Parameter 3
group
Parameter
Display
Default
Setting range
Display
condition
P3-1
Lock
LOC
OFF
OFF : Unlock
LOC.0 : Lock All
LOC.1 : Lock parameter 1 / 2 / 3
LOC.2 : Lock parameter 2 / 3
LOC.3 : Lock parameter 3
-
P3-2
Parameter
reset
mRST
ENA
ENA: enable, DISA: disable
-
■
Parameter 2
group
Parameter
Display
Default
Setting range
Display
condition
P2-1
Decimal
point
position of
display value
DOT
00000
00000, 0000.0, 000.00, 00.000, 0.0000
P1-1 Input
operation
mode:
F1 to 2,
F7 to 14
P2-2
Time unit
01)
tUNT
tSEC
T.SEC, T.MIN
P1-1 Input
operation
mode:
F3 to 6
P2-3
Time range
(unit: sec)
01)
tSEC 99 (99
999.99: 999.99 s
9999.9: 9999.9 s
99999: 99999 s
P2-4
Time range
(unit: min)
01)
tMIN 99 (99
999.99: 999.99 m
9999.9: 9999.9 m
99999: 99999 m
P2-5
Input A
prescale
mantissa (x)
PScaH
^0000
0.0001 to 9.9999
P1-1 Input
operation
mode:
F1 to 2,
F4,
F7 to 14
P2-6
Input A
prescale
exponent (y)
PScaY
10 01
10 - 9 (10
-9
) to 10 09 (10
9
)
P2-7
Input B
prescale
mantissa (x)
PScbH
^0000
0.0001 to 9.9999
P1-1 Input
operation
mode:
F7 to 8
P2-8
Input B
prescale
exponent (y)
PScbY
10 01
10 - 9 (10
-9
) to 10 09 (10
9
)
P2-9
Display
cycle
dISpT
)05
OFF
02)
or 0.05, 0.5, 1, 2, 4, 8 sec
P1-1 Input
operation
mode:
F1 to 2,
F7 to 8, F14
P2-10
Input B
setting value
(INB)
COUnB
99999
1 to 99999
P1-1 Input
operation
mode: F14
01) To enter P2-3 time range (unit: sec) and P2-4 time range (unit: min) setting, press [▲] key at P2-2 time unit.
02) Only available operation mode F2, F14
Parameter
Display
Default
Setting range
Display
condition
P1-1
Input
op
e
ration
mode
MODE
F1
F1 to F14
-
P1-2 Input A
sensor type
IN-A
NPnhF
NPN.H.F : NPN non-contact input1
NPN.M.F : NPN non-contact input2
NPN.L.F : NPN contact input
PNP.H.F : PNP non-contact input1
PNP.M.F : PNP non-contact input2
PNP.L.F : PNP contact input
-
P1-3 Input B
sensor type
IN-B
NPnhF
P1-1 Input
op
e
ration
mode:
F2, F6 to 12,
F14
01)
P1-4 Output mode
OUT-T
STARD
[Relay double output model]
STARD : S (Standard)
OUT-H : H (High)
OUT-L : L (Low)
OUT-B : B (Block)
OUT-I : I (One-shot)
OUT-F : F (Deflection) *
P1-1 Input
operation
mode:
except F11
&
* P1-1 Input
operation
mode:
except F14
P1-5 Output
hysteresis
HYS
0001
[Relay single / double output model]
0000 to 9999
• Varies according to P2-1 Decimal point
position of display value
P1-1 Input
operation
mode:
F1, F7 to 8
P1-6 Delay
monitoring
GUARD
fDEFY
[Relay double output model]
F.DEFY: L comparative output limit *
STAR.T: Start compensation timer
02)
P1-1 Input
operation
mode:
F1 to 10
*P1-4 Output
mode: S, B, F
P1-7 Compensation
time
STArT
)0
[Relay double output model]
0.0 to 99.9 sec
P1-6 Delay
monitoring:
STAR.T
P1-8
Input A
auto-zero
time
AUToA
999(9
0.1 to 9999.9 sec
P1-1 Input
operation
mode: F1, F4,
F7 to 8
P1-9
Input B
auto-zero
time
AUToB
999(9
P1-1 Input
operation
mode: F7 to 8
P1-10 Memory
retention
MEMO
OFF
OFF, ON
P1-1 Input
operation
mode:
F11 to 14
01) In case of P1-1 Input operation mode F13, input B sensor type is not displayed and IN-B setting is same as IN-A.
02) [◀] key: Entering compensation time setting.
■
Parameter 1
group
Output Mode
Output mode is available to set.
The output modes supported by each model are different.
- Indicator : not support output mode, Relay single output model: S (Standard),
Relay double output model: total output modes
OFF:
ON:
H:
hysteresis
■ S (Standard) / B (Block) output mode
• Comparative value setting condition
S (Stanrdard): individual output operation regardless of size or order of set
comparative values
B (Block): L < H
H output: Display value ≥ Comparative value
H
L output: Display value
≤
Comparative value L
H
L
H
L
H
H
Comp
ar
ative
value
Output
■ H (High) output mode
■ L (Low) output mode
• Comparative value setting condition:
individual output operation regardless of
size or order of set comparative values
• Comparative value setting condition:
individual output operation regardless of
size or order of set comparative values
H output: Display value
≥
Comparative value
H
L output: Display value
≥
Comparative value L
H
L
H
L
H
H
Comp
ar
ative
value
Output
H output: Display value
≤
Comparative value
H
L output: Display value
≤
Comparative value L
Comp
ar
ative
value
Output
H
L
H
L
H
H
■ I (One-shot) output mode
• Comparative value setting condition: individual output operation regardless of size or
order of set comparative values
•
One-shot output time: 0.3 sec (fixed)
• No hysteresis.
H output: Display value
≥
Comparative value
H
L output: Display value
≥
Comparative value L
Comp
ar
ative
value
Output
H
L
H
L
0.3 s
0.3 s
■ F (Deflection) output mode
•
Transmits outputs when the saved setting value exceeds H deviation or L deviation.
• Comparative value setting
: Based on the set value, use the front HIGH / LOW set value thumbwheel switch to set
the H / L deviation.
( The set deviation value is saved during Power OFF until it is re-set.)
• Comparative value setting range
: 0.0001 to 99999
The setting range is different according to the P2-1 Decimal point position of display
value setting.
E.g.)
In case of P2-1 Decimal point position of display value = 0000.0,
setting range = 0.1 to 9999.9
•
Saving setting value: [MODE] + [▲]
• Checking setting value: [▲]
•
The deviation can be set to “0” but the actual operation will be the same as “1”.
01)
02)
(
Max.)H deviation
SV
(
Min.) L deviation
Power
Save SV
L deviation
output
H
deviation
output
Save SV
01) When P1-6 Delay monitoring = F.DEFY is set, there is no output.
02) The graph is assuming that there is a saved setting value prior to the setting value save point. The actual
output position may be different.