7 Counter Mode
44
© Copyright Reserved Autonics Co., Ltd.
Parameter
Parameter setting value
Min. reset time
[
RST
]
,
unit: ms
※
Set min. width of external reset signal input.
Input logic
[
SIG
]
NPN
: no-voltage input,
PNP
: voltage input
※
Check input logic (NPN, PNP).
Prescale
decimal point
※
2
[
ScDP
]
●
6-digit model
●
4-digit model
※
Decimal point of prescale should not set smaller than decimal point [
DP
].
Prescale value
[
SCL
]
※
Setting range of prescale value
6-digit model: 0.00001 to 99999.9, 4-digit model: 0.001 to 999.9
Start point
value
[
STRT
]
※
Setting range is linked with decimal point [
DP
].
6-digit model: 0.00000 to 999999, 4-digit model: 0.000 to 9999
※
When input mode is
DN
,
DN-1
,
DN-2
, start point value does not appear.
Memory
protection
[
DATA
]
※
CLR
:
Resets the counting value when power OFF.
REC
:
Maintains the counting value when power OFF. (memory protection)
Key lock
[
LOCK
]
※
lOFF
: Unlock keys, key lock indicator turns OFF
LOc1
: Locks
key, key lock indicator turns ON
LOc2
: Locks
,
,
keys, key lock indicator turns ON
LOc3
: Locks
,
,
,
keys, key lock indicator turns ON
※
1: For 1-stage setting value change model, OUT1 does not appear. The output time of OUT2 is
displayed as
OUtT
.
※
2: Decimal point and prescale decimal point
Decimal point: Set the decimal point for display value regardless of prescale value.
Prescale decimal point: Set the decimal point for prescale value of counting value
regardless of decimal point of display value.
Содержание CT4S-2P series
Страница 1: ...Programmable Counter Timer User Manual CT Series CT Series CT Series ...
Страница 2: ...내 ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Cautions During Use 나 viii Copyright Reserved Autonics Co Ltd ...
Страница 16: ...1 Product Overview 16 Copyright Reserved Autonics Co Ltd ...
Страница 20: ...3 Communication Specification 20 Copyright Reserved Autonics Co Ltd ...
Страница 24: ...4 Dimensions 24 Copyright Reserved Autonics Co Ltd ...
Страница 29: ...나 5 Guide For Connection Copyright Reserved Autonics Co Ltd 29 5 1 3 CTM Series 1 CT6M 1P 2 CT6M 1P T ...
Страница 36: ...5 Guide For Connection 36 Copyright Reserved Autonics Co Ltd ...
Страница 42: ...6 Basic Operations Counter Timer Communication 42 Copyright Reserved Autonics Co Ltd ...
Страница 74: ...1 74 Copyright Reserved Autonics Co Ltd ...