TF3 Series

 Defrost control (except 1CH, compressor output model: TF31-1

)

Parameter

Defrost method Defrost operation

hTM

Heater defrost

Operates during the set defrost cycle/time 

gTM

Hot-gas defrost

hTT

heater defrost

Operates when PV is lower than defrost end temperature during the set defrost cycle/time 

(only for 3CH input model (TF33-

- ))

gTT

Hot-gas defrost

When operating a compressor for a long time, an evaporator and a freezer are freezing and thermal efficiency of 

compressor is decreased. For increasing thermal efficiency, defrost operation helps to remove frost or ice around of 

evaporator.

Set defrost cycle, time, and end temperature, etc to operate defrost (heater/hot-gas defrost). 

The front defrost (DEF) output indicator (green) turns ON during defrost output and it flashes during defrost delay operation. 

In case of comdefrost or auxiliary (alarm/evaporator-fan) output model (TF3 -2

- ), defrost operation is 

available when defrost/auxiliary output [

sDA

] of parameter 1 group is set as defrost [

DEF

]. 

● Defrost cycle [

DIN

], defrost time [

DET

]

Set defrost cycle and time to operate defrost at every set cycle and during the set time. 

Defrost cycle setting range: 0 to 24 (hour)/0 to 100 (min)

Defrost time setting range: 1 to 100 (min/sec)

 Compressor operation during defrost is varied by defrost method. In case of heater defrost, compressor output turns 

OFF, and in case of hot-gas defrost, compressor output turns ON. Evaporator-fan operation is varied by evaporator-fan 

operation mode setting. 

 In case of RTC function model (TF33-3

-R/A), defrost operates at every specific time. Set real-time defrost cycle [

rDI

of parameter 3 group as [

ON

] and 8 real-time defrost times are available to set. 

● Defrost end temperature [

EDT

], Defrost hysteresis [

dHY

] (only for 3CH input model: TF33-

- )

Set defrost end temperature and defrost hysteresis from input sensor 2 (defrost temperature). When the measured 

temperature of defrost sensor is same as the set defrost end temperature, defrost operation is stopped. It is available when 

input sensor 2 ON/OFF [

S2

] is set as [

ON

] and defrost method and operation [

DEF

] is set as [

hTT

] or [

gTT

]. 

Defrost end temperature setting range: -40 to 99 (

) / -40 to 212 (

)

Defrost hysteresis setting range: 1 to 5 (1.0 to 5.0) (

) / 2 to 10 (

)

● Manual defrost

Execute defrost manually regardless of the set defrost cycle which consists of defrost method and operation setting. Hold 

the front   key over 3 sec or, turn ON the digital input when digital input [

DI

] of parameter 5 group is set as [

mDF

] to 

operate defrost during the set defrost time. 

The front defrost (DEF) output indicator turns ON for 2 sec and turns OFF for 1 sec during manual defrost. Hold the front 

 key over 3 sec or turn OFF the digital input during manual defrost, and the set defrost cycle re-starts. 

●  

Defrost synchronization  

(only for synchronize defrost function model: TF33-

A-S, RS485 communication model: TF33-

A-T/A) 

When connecting over 2 units of TF3, defrost and compressor operation is able to synchronize via synchronize terminal/

RS485 communication. 

It is available for synchronize defrost function model (TF33-

A-S), or RS485 communication model (TF33-

A-T/A).

 [Setting Order] 

1.  Connect each other synchronize terminals or RS485 communication terminals of the units which are synchronized for 

defrost. 

2.  Set defrost cycle [

DIN

] same as among the units. (if error occurs, defrost cycle is the setting of each unit)

3. Set defrost group [

dGR

] as 1 master unit [

MAS

] and slave unit (s) (up to 5 units) [

SLA

]. 

4.  According to defrost operation of Master, the defrost operation of slave (s) executes. (when changing the defrost 

parameters of master, defrost operations of slave (s) are also changed forcibly as same as the defrost operation of 

master via connected terminals. The defrost parameters of slave (s) are not changed.)  

Defrost operation by real-time defrost cycle is not able to synchronize.  

Defrost operation of master is prior to the compressor operation of slave. 

For more information about parameters for defrost operations, refer to user manual.  

 Defrost method and operation [

DEF

]

Содержание TF31-1G

Страница 1: ...tonics com to download user manual and communication manual User manual describes for specifications and function and communication manual describes for RS485 communication Modbus RTU protocol and parameter address map data Standard installation size for refrigeration and air cooling panels W70 3 H28 2mm Various compressor load current capacity 5A 16A 20A Various user friendly functions Defrost sy...

Страница 2: ...communication R 3 RTC real time clock A 3 RS485 communication RTC real time clock G 1 Compressor 20A 1a contact A Compressor 5A 1a contact H Compressor 16A 1c contact 1 24VAC 50 60Hz 12 24VDC 4 100 240VAC 50 60Hz 1CH 1 Compressor output 1CH 3CH 2 Compressor Defrost or Auxiliary alarm evaporator fan output 3 Compressor Defrost Auxiliary alarm evaporator fan output 1 1CH input NTC or RTD temperature...

Страница 3: ...10A 1a Auxiliary AUX 250VACᜠ 5A 1a Communication output RS485 communication output Modbus RTU Digital input Contact input ON max 1 OFF min 100 No contact input ON residual voltage max 1V OFF leakage current max 1mA outflow current 4 Control method ON OFF control Hysteresis 0 5 to 5 0 2 to 10 variable Relay life cycle Compressor COMP 5A 1a Mechanical 5 000 000 operations Electrical 50 000 operation...

Страница 4: ...C 5A RESISTIVE LOAD 2 SOURCE SYNCHRONIZE RS485 3 100 240VAC 50 60Hz 24VAC 50 60Hz 12 24VDC TF31 1 G TF31 A COMP OUT 250VAC 20A RESISTIVE LOAD SOURCE NTC 5K 10K DPt100 DIGITAL INPUT SENSOR 100 240VAC 50 60Hz 24VAC 50 60Hz 12 24VDC SENSOR NTC 5K 10K DPt100 DIGITAL INPUT SOURCE COMP OUT 250VAC 5A RESISTIVE LOAD DEF OUT 250VAC 10A RESISTIVE LOAD 1 AUX OUT 250VAC 5A RESISTIVE LOAD 2 100 240VAC 50 60Hz ...

Страница 5: ...0 6 0 25 4 0 3 0 1 When connecting remote display unit TFD or SCM US Min 120 NTC sensor 5kΩ AWG22 TPE lead wire Soldering Max 5 6 0 2 Max 15 2000 50 5 1 Dimensions unit mm unit mm 52 12 Ø2 5 3m or 5m 3 31 5 25 Sold Separately SCM US USB to Serial converter Communication converter SCM 38I RS232C to RS485 converter SCM US48I USB to RS485 converter SCM WF48 Wi Fi to RS485 USB wireless communication c...

Страница 6: ... defrost 5 Evaporator fan FAN output indicator green Turns ON for evaporator fan output Flashes for delay operation of evaporator fan output 6 Auxiliary AUX output indicator green Turns ON for alarm output Flashes for delay operation of alarm output 7 Unit indicator red Displays temperature unit set at temperature unit UNT of parameter 1 group 8 MODE key Used for entering parameter setting group r...

Страница 7: ...not valid the password code appears Press any key among the keys to return to password entering window Press the MODE key to return to RUN mode If you forget password contact Autonics after checking password code 2 It appears when setting user parameter group in the comprehensive device management program DAQMaster Press the MODE key after changing the setting to save the SV Hold the MODE key for ...

Страница 8: ...h limit deviation AlH Alarm low limit deviation AlL Alarm hysteresis aHY Alarm ON delay time aON Alarm OFF delay time aOF External alarm delay time eAD Alarm output method aN Evaporator fan operation fTY Evaporator fan control temperature fT Evaporator fan hysteresis fHY Evaporator fan mode FAN Evaporator fan start up delay time pDR Alarm operation mode AL Parameter 5 group PA5 Current minute CUM ...

Страница 9: ...are reset Appears only for 3CH input model Setting range 0 to 100 Appears only when input sensor 3 selection INT is set as TS Setting range 40 to 40 Setting range 0 5 to 10 0 sec Setting range 40 to 40 Appears only for 3CH input model Appears only for compressor defrost or auxiliary alarm evaporator fan output model Appears only for compressor defrost or auxiliary alarm evaporator fan output model...

Страница 10: ... compressor output mode CLE DUT parameter values are reset Setting range 1 to 5 0 5 to 5 0 2 to 10 2 0 to 10 0 Setting range 0 to 5 0 0 to 5 0 0 to 10 0 0 to 10 0 Setting range 20 to 20 20 to 20 0 50 to 50 50 to 50 0 Setting range 1 to 5 0 5 to 5 0 2 to 10 2 0 to 10 0 Setting range 0 to 5 0 0 to 5 0 0 to 10 0 0 to 10 0 Setting range 0 to 23 hour Setting range 0 to 59 min Setting range LSV 1digit t...

Страница 11: ...de end min Comp start up delay time Comp min operation cycle Comp min operation time Comp continuous operation Alarm delay time after continuous operation Comp operation cycle when sensor break Comp duty rate when sensor break Comp restart delay time S 8 S S S S S S S S S 0 0 0 0 0 0 2 0 50 S eMO Temperature monitoring OFF S1 VS Setting range OFF S1 S2 S3 VS Appears for RTC function model Does not...

Страница 12: ...y part for wrong PW When PW is correct 3 times When PW is wrong 3 sec 2 sec S S S PS PS 000 PA3 DEF DIN rDI DET DH DM PdD DrT Password input Parameter 3 group Defrost method operation Defrost cycle Real time defrost cycle Real time defrost cycle hour Real time defrost cycle min Defrost time Pump down delay time Defrost end delay time S 4 S S 30 S S S S OFF OFF 00 00 hTM gTM hTT gTT OFF ON Setting ...

Страница 13: ...A AlB AlF Setting range AlA AlB AlC AlD AlE AlF When changing alarm option AlH AlL AhY parameter values are reset Setting range In case of compressor output model below parameters of parameter 4 group do not appear Parameter 4 Group 1 S Press any key among keys After entering setting mode hold the MODE key anytime for 3 sec to return to RUN mode After entering setting mode hold the MODE key anytim...

Страница 14: ...s T Software AlH Alarm high limit deviation Alarm low limit deviation S 139 AlL S 139 aHY Alarm hysteresis Alarm ON delay time S 1 Setting range 0 to 60 min aON S 0 NO NC aOF eAD Alarm OFF delay time External alarm delay time S S 0 0 aN Alarm output method S Setting range F S to F S Setting range 1 to 5 0 5 to 5 0 2 to 10 2 0 to 10 0 fT fHY FAN pDR Evaporator fan control temperature Evaporator fan...

Страница 15: ... Setting range OFF sTP dSW nMD eAL eDF mDF Setting range 24 48 96 192 384 Multiply SV 100 to read NON EVN ODD 2 1 EnA DsA Appears only for RTC function model Appears only for RS485 communication model Parameter 5 Group 1 S Press any key among keys After entering setting mode hold the MODE key anytime for 3 sec to return to RUN mode After entering setting mode hold the MODE key anytime for 1 5 sec ...

Страница 16: ...play Units O Sensor Controllers P Switching Mode Power Supplies Q Stepper Motors Drivers Controllers R Graphic Logic Panels S Field Network Devices T Software lDK lP PWD Front key lock Parameter group lock Password S S S 000 S lSV SV setting group lock OFF ON OFF ON OFF ON USR User level S STD HGH Hold keys for 5 sec to reset all parameters in memory to default value Set INI parameter to YES to re...

Страница 17: ... and Range You can set the temperature to control with the keys Set range is within SV low limit value LSV to SV high limit value HSV E g In case of changing SV from 19 to 10 Press any key among the in RUN mode to enter into SV setting mode Last digit 100 digit on SV display part flashes Press the key to move digit 100 10 10 10 100 1 2 Press the key to raise or lower the set value 9 0 Press the MO...

Страница 18: ...DEF Parameter Factory default SV 0 Parameter 0 group Parameter Factory default DpT S1 MoT Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default OFT C nSV 1 nEM 0 CC 0 HYS 1 nHY 1 eMO OFF AdC 2 OFS 0 nOF 0 SDL 0 CLE 0 HSV 99 nSH 0 CYC 0 DUT 50 LSV 40 nTM 0 RDL 0 nMD OFF nEH 8 ONT 0 Parameter Factory default Parameter Factory default Parameter Factor...

Страница 19: ... value PV and setting value SV is higher than high limit or low limit deviation SV alarm output turns ON Mode Name Description AlA Standard alarm If it is an alarm condition alarm output is ON If it is a clear alarm condition alarm output is OFF AlB Alarm latch 1 If it is an alarm condition alarm output is ON and maintains ON status AlC Standby sequence 1 First alarm condition is ignored and from ...

Страница 20: ...r green is flashing 1 When starting compressor if present value PV is out of hysteresis range compressor output does not turn ON and the compressor COMP output indicator is flashing during compressor start up delay time 2 When compressor delay is completed and it is within compressor min operation cycle compressor output does not turn ON and the compressor COMP output indicator is flashing The lat...

Страница 21: ...t sensor is same as the set defrost end temperature defrost operation is stopped It is available when input sensor 2 ON OFF S2 is set as ON and defrost method and operation DEF is set as hTT or gTT Defrost end temperature setting range 40 to 99 40 to 212 Defrost hysteresis setting range 1 to 5 1 0 to 5 0 2 to 10 Manual defrost Execute defrost manually regardless of the set defrost cycle which cons...

Страница 22: ...ary output AUX should be set evaporator fan FAN It is available for compressor defrost auxiliary alarm evaporator fan output model TF3 3 Also auxiliary output AUX of parameter 1 group should be set as evaporator fan FAN Parameter Operation method EF1 When compressor operates evaporator fan also operates When compressor operation is finished evaporator fan also operation turns OFF except compressor...

Страница 23: ... TF33 input sensor 3 selection S3 of parameter 1 group is set as outlet temperature TS You can set virtual temperature rate If the temperature of inlet and outlet is significantly different at freezer virtual temperature helps to control temperature efficiently Virtual temperature is designated by the rate of input sensor 1 inlet temperature and input sensor 3 outlet temperature There is virtual t...

Страница 24: ...e dedicated sensor is higher than high limit temperature among temperature setting range ERR LBA Even though input sensor is normal freezer temperature does not change over 1 0 1 8 during loop break alarm monitoring time LBA Check the compressor and hold the key at the same time for 3 sec It clears when input is within the adequate range 1 indicates input sensor number of error display priority wh...

Страница 25: ...onnecting the connectors of the product Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power Do not use the unit for other purpose e g voltmeter ammeter but temperature controller 24VAC 12 24VDC power supply should be insulated and limited voltage current or Class 2 SELV power supply device Make a required space around the unit for radia...

Отзывы: