Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 26
All other panels
(Operator Panel BS-210, Repeater Panel BS-
211, Fire Brigade Panel BU-210, Information Panel BV-210)
If in-wall cabling is used
, feed the external cables through the hole
of the bracket before mounting the panel (the cables should
preferably stick out approximately 25cm from the surface of the
wall).
or;
if on-wall cabling is used
, remove the appropriate knockouts on the
top, bottom, left or right hand side of the panel.
Before mounting the panel on the bracket, connect all external
cables to the correct terminal points (the panel bus cable). Refer
also to
Description of Terminal Points – Main Board,
chapter 9.8
Verify that all cables are correctly and properly connected before
connecting the mains cable and the internal battery cables.
Verify that the switchsetting on dipswitch S2.4 is correct according
to the panel in question (land market/BS-200 or maritime market
BS-200M). Refer to dipswitch S2.4.
Switch
Description
S2.4
Market selection. Select between Land (BS-200) and Maritime
(BS/200M)
Land: S2.4 ON
Maritime: S2.4 OFF
Содержание Autroprime
Страница 84: ......
Страница 85: ...Appendix 116 P APRIME2 INSTAL DGB Rev C 2016 29 02 ...