Appendix
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 29
10.2 BX-10M Control Panel variants
BX-10M can be supplied with variants of the system program adapted
to particular markets and special functions, e.g. the agricultural industry,
maritime installations, and control panels to which intruder detectors
can be connected.
Special program versions for specific countries are also available. If the
program features for the individual country do not vary in relation to the
Norwegian version, then only the front panel notation (language) is
different.
The following versions are available:
BX-10 Standard
version,
Norwegian.
BX-10L Agricultural
version,
Norwegian.
BX-10I
Fire and intruder version, Norwegian.
BX-10LI
Agricultural version with fire and intruder
detection, Norwegian.
BX-10M
Maritime version. 230VAC, small cabinet.
BX-10M1
Maritime version. Approved according to
EN60945. 110 - 230VAC. Double-sized cabinet.
Language variants of standard versions are denoted by BX-10/xx,
where xx is the language code.
Brief explanation of what is unique about the different control panel
variants.
BX-10:
Standard Norwegian version (program P1BX10-110-xx)
This version has an automatic safety coupling for disabled
functions after 12 and 24 hours. This means that:
•
disabled detector zones (loops) are automatically
restored after 24 hours (oversight safety coupling).
This automatic coupling overrides any disabling via an
external trip switch with a closed contact.
•
disabling of immediate detection (D/N function) is
automatically restored after 12 hours.
BX-10L:
Agricultural version (P1BX10-112-xx)
This version has a 4-hour automatic safety coupling feature
for disabled loops. Otherwise it is identical to the standard
version.
BX-10I:
Fire and intruder detection (P1BX10-113-xx).
This version does not have automatic safety coupling for
loop 4. This enables intruder detectors on loop 4 to be
disabled with the possibility for manual disabling/restoring
via an external code switch on input 4.
BX-10LI:
Agricultural version with fire and intruder detection
(P1BX10-113-xx).
Combination of functions for BX-10L and BX-10I versions.
Содержание BX-10M1
Страница 36: ......