Automationdirect.com Productivity 3000 P3-08AD Скачать руководство пользователя страница 2

Tech Support 770-844-4200

www.automationdirect.com/P3000

2

Input Specifications

Input Channels 

Module Signal Input 

Ranges 

±10VDC, ±5VDC, 0 - 5VDC, 0 - 10VDC,  

0 - 20mA

Signal Resolution

16-bit

Resolution Value of LSB 

(least significant bit) 

1 LSB = 1 count 

±10V = 305µV 

±5V = 152µV 

0 - 5V = 76µV 

0 - 10V = 152µV 

0 - 20mA = 0.305µA

Data Range

0 to 65535 counts unipolar  

-32768  to +32767 counts bipolar

Maximum Continuous 

Overload 

±31mA, current input 

±100V, voltage input

Input Impedance

1M

V

 ±10% voltage input 

250

V

 ±0.1% 

1/4

W. current input

Hardware Filter 

Characteristics

Low pass 1st order, -3dB@48Hz  

Sample Duration Time

455µs per channel  

(does not include ladder scan time)

All Channel Update Rate 

4ms

Open Circuit Detection 

Time

Zero reading within 1s (current input only)

Conversion Method

Successive Approximation

Accuracy vs. Temperature ±10PPM / °C Maximum

Maximum Inaccuracy

0.1% of range voltage, 0.2% of range current (including 

temperature drift)

Linearity Error (end to 

end)

±0.01% of range max., ±10V & ±5V  

±0.015% of range max., 0-10V, 0-5V & 0-20mA 

Monotonic with no missing codes

Input Stability and 

Repeatability

±0.035% of range (after 10 min. warmup)

Full Scale Calibration 

Error 

±0.2% of range maximum

Offset Calibration Error

± .065% of range maximum

Max Crosstalk

-96dB

Recommended Fuse 

(external)

Edison S500-32-R, .032A fuse  

on current inputs only

External DC Power 

Required

24VDC (-20% / + 25%) 33mA

General Specifications

Operating Temperature

0° to 60°C (32° to 140°F),

Storage Temperature

-20° to 70°C (-4° to 158°F)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted 

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800 VAC applied for 1 second

Insulation Resistance

>10M

V

 @ 500 VDC

Heat Dissipation

1.1 W

Enclosure Type

Open Equipment

Agency Approvals

UL508 file E157382, Canada & USA

UL1604 file E200031, Canada & USA

CE (EN61131-2*)

This equipment is suitable for use in Class 1, 

Division 2, Groups A, B, C and D or non-hazardous  

locations only.

Module Keying to Backplane Electronic

Module Location

Any I/O slot in any local, expansion, or remote 

base in a Productivity3000 System.

Field Wiring

Removable terminal block (not included). Use 

ZIPLink Wiring System or optional terminal block. 

See “Wiring Options” on page 5.

EU Directive

See the “EU Directive” topic in the 

Productivity3000 Help File. Information can also be 

obtained at: www.automationdirect.com/P3000

Terminal Type (not included) 20-position removable terminal block

Weight

105g (3.73 oz)

*Meets EMC and Safety requirements.  See the D.O.C. for details.

WARNING: 

Explosion hazard – Substitution of components may impair suitability 

for Class I, Division 2.

AVERTISSEMENT: 

Risque d’explosion : la substitution de composants peut com-

promettre la convenance pour la Classe I, Zone 2 ou pour la Classe I, Division 2.

Содержание Productivity 3000 P3-08AD

Страница 1: ...ublications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product P3 08AD Analog Input The P3 08AD Voltage Current Analog Input Module provides 8 channels for receiving 10 VDC 5 VDC 0 to 5 VDC 0 to 10 VDC and 0 to 20mA signals for use with the Productivity3000 Programmable Automation Controller...

Страница 2: ...n current inputs only External DC Power Required 24VDC 20 25 33mA General Specifications Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 20 to 70 C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800 VAC applied for 1 second Insulation Resistance 10MV ...

Страница 3: ...iagram Voltage Input Circuits Current Sinking Input Circuits An Edison S500 32 R 0 032A fast acting fuse is recommended for all current loops COM V 4 Wire Voltage Transmitter 4 Wire Transmitter Optional Transmitter Power Supply AC or DC 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter 032A 2 Wire 4 20 mA Transmitter fuse fuse 032A fuse 032A V I COM V I 3 Wire Current ...

Страница 4: ...ted See hot swapping procedure for exceptions Align here Align here Step One Align circuit card with slot and press firmly to seat module into connector To install or remove terminal block cover press middle to flex cover AVERTISSEMENT Ne pas appliquer la puissance de champ avant l exécution des étapes qui suivent Consultez la procédure de remplacement à chaud pour les exceptions AVERTISSEMENT Ris...

Страница 5: ... a User Tagname to each input point channel selected and to each Status Bit Item Module Configuration Wiring Options ZIPLink Connection System Cable ZIPLink Module Complete System ZIPLink pre wired terminal block cables 0 5m 1 6FT cable 1 0m 3 3FT cable 2 0m 6 6FT cable ZIPLink Modules Feed through ZL P3 CBL20 L ZL P3 CBL20 1L ZL P3 CBL20 2L ZL RTB20 Terminal Block with pigtail cable 0 5m 1 6FT ca...

Страница 6: ...ng The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Make other linear conversions in ranges appropriate to the application 65535 220 12500 Tank Level 0 Control Valve Select the Input and Output tags appropriate for the application Convert raw input signals to engineering units for ...

Страница 7: ...er On Appears initially These screens will then auto cycle Fault Messages Appear in place of data during a fault condition Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information Input signal is OVER the maximum detectable by the module Input signal range minimum Voltage only Input signal 2mA Current only Note SPARE ...

Страница 8: ...h Support 770 844 4200 www automationdirect com P3000 8 Document Name Edition Revision Date P3 08AD M 1st Ed Rev B 12 06 2017 Copyright 2017 AutomationDirect com Incorporated All Rights Reserved Worldwide ...