Terminal Block Removal

1.

 

Pull hinged 

door open 

here.

NOTE:

 

Do not grip 

door in middle.

IMPORTANT

Torque =  2.7 - 3.6 in./lb (0.3 - 0.4 Nm). 

Do not overtighten screws when         

installing terminal block.

2.

 Loosen self-

jacking screws 

to disengage 

terminal block.

3.

 

Grip opened door along 

edge to avoid flexing door 

and pull terminal block 

from module.

Important Hot-Swap Information

The Productivity3000 PAC supports hot-swap! 

Individual modules, expansion bases, and entire 

remote base groups can be taken offline, removed, and 

replaced while the rest of the PAC system continues 

controlling your process. Before attempting to use the 

hot-swap feature, be sure to read the hot-swap topic in 

the programming software’s help file or our online docu-

mentation at AutomationDirect.com for details on how to 

plan your installation for use of this powerful feature.

Module Installation Procedure 

WARNING:

 

Do not apply field power until the following 

steps are completed. See hot-swapping procedure for 

exceptions.

Align

here

Align

here

Step One: 

Align circuit card with slot and 

press firmly to seat module into connector.

To install or remove terminal 

block cover, press middle to flex 

cover.

AVERTISSEMENT:

 

Ne pas appliquer la puissance de 

champ avant l’exécution des étapes qui suivent. Consultez la 

procédure de remplacement à chaud pour les exceptions.

AVERTISSEMENT:

 

 

Risque d’explosion : ne pas connecter ou déconnecter les connec-

teurs ni actionner les commutateurs alors que le circuit est sous tension, à moins que la 

zone ne soit reconnue non dangereuse. Ne pas remplacer à chaud les modules à moins 

que la zone ne soit reconnue non dangereuse.

Step Two:

 

Pull top and bottom locking 

tabs toward module face. Click indicates lock 

is engaged.

Step Three:

 

Attach field wiring using 

optional terminal block or ZIPLink wiring 

system and install cover. 

WARNING:

 

Explosion hazard – Do not connect or disconnect connectors or  

operate switches while circuit is live unless the area is known to be non-hazardous.  

Do not hot-swap modules unless the area is known to be non-hazardous.

Содержание Productivity 3000 P3-08AD

Страница 1: ...ublications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product P3 08AD Analog Input The P3 08AD Voltage Current Analog Input Module provides 8 channels for receiving 10 VDC 5 VDC 0 to 5 VDC 0 to 10 VDC and 0 to 20mA signals for use with the Productivity3000 Programmable Automation Controller...

Страница 2: ...n current inputs only External DC Power Required 24VDC 20 25 33mA General Specifications Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 20 to 70 C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800 VAC applied for 1 second Insulation Resistance 10MV ...

Страница 3: ...iagram Voltage Input Circuits Current Sinking Input Circuits An Edison S500 32 R 0 032A fast acting fuse is recommended for all current loops COM V 4 Wire Voltage Transmitter 4 Wire Transmitter Optional Transmitter Power Supply AC or DC 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter 032A 2 Wire 4 20 mA Transmitter fuse fuse 032A fuse 032A V I COM V I 3 Wire Current ...

Страница 4: ...ted See hot swapping procedure for exceptions Align here Align here Step One Align circuit card with slot and press firmly to seat module into connector To install or remove terminal block cover press middle to flex cover AVERTISSEMENT Ne pas appliquer la puissance de champ avant l exécution des étapes qui suivent Consultez la procédure de remplacement à chaud pour les exceptions AVERTISSEMENT Ris...

Страница 5: ... a User Tagname to each input point channel selected and to each Status Bit Item Module Configuration Wiring Options ZIPLink Connection System Cable ZIPLink Module Complete System ZIPLink pre wired terminal block cables 0 5m 1 6FT cable 1 0m 3 3FT cable 2 0m 6 6FT cable ZIPLink Modules Feed through ZL P3 CBL20 L ZL P3 CBL20 1L ZL P3 CBL20 2L ZL RTB20 Terminal Block with pigtail cable 0 5m 1 6FT ca...

Страница 6: ...ng The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Make other linear conversions in ranges appropriate to the application 65535 220 12500 Tank Level 0 Control Valve Select the Input and Output tags appropriate for the application Convert raw input signals to engineering units for ...

Страница 7: ...er On Appears initially These screens will then auto cycle Fault Messages Appear in place of data during a fault condition Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information Input signal is OVER the maximum detectable by the module Input signal range minimum Voltage only Input signal 2mA Current only Note SPARE ...

Страница 8: ...h Support 770 844 4200 www automationdirect com P3000 8 Document Name Edition Revision Date P3 08AD M 1st Ed Rev B 12 06 2017 Copyright 2017 AutomationDirect com Incorporated All Rights Reserved Worldwide ...

Отзывы: