cooling Modules in Avaya VSP 9000
15