-|Transparent Guide|-
Mode Setting
RUN
[▲] + [▼] 3 sec
→
Digital input
01)
Auto
→
RUN
[MODE]
→
Monitoring mode
[MODE] 3 sec
→
[MODE] 3 sec
→
Program mode
[MODE] 3 sec
→
[MODE] + [◀]
→
Reset
[MODE]
→
01) P 1-34, P2-30 Digital input key (HOLD: hold display value or ZERO: remote zero)
Monitoring Mode
• Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
• If any key is not entered for 30 sec in each parameter, it returns to RUN mode.
• [MODE] key: Saves current setting value and moves to the next parameter.
• [◀] key: Changes setting digits.
• [▲], [▼] key: Changes setting values.
Parameter
Display
Defaults
Setting range
Display
condition
M1-1 1 CH output
value
OUt1
----
[Transmission output model]
• Displays output value by each
channel.
-
M1-2 2 CH output
value
OUt2
----
M1-3 Alarm 1 value
AL1
10)0
[Alarm output model]
Temperature sensor input
: within temperature range
Analog input
: low-limit
to
high-limit
scale
•
Depending on the number of alarm
outputs, whether to display alarm 3 /
4 is different.
P1-20 to 27,
P2-19 to 26
Alarm
operation /
option:
AT1.A,
AT2.A
M1-4 Alarm 2 value
AL2
00)0
M1-5 Alarm 3 value
AL3
10)0
M1-6 Alarm 4 value
AL4
00)0
M1-7 Display max.
peak value
01)
hPEK
----
Max. peak value in run mode
-
M1-8 Display min.
peak value
01)
lPEK
----
Min. peak value in run mode
-
01) Initial max. / min. peak value is saved after 2 sec from supplying the power.
Reset: Press the [▼] + [▲] keys for at least 1 sec
Specifications
Model
CN-610
□
-
□
CN-640
□
-
□
Input type
01)
Universal
- Temperature sensor
: RTD, thermocouple
- Analog: voltage, current
Pulse
Display method
12-segment (selectable red, green, yellow) LCD (character size: 6.4 ×
11.0 mm),
Graphic bar and input type / unit display part (red) LCD (character size:
1.4 × 2.75 mm)
Display accuracy
02)
Dependent on the ambient temperature
25 ± 5°C
± 0.2 % F.S. ± 1 digit
-10 to 20°C, 30 to 50°C ± 0.3 % F.S. ± 1 digit
Display cycle
03)
-
Same with pulse input cycle
Sampling cycle
Temperature sensor input: 250 ms
Analog input: 100 ms
-
Unit weight
(packaged)
≈ 160 g (≈ 301 g)
≈ 200 g (≈ 340 g)
Approval
ᜢ ᜫ
01) For details, refer to the input type and range.
02) Thermocouple, below -100 ℃: ± 0.4 % F.S. ± 1 digit
Thermocouple T, U: min. ± 2.0 ℃
03) When pulse input cycle is over 10 sec, it is updated by every 10 sec.
Output
Transmission
(DC 0 - 20 mA)
Transmission
(0 - 10 VDCᜡ)
Alarm
Load resistance
≤ 600Ω
≥ 10 kΩ
-
Accuracy
± 0.3 F.S.
-
Resolution
8,000
-
Contact capacity
-
250 VACᜠ
Contact
composition
-
5 A, 1a: 1 /
3 A, 1c: 2 /
5 A, 1a: 4 model
Power supply
100 - 240 VACᜠ ± 10 % 50 / 60 Hz 24 VDCᜡ ± 10 %
Power
consumption
≤ 8 VA
≤ 3 W
Insulation
resistance
≥ 100 MΩ (500 VDCᜡ megger)
Dielectric strength
Between input terminal and power terminal: 2,000 VACᜠ 50 / 60 Hz for 1 min
Vibration
0.75 mm double amplitude at frequency of 5 to 55 Hz (for 1 minute) in
each X, Y, Z direction for 2 hours
Noise immunity
± 2 kV the square wave noise (pulse width: 1 ㎲) by the noise simulator
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient
temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Parameter
Display
Defaults
Setting range
Display
condition
P1-1 Input type
IN-P
aMA2
•
Refer to Input Type and Range
-
P1-2 Temperature
unit
01)
UNIT
?C
℃, ℉
P1-1 Input
type:
Temp.
sensor
P1-3 Display unit
dUNT
?/O
%, OFF, mV, V, mA, A, ℃, ℉
P1-1 Input
type:
Analog
P1-4 Low-limit
input value
L-RG
0$00
Within input type range
• Low-limit input value + 20 % F.S. <
High-limit input value
P1-5 High-limit
input value
H-RG
2)00
P1-6
Decimal
point
position
dP
)0
0.0, 0.00, 0.000, 0
•
Set the decimal point position of the
high / low-limit scale.
P1-7 Low-limit scale
L-SC
00)0
-1999 to 9999
P1-8 High-limit scale
H-SC
10)0
P1-9 Input correction
IN-B
000
-999 to 999
-
P1-10
Low-limit
value of
transmission
output 1
lOR1
0$00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
0)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P1-11
High-limit
value of
transmission
output 1
hOR1
2)00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
1)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P1-12
Low-limit
value of
transmission
output 2
lOR2
0$00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
0)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P1-13
High-limit
value of
transmission
output 2
hOR2
2)00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
1)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P1-14 Bar display
CH
BAR
OUT1
[
Transmission output model]
OUT1, OUT2
P1-37 User
level: HIGH
P1-15
Low-limit
scale value of
transmission
output 1
lOU1
00)0
[
Transmission output model]
Temperature sensor input
: within temperature range
Analog input
: low-limit
to
high-limit
scale
-
P1-16
High-limit
scale value of
transmission
output 1
hOU1
10)0
P1-17
Low-limit
scale value of
transmission
output 2
lOU2
00)0
P1-18
High-limit
scale value of
transmission
output 2
hOU2
10)0
P1-19
Input and
transmission
output
extension
02)
ExIO
5P
[
Transmission output model]
5P: output DC 3.2 - 20.8 mA, 0 - 10.5 VDCᜡ
out of 5 % of analog input range
10P: output DC 2.4 - 21.6 mA, 0 - 11 VDCᜡ
out of 10 % of analog input range
0P: output DC 4 - 20 mA, 0 - 10 VDCᜡ in
the analog input range
P1-1 Input
type:
Analog
&
P1-37
User level:
HIGH
P1-20 Alarm 1
operation
AL-1
AT!A
□□□.■
[Alarm output model] □□□
AT1: high-limit alarm, AT2: low-limit
alarm, SBA: sensor break alarm, AT0:
no alarm output
-
P1-21 Alarm 1 option
[Alarm output model] ■
A: standard alarm, B: alarm
latch
,
C: standby sequence,
D: alarm latch and standby sequence
•
Enter alarm option setting mode
: Operate in ‘Alarm 1 operation’ mode
select AT1 or AT2 and input [◀] key
-
P1-22 Alarm 2
operation
AL-2
AT@A
□□□.■
[Alarm output model]
Same as 'P1-20 / 21 Alarm 1 operation
/ option'
•
Depending on the number of alarm
outputs, whether to display alarm 3 /
4 is different.
-
P1-23 Alarm 2 option
P1-24 Alarm 3
operation
AL-3
AT!A
□□□.■
P1-25 Alarm 3 option
P1-26 Alarm 4
operation
AL-4
AT@A
□□□.■
P1-27 Alarm 4 option
P1-28 Alarm output
hysteresis
A-HY
001
[Alarm output model]
001 to 999
P1-20 to 27
Alarm
operation
/ option:
AT1.A,
AT2.A
01) When changing the setting value, input type, high / low-limit scale, high / low-limit scale value of transmission
output 1 / 2, and AL1 to 4 are reset.
02) 0 mA, 0 VDCᜡ or less cannot be expanded. 1 VDCᜡ, 10 VDCᜡ input are available to extend only 5 %.
Program Mode
• Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
• If any key is not entered for 30 sec in each parameter, it returns to RUN mode.
• [MODE] key: Saves current setting value and moves to the next parameter.
• [◀] key: Changes setting digits.
• [▲], [▼] key: Changes setting values.
■
Universal