1 Modbus RTU Protocol
18
© Copyright Reserved Autonics Co., Ltd.
1.8
Exception response-error code
If occurs an error, send a response command and transmit each Exception Code after set(1) the
highest-level bit of received command (Function).
Slave address Function
+80 H
Exception
code
Error check (CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
ILLEGAL FUNCTION (Exception Code: 01 H)
: A command that is not supported
ILLEGAL DATA ADDRESS (Exception Code: 02 H)
: Starting address of queried data is inconsistent with transmittable address from the
device.
ILLEGAL DATA VALUE (Exception Code: 03 H)
: Numbers of queried data are inconsistent with the numbers of transmittable
(transferable) data from the device.
SLAVE DEVICE FAILURE (Exception Code: 04 H)
: Not properly completed the queried command (order).
Read the output status of non-existing coil 001001 (03E8 H) [ON: 1, OFF: 0] on Slave (Address
17) from Master.
Query (Master)
Slave address Function Starting address
No. of points
Error check (CRC16)
High
Low
High
Low
Low
High
11 H
01 H
03 H
E8 H
00 H
01 H
## H
## H
Response (Slave)
Slave address Function
+80 H
Exception Code
Error check (CRC16)
Low
High
11 H
81 H
02 H
## H
## H
CRC16
Содержание SPR1 Series
Страница 1: ... Copyright Reserved Autonics Co Ltd i ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Safety Considerations viii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 22: ...2 Modbus Mapping Table 22 Copyright Reserved Autonics Co Ltd MCY SPRC1 V1 2 1807US ...