Serial Interface

All devices which are connectible with APC-1011 including PC, PLC, serial printer, 

barcode reader, and dedicated controllers can be connected to any of RS232C, RS485 

and RS422 ports.

  

■ Changing serial interface

1)  Open the rear case of APC-1011 with a screw driver.

2)  Set the serial interface selecting jumper pin (①) with the jumper bar to serial 

interface to use.

3)  When setting to RS232C, connect the D-sub connector to COM2 (②).

 

When setting to RS485 / RS422, connect the D-sub connector to JP12 (③).

• 

For more details, refer to the below image and table.

No. Name

RS232C (default

)

RS485

RS422

Serial interface 

setting jumper pin

1  3  5  7  9  11

2  4  6  8 10 12

1  3  5  7  9  11

2  4  6  8 10 12

1  3  5  7  9  11

2  4  6  8 10 12

COM2

2  4  6  8  10

1   3   5   7   9

JP12

2   4   6

1   3   5

<Inside of APC-1011>

  

D-sub connector for each serial interface

RS232C

RS422

RS485

Port

Pin 

function

Port

Pin 

function

Port

Pin 

function

1
2

3
4

5

6
7
8
9

1 DCD

1
2

3
4

5

6
7
8
9

1

TXD-

1
2

3
4

5

6
7
8
9

1

DATA-

2

RXD

2

TXD+

2

DATA+

3 TXD

3 RXD-

3 -

4 DTR

4 RXD+

4 -

5

GND

5

GND

5

-

6 DSR

6 GND

6 -

7 RTS

7 -

7 -

D-sub 9-pin

Female

8 CTS

D-sub 9-pin

Female

8 -

D-sub 9-pin

Female

8 -

9 RI

9 -

9 -

Dimensions

• 

Unit: mm, For the detailed drawings, follow the Autonics website. 

  

■ Fixing

 bracket

  

Mold bracket

15

14

M4

10.4

5

4

12

2-R1.5

2-Ø3.2

2-R1.5

22

2.4

3.8

15.4

8

2

18

11

  

■ Panel cut-out

≥318

≤ 4-R3

≥ 232

246

160

+ 1.1

 

0.0

+ 1.0

 

0.0

245

273

100

4-M4

100

186.6

160

43

7