18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com | +82-2-2048-1577 | [email protected]
-|Transparent Guide|-
Specifications
■ Input
Rated input voltage range
10 - 30 VDCᜡ
90 - 240 VACrmsᜠ
(50 / 60 Hz)
Allowable input voltage range
9 - 32 VDCᜡ
85 - 264 VACrmsᜠ (50 / 60 Hz)
Max. input current
15 mA
22 mA
Operating voltage
≥ 9 VDCᜡ
≥ 85 VACrmsᜠ
Releasing voltage
≤ 1 VDCᜡ
≤ 10 VACrmsᜠ
Operating
time
Zero cross
turn-on
≤ 0.5 cycle of load power
+ 1 ms
≤ 2 cycle of load power
+ 1 ms
Random turn-on ≤ 1 ms
-
Releasing time
≤ 0.5 cycle of load power
+ 1 ms
≤ 2 cycle of load power
+ 1 ms
■ Output
Rated load voltage range
24 - 240 VACrmsᜠ (50 / 60 Hz)
Allowable load voltage range
24 - 264 VACrmsᜠ (50 / 60 Hz)
Rated
load current
Resistive load
(AC-51)
01)
10 Arms
15 Arms
20 Arms
25 Arms
40 Arms
Min. load current
0.15 Arms 0.15 Arms 0.2 Arms
0.2 Arms
0.5 Arms
Max. 1 cycle surge current
(60 Hz)
160 A
160 A
250 A
250 A
400 A
Max. non-repetitive surge
current (I
2
t, t = 8.3 ms)
130 A
2
s
130 A
2
s
300 A
2
s
300 A
2
s
910 A
2
s
Peak voltage (non-repetitive)
600 V
Leakage current (Ta = 25 ℃)
≤ 10 mArms (240 VACᜠ/60 Hz)
Output ON voltage drop [Vpk]
(max. load current)
≤ 1.6 V
Static off state dv/dt
500 V/μs
Rated load voltage range
48 - 480 VACrmsᜠ (50 / 60 Hz)
Allowable load voltage range
48 - 528 VACrmsᜠ (50 / 60 Hz)
Rated
load current
Resistive load
(AC-51)
01)
10 Arms
15 Arms
20 Arms
25 Arms
40 Arms
Min. load current
0.5 Arms
Max. 1 cycle surge current
(60 Hz)
300 A
300 A
500 A
500 A
500 A
Max. non-repetitive surge
current (I
2
t, t = 8.3 ms)
350 A
2
s
350 A
2
s
1000 A
2
s
1000 A
2
s
1000 A
2
s
Peak voltage (non-repetitive)
1200 V (zero cross turn-on), 1000 A (random turn-on)
Leakage current (Ta = 25 ℃)
≤ 10 mArms (480 VACᜠ/60 Hz)
Output ON voltage drop [Vpk]
(max. load current)
≤ 1.6 V
Static off state dv/dt
500 V/μs
01) AC-51 is utilization category at IEC60947-4-3.
■ Overheat prevention function
Overheat prevention function is when SSR internal temperature is overheated, the load
output is cut off to prevent internal device damage and also the alarm indicator and alarm
output turn ON.
The operating temperature of the overheat prevention function may vary depending on the
external environment, product configuration, and load current.
Rated input voltage range 10 - 30 VDCᜡ
90 - 240 VACrmsᜠ
(50 / 60 Hz)
Load voltage
≤ 30 VDCᜡ
≤ 30 VDCᜡ
Load current
≤ 50 mA
≤ 50 mA
Turn-off time
≤ 50 ms
≤ 100 ms
•
Alarm output is only for the rated load current 40 A model, in case of the rated load current 10 / 15 / 20 / 25 A
model, the alarm indicator turns ON without the alarm output.
•
To clear alarm, cut off the input signal during over the alarm output return time at the rated ambient temperature.
■ General specifications
Dielectric strength (Vrms)
Input-output: 2500 VACᜠ 50 / 60 Hz for 1 min
Input / output-case: 4000 VACᜠ 50 / 60 Hz for 1 min
Insulation resistance
Input-output, input/output-case
: ≥ 100 MΩ (500 VDCᜡ megger)
Indicator
Input indicator (green), alarm indicator (red)
Vibration
0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min)
in each X, Y, Z direction for 1 hour
Vibration (malfunction)
0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min)
in each X, Y, Z direction for 10 min
Shock
300 m/s
2
(≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)
100 m/s
2
(≈ 10 G) in each X, Y, Z direction for 3 times
Ambient temperature
01)
-30 to 70 ℃, storage: -30 to 100 ℃ (no freezing or condensation)
Ambient humidity
45 to 85 %RH, storage: 45 to 85 %RH (no freezing or condensation)
Input terminal
connection
≥ 1×0.5 mm
2
(1×AWG 20),
≤ 1×4 mm
2
(1×AWG 12) or ≤ 2×1.5 mm
2
(2×AWG 16)
Output terminal
connection
02)
Rated load current 10 / 15 / 20 / 25 A
: ≥ 1×0.75 mm
2
(1×AWG 18),
≤ 1×6 mm
2
(1×AWG 10) or ≤ 2×2.5 mm
2
(2×AWG 14)
Rated load current 40 A
: ≥ 1×1.5 mm
2
(1×AWG 16),
≤ 1×16 mm
2
(1×AWG 6) or ≤ 2×6 mm
2
(2×AWG 10)
Input terminal
fixed torque
0.75 to 0.95 N m
Output terminal
fixed torque
Rated load current 10 / 15 / 20 / 25 A: 1.0 to 1.35 N m
Rated load current 40 A: 1.6 to 2.2 N m
Approval
ᜢ ᜧ ᜫ
Weight (packaged)
Rated load current 10 / 15 / 20 / 25 A: ≈ 192 g (≈ 270 g)
Rated load current 40 A: ≈ 372 g (≈ 468 g)
01) See the 'SSR Derating Curve' because the capacity of the rated load current is differ depending on the ambient
temperature.
02) Connect the wire met the capacity of the load current to the output terminal.
SSR Derating Curve
•
Be aware that the ambient temperature and the derating curve is different by the
rated input voltage when using the product..
•
Since the effectiveness of the heat radiation is decreased when SSRs are installed
closely, be sure to supply less than 50 % of the rated load current.
•
SSR derating curves obtained approval from the UL certification authority.
■ SRHL1-1210 / 1410 / 1410R / 4210 / 4410
Lo
ad curr
ent [A]
10
40
25
20
15
6
0
Ambient temperature [℃]
10 20
30
40
50 60
70
80
90
0
■ SRHL1-1215 / 1415 / 1415R / 4215 / 4415
Lo
ad curr
ent [A]
10
40
25
20
15
6
0
Ambient temperature [℃]
10 20
30
40
50 60
70
80
90
0
■ SRHL1-1220 / 1420 / 1420R / 4220 / 4420
Lo
ad curr
ent [A]
Ambient temperature [℃]
10 20
30
40
50 60
70
80
90
0
10
40
25
20
15
8
0
6
SRHL1-1220/1420/1420R/4220
SRHL1-4420
■ SRHL1-1225 / 1425 / 1425R / 4225 / 4425
SRHL1-1225/1425/1425R/4225
SRHL1-4425
Lo
ad curr
ent [A]
10
40
25
20
15
8
0
Ambient temperature [℃]
10 20
30
40
50 60
70
80
90
0
6
■ SRHL1-1240 / 1440 / 1440R / 4240 / 4440
Lo
ad curr
ent [A]
Ambient temperature [℃]
10 20
30
40
50 60
70
80
90
0
10
40
25
20
15
9
0