background image

1

Sales 800-633-0405

www.productivity2000.com

Terminal Block sold separately, (see wiring options on page 5).

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity2000.com for details).



 







 







®

WARNING:

 

To minimize the risk of potential safety problems, you should 

follow all applicable local and national codes that regulate the installation 

and operation of your equipment. These codes vary from area to area and 

it is your responsibility to determine which codes should be followed, and to 

verify that the equipment, installation, and operation are in compliance with 

the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the 

failure to follow all applicable codes and standards. We do not guarantee 

the products described in this publication are suitable for your particular 

application, nor do we assume any responsibility for your product design, 

installation, or operation.

If you have any questions concerning the installation or operation of this 

equipment, or if you need additional information, please call Technical 

Support at 770-844-4200.

This publication is based on information that was available at the time it 

was printed. At AutomationDirect.com

®

 we constantly strive to improve 

our products and services, so we reserve the right to make changes to 

the products and/or publications at any time without notice and without 

any obligation. This publication may also discuss features that may not be 

available in certain revisions of the product.

Removable Terminal Block Specifications

Part Number

P2-RTB

P2-RTB-1

Number of  

positions

18 Screw Terminals

18 Spring Clamp Terminals

Wire Range

30–16 AWG (0.051–1.31 mm²)
Solid / Stranded Conductor
3/64 in. (1.2 mm) Insulation Maximum
1/4 in (6–7 mm) Strip Length

28–16 AWG (0.081–1.31 mm²)
Solid / Stranded Conductor
3/64 in (1.2 mm) Insulation Maximum
19/64 in (7–8 mm) Strip Length

Conductors

“USE COPPER CONDUCTORS, 75ºC” or equivalent.

Screw Driver 

Width

0.1 in (2.5 mm) Maximum*

Screw Size

M2

N/A

Screw Torque

2.5 lb·in (0.28 N·m)

N/A

P2-08AD-1 Analog Input

The P2-08AD-1 Current Analog Input Module provides 

eight channels for receiving 0-20 mA signals for use 

with the Productivity2000 system.

Warning  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Removable Terminal Block Specifications. . . . . . . .  1

General Specifications   . . . . . . . . . . . . . . . . . . . . . . 2

Input Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . 2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3

Module Installation Procedure . . . . . . . . . . . . . . . . . 4

QR Code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Hot Swap Information  . . . . . . . . . . . . . . . . . . . . . . . 4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Module Configuration   . . . . . . . . . . . . . . . . . . . . . . . 5

Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Non-Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . 6

OLED Panel Display Menus  . . . . . . . . . . . . . . . . . . 7

Diagnostic/Status. . . . . . . . . . . . . . . . . . . . . . . . . . .  8

*Recommended Screwdriver TW-SD-MSL-1

Содержание Productivity2000 P2-08AD-1

Страница 1: ...the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time withou...

Страница 2: ...2 201 Safety Input Specifications Input Channel 8 Input Ranges 0 20 mA Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 20 mA 0 305 A per count 1 LSB 1 count Data Range 0 to 6...

Страница 3: ...for current loops 24VDC User Supplied Power User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM I1 I2 I3 I4 I5 I6 I8 I7...

Страница 4: ...your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot s...

Страница 5: ...Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20 1 ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 Term...

Страница 6: ...4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7...

Страница 7: ...the cycling Status Info screen This screen will auto cycle with status information Fault Messages Appear in place of data during a fault condition Input current 20mA Input current 0 5 0 6 0 7 0 8 SPAR...

Страница 8: ...evision Date P2 08AD 1 DS 3rd Ed Rev A 2 11 2022 Copyright 2016 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1...

Отзывы: