Test condition 

4.1

  Environmental condition:- 

Unless otherwise specified,all test of this specification should be performed under standard         
atmospheric condition: 

                  Temperature

15

℃~

35

;Relative humidity

45%

75%;Atmosphere pressure:86kPa

106kPa 

 
4.2

Measure instrument and equipment requirement 

Accuracy of measuring voltage instrument should not be less than level 0.5,resistance should be no less 
than 10KΩ/V. 

 

Accuracy of measuring current instrument should not be less than level 0.5. 

 

the relative error of measuring time instrument is ±0.1%. 

 

The  current  of  constant  current  load  is  adjustable  if  it  is  within  the  power  voltage  range,the 

current relative error is ±0.1%. 

 

The  current  of  constant  current  load  is  adjustable  if  it  is  within  the  power  voltage  range,the 

current relative error is ±0.1%. 

 

Charging power (or the charger) should be able to change to constant voltage charging after the 

battery voltage achieve constant voltage value of charging voltage. 

 

 
     

 

Содержание AWS-BATTERY

Страница 1: ...SLIDE PTY LTD 7TH JUNE 2022 1 AUTOSLIDE PTY LTD 3 413 VICTORIA STREET WETHERILL PARK 2174 NSW AUSTRALIA Specification for Lithium ion Battery AUTOSLIDE AUTOSWING BATTERY MODEL AWS BATTERY Part Number DY 6S1P18650 2103C ...

Страница 2: ...charge capacity 3 1Ah charge 0 5C 1 55A 25 2V 0 02C 0 62A up to current RT release charge 0 2C 20A 15V end voltage RT Standard voltage 21 6V Discharge protection voltage 2 8V 0 08V Single string voltage protection value Charge voltage 25 2 0 05V Charge mode CC CV Charge protection voltage Level 1 4 2 0 025VLevel2 4 34 2 0 025V Single string voltage protection value with secondary protection Standa...

Страница 3: ...an level 0 5 resistance should be no less than 10KΩ V Accuracy of measuring current instrument should not be less than level 0 5 the relative error of measuring time instrument is 0 1 The current of constant current load is adjustable if it is within the power voltage range the current relative error is 0 1 The current of constant current load is adjustable if it is within the power voltage range ...

Страница 4: ... maintained at 0 8 mm 1 6 mm total excursion and the frequency increased until a peak acceleration of 8 gn occurs approximately 50 Hz A peak acceleration of 8 gn is then maintained until the frequency is increased to 200 Hz No leakage No venting No disassembly No rupture and No fire voltage 90 before testing Overcharge protection Set the charge voltage of battery pack as 25 2V charge with 0 5C cur...

Страница 5: ... cells are used for the work piece process and batteries are delivered from storage 9 Safety specification and instructions Please read the instructions and battery surface marks carefully before use battery Please use battery in the normal and indoor environment In use process stay away from heat source and high voltage prevent children playing with battery Don t throw it Don t short circuit the ...

Страница 6: ...r the fire or under direct sun light It will cause the battery internal protection function loss and abnormal chemical reaction battery may be heating smoking deformation or burn Use dedicated charger and properly charging It is dangerous to charge the battery by non dedicated charger It will cause the battery internal protection function loss and abnormal chemical reaction battery may be heating ...

Страница 7: ...radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encourage...

Отзывы: