Cable Specifications
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 23
Panel 3
(BS-210/BU-210
etc)
Cable 2b
Redundant Power between external panels
Panel 1
(BSA-200/J1)
Terminals
Not connected
Pair 1
Not
connected
J13/3
24V IN 2
Pair 2 (both wires)
24V IN 2
J14/3
J13/4
0V IN 2
Pair 3 (both wires)
0V IN 2
J14/4
Not connected
Pair 4
Not
connected
Panel 2
(BS-210/BU-210
etc)
Cable 3
From last external panel and back to Fire
Alarm Control Panel
Panel 1
(BS-200)
Terminals
J13/5
A_1
Pair 1+
Panel Bus
Out A
J4/11
J13/6
B_1
Pair 1-
Panel Bus
Out B
J4/12
J13/3
24V IN 2
Pair 2 (both wires)
+24V out 2
J1/7
J13/4
0V IN 2
Pair 3 (both wires)
0V out 2
J1/8
Not connected
Pair 4
Not
connected
See drawing, chapter 9.11.