Autronica AutroSense Nano Скачать руководство пользователя страница 22

Optional: Communications Card 

Installation Handbook, AutroSense Nano 116-P-ASENSENANO/DGB, 2010-08-09, Autronica Fire and Security AS 

 

Page 20

 

configure the detector except to enter time and date settings 
for the detector event log and chart recording to be viewed in 
the Remote Software. The detector does not incorporate a real 
time clock, so the time and date need to be re-entered if the 
detector is powered down for any reason.   
Installation of the Communications Card also provides the 
detector with RS-485 network communication via the A, B and 
SCREEN terminals on the detector main board. This can be used 
for simple remote display indication or integration into a larger 
site wide management and display system, separate from the 
local Fire Detection and Alarm system connection. The 
Communications Card has short circuit bus isolation but does 
not have an RS485 repeater 

Содержание AutroSense Nano

Страница 1: ...116 P ASENSENANO DGB 2010 08 09 Installation Handbook AutroSense Nano Aspirating Smoke Detector...

Страница 2: ...ility for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire and...

Страница 3: ...1 Introduction 3 2 Outside the Detector 4 3 Inside the Detector 6 4 Installation Mechanical 8 5 Installation Drilling Template 9 6 Installation Electrical 10 7 Installation Pipework 12 8 Configuratio...

Страница 4: ...NSENANO DGB 2010 08 09 Autronica Fire and Security AS Page 2 0832 Autronica Fire and Security Haakon VII s gt 4 N 7483 Trondheim Norway 10 0832 CPD 1473 EN 54 20 2006 Aspirating smoke detectors for fi...

Страница 5: ...rdous voltages _______________________________________________________ If this detector is to form part of an approved fire detection system its power must be supplied from a certified power supply ty...

Страница 6: ...inates to indicate that the smoke level has passed the detector s Pre Alarm threshold and the normally open PRE ALARM relay contacts have closed 4 Fault illuminates to indicate a fault condition and t...

Страница 7: ...amaged or disconnected It can also be caused by certain kinds of internal systems faults which appear in the detector s event log as process errors NB if the FAULT LED is illuminated but none of the a...

Страница 8: ...nd the detector will indicate a FLOW fault 2 Main PCB No user serviceable parts NB The PCB is fixed in place with 5 off M3 x 6 screws The detector must not be operated with any of the screws missing a...

Страница 9: ...parts Do not remove this from the detector due to the risk of exposure to the laser 7 Replaceable Dust Filter This simply slides in and out of its mounting The filter and its replacement have IN writ...

Страница 10: ...oning NB Ensure the detector is fixed to a flat surface otherwise the enclosure will twist Cable Entries 2x 20mm Conduit Holes e g for 20mm packing glands Drilling guides are provided for drilling two...

Страница 11: ...bottom of the detector The screw is M6 x 15 panhead Pozidrive Upper clearance Remember to leave sufficient clearance above the detector for the cable glands and pipe inlet stubs 3 x wall fixing screw...

Страница 12: ...Do not connect 0V to EARTH Use screened cable with screen connected to the detector EARTH terminal DIP Switch 7 OFF connect to PSU fault relay Normally Closed contacts for PSU monitoring DIP Switch 7...

Страница 13: ...ANO DGB 2010 08 09 Autronica Fire and Security AS Page 11 The INPUT terminals are set by default to monitor the power supply If power supply monitoring and ClassiFire Override are not required fit a w...

Страница 14: ...rotected area and detector are at the same atmospheric pressure it is good practice to fit a pipe stub with a bend to the exhaust to prevent debris falling into the detector Do not glue the pipe into...

Страница 15: ...Changing the Alarm Factor starts a new FastLearn cycle during the initial 15 minute learning period the detector is incapable of reporting an alarm and will take 24 hours to achieve optimum performanc...

Страница 16: ...mal sensitivity by 50 NB in the factory default condition the switch is set to OFF power supply monitoring This will give a fault condition if there is an open circuit on the INPUT terminals so fit a...

Страница 17: ...er up detector and wait for 15 minute FastLearn cycle to finish steady OK LED when complete Disconnect detector from fire panel if required Check test connections to main Fire Detection and Alarm Syst...

Страница 18: ...ges due to building upgrades Check detector for contamination and clean if necessary Check maintenance logs for issues and rectify as appropriate Check transport times against original records signifi...

Страница 19: ...09 Autronica Fire and Security AS Page 17 Notes It is prudent to disconnect or isolate the detector from the fire panel during maintenance to prevent unintentional alarm activations The detector shoul...

Страница 20: ...during or immediately after smoke tests Reinitiate FastLearn with the detector in a clean environment The Alarm Factor is too high Change the Alarm Factor to a lower more sensitive setting Nuisance f...

Страница 21: ...e detector event memory to review previous or current events such as detector sensitivity The detector internal Chart Recorder may also be accessed for analysis of detector behaviour see separate Remo...

Страница 22: ...so the time and date need to be re entered if the detector is powered down for any reason Installation of the Communications Card also provides the detector with RS 485 network communication via the...

Страница 23: ...Sensitivity Range 0 4 to 25 obscuration metre Detection Principle Laser Light Forward Scattering Mass Detection Maximum Number of Sampling Holes Class A 2 Class B 4 Class C 10 Maximum Sampling Pipe Le...

Страница 24: ...Technical Data Installation Handbook AutroSense Nano 116 P ASENSENANO DGB 2010 08 09 Autronica Fire and Security AS Page 22...

Страница 25: ...Security AS 14 Reader s Comments Please help us to improve the quality of our documentation by returning your comments on this manual Title Installation Handbook AutroSense Nano Ref No 116 P ASENSENAN...

Страница 26: ...ity AS Suggestions for improvements Thank you We will investigate your comments promptly Would you like a written reply Yes No Name Title Company Address Telephone Fax Date Please send this form to Au...

Страница 27: ...Reader s Comments Installation Handbook AutroSense Nano 116 P ASENSENANO DGB 2010 08 09 Autronica Fire and Security AS...

Страница 28: ...nica Fire and Security ASsures the excellence of our products and services Our products are CE marked and developed for worldwide standards and regulations and conform to the CEN regulation EN54 Our q...

Отзывы: