-|Transparent Guide|-
Timing Chart of the Control Output
•
The settings of the control output: KEEP, ON, OFF
•
External input time: ≥ 2 ms
■
KEEP
When the external input is applied, maintaining the state of the control output (a).
a = ON
a = OFF
Sensing
condition
External
input
Control
output
2 ms
a
a
2 ms
a
a
Sensing
condition
External
input
Control
output
■
ON
■
OFF
The control output is ON state under the
external input time.
The control output is OFF state under the
external input time.
2 ms
Sensing
condition
External
input
Control
output
2 ms
Sensing
condition
External
input
Control
output
Teaching Selection
■ Auto-tuning
It is suitable for the sensing environment in which fast-moving objects make unstable
incident light levels. Also, it is convenient because the object maintains its movement
continuously during the teaching mode. It uses the average value of the incident light
level estimated a certain period of time.
■ 1-point teaching
It is suitable for the sensing environment where much dust or pollutant makes the
lower incident level. The teaching proceeds; through-beam type: with sensing target,
reflective type: without sensing target
■ 2-point teaching
It is suitable for the sensing environment in which the object moves slowly or stops
with stable incident light level. After the teaching 2 points (with/without sensing
target), set the average value as a teaching value.
■ Positioning teaching
After placing the sensing target to the desired position, set 90% of the incident light
level as a teaching value. Typically, it is available for detecting a small hole on the
surface (through-beam type) or detecting moving object having a curve (reflective
type).
Teaching Sensitivity Setting
•
Before setting the sensitivity, select the teaching mode suitable for the sensing
environment. Refer to the detailed explanation of the teaching mode.
•
To use the teaching sensitivity setting by external input, select P-8. External input to
the teaching sensitivity setting (SET).
Mode
PV
SV
Descriptions
Auto-tuning
AUTO
1_5
Press [SET] key to proceed the teaching: 2 sec
2_5
OK
Flash twice (save a teaching value) and return to
RUN mode
1-point
teaching
01)
1PNT
1_5
Press [SET] key to proceed the teaching: 2 sec
2_5
OK
Flash twice (save the teaching value) and return to
RUN mode
2-point
teaching
02)
2PNT
1P
1-point
teaching
:
without
sensing
target
Press [SET] key to enter 1-point teaching
mode
1_5
Press [SET] key to proceed teaching
: 2 sec
2_5
1POK
Cross-flashing twice
(e.g., 1-point teaching value (P
Min
) = 250)
250
2P
2-point
teaching
: with
sensing
target
Standby 2-point teaching
1_5
Press [SET] key to proceed the teaching
: 2 sec (without pressing key over 1 min:
end teaching and return to RUN mode)
2_5
2POK
Cross-flashing twice
(e.g., 2-point teaching value (P
Max
) = 3400)
3400
1825
Completion
Cross-flashing twice (save the teaching
value) and return to RUN mode
(e.g., teaching value (
P
Min
+ P
Max
2
) = 1825)
Positioning
teaching
PSTN
1_5
Press [SET] key to proceed teaching: 2 sec
2_5
OK
Flash twice (save the teaching value) and return to
RUN mode
01) Adjust incident light level depending on the response time. Refer to the table below.
Response time
Incident light level
0
Saturation
Ultra fast mode
10
3980
Fast mode
Standard (STD) mode
Long distance mode
5
9980
Ultra long distance mode
02) Based on the reflective type.
Reset to Factory Settings
•
Restore the setting value to the factory default settings.
(except the incident light level monitoring)
•
[◀], [▶] key: select the setting value
Mode
PV
SV
Descriptions
Initialization
•
Entering method: in RUN mode, press [MODE] key for 7 sec
INIT
NO
Press [MODE] key and return to RUN mode
YES
Press [SET] key to proceed
INIT
Flash twice (initialization) and return to RUN mode
Manual Sensitivity Setting
•
You can set the sensitivity as the desired value. (factory defaults
: 2000)
•
You can adjust the teaching value from the teaching sensitivity setting.
•
PV display part shows the present incident light level during the manual sensitivity
setting.
Mode
PV
SV
Descriptions
RUN mode
3210
3000
Change the setting value using [◀], [▶] key
(e.g., 3000 → 2500)
Sensitivity
setting
3210
2500
Press [MODE] key or without pressing a key over 3 sec,
flashing the setting value twice (save the setting value)
and return to RUN mode
Incident Light Level Monitoring
•
You can check the high peak and low peak values of the incident light level and
change them to the currently measured values.
Mode
PV
SV
Descriptions
Incident light level
monitoring
•
Entering method: in RUN mode, press [MODE] key once
Max. value
(High peak)
HPEK
4000
Check max. incident light level and press [SET] key
to change (e.g., 4000 → 3000)
HPEK
3000
Press [MODE] key to move the parameter
Min. value
(Low peak)
LPEK
1000
Check min. incident light level and press [SET] key
to change (e.g., 1000 → 950)
LPEK
950
Press [MODE] key and return to RUN mode
Anti-saturation Function
•
When the incident light level is saturated, optimizing this value automatically
(max. 10 levels).
•
The anti-saturation function may change the operation of the control output.
Mode
PV
SV
Descriptions
RUN mode
4000
2000
Press [SET] +
[
▶] key to activate the function
ON
1000
---1
Adjust the incident light level
(e.g., 3 levels)
1700
---2
2000
---3
2000
--OK
Flash twice and complete the setting
01)
, return to RUN
mode
OFF
2100
2000
Press [SET] +
[
▶] key to deactivate the function
4000
S_OF
Flash twice and release the function, return to RUN
mode
01) The condition for setting completion differs depending on the response time.
Response time
Condition for the setting completion
Ultra fast mode
Incident light level ≥ 2,000
Fast mode
Standard (STD) mode
Long distance mode
Incident light level ≥ 5,000
Ultra long distance mode