9.ModbusMappingTable
53
©CopyrightReservedAutonicsCo.,Ltd.
Address
Item
Factor
400031(001E) Operation
Bit0...
Bit1...
Bit2...
Bit3...
Bit4...
Bit5...
Bit6...
Bit7...
Bit8...
Bit9...
Bit10...
Bit11...
Bit12...
Bit13...
Fault
I-OC
Over current
Over volt
Over temperature
Fuse cut
Phase loss
Load open
Over SCR
Over Frequency
Run/Stop
Auto/Manual
EMS Power
Not Load
400032(001F) Output slope (%)
*0.001(0 to 1.000)
400033(0020) Output (%) for input 0%
*0.01(0 to 1000)
400034(0021) Input correction
*0.1(-999 to 999)
400035(0022) Input slope correction
*0.1(-999 to 999)
400036(0023) Overcurrent alarm output
0 to 2 (*1)
400038(0025) Overvoltage alarm output
0 to 2
400039(0026) Burn out fuse alarm
400041(0028) Heat sink temperature abnormal
condition alarm
400042(0029) Element error alarm
400044(002B) Heater break alarm