IronHorse GSDA-CM-8 User Manual –  1st Ed. Rev. A – 10/15/19

Parameter 

(Item)

Description

Value Range

Units

Default

GSD8-

240-5C

All other 

GSD8 

drives

17

Power-Up Value

0-9999

(Eng. 

units)

0

18

Power-Up Mode

1 = Default to Zero Display 

2 = Default to Power-up Value 

3 = Default to Previous Running 

Value

3

18

Front-Panel Double-Click 

Destination

0 = Double-Click Ignored 

1 = Inhibit 

2 = Estop 

3 = Jog1 

4 = Jog2 

5 = Auto/Man - 4 to 20mA Card

0

19

Power-Up Value

0-9999

(Display 

units)

0

19

Output Invert (Unused on 

GSD8-240-5C-D, 10C-D, 10N4X, 

10N4X-A, 10N4X-U)

0 = Normal 

1 = Inverted

0

Display and Control/PID Setup Parameters

20

Display Minimum

0-9998

(Display 

units)

0

21

Display Maximum

1-9999

2400

22

Motor Control Method

0 = Gain Tracking Off, Low Spd 

Mode Off 

1 = Gain Tracking On, Low Spd 

Mode Off 

2 = Gain Tracking Off, Low Spd 

Mode On  

3 = Gain Tracking On, Low Spd 

Mode On

1

23

Accel Setting

1-9999

(Display 

units)

2500 

9999

24

Decel Setting

1-9999

(Display 

units)

2500 

9999

26

Proportional Gain

0-9999

(Non Unit 

Specific)

150

27

Integral Gain

1-9999 

0-9999

(Non Unit 

Specific)

5000 

20

28

Derivative Gain

0-9999

10

29

Pulse Accumulation Limit

2-5000

(Non Unit 

Specific)

15

29

Startup Lag Compensation

0-5000

0

Signal Input #1 (S1) Setup Parameters

30

S1 Display Reference

0-9999

1-9999

(Eng. 

Units)

2400

31

S1 Reference RPM

0-9999 

1-9999

RPM

2400

32

S1 Pulses Per Revolution

1-2048 

1-9999

PPR

20"

33

S1 Deadband - (Follower Mode 

Only)

0-1000

0

33

S1 Initial Stall Timeout

0, 5-9999 - (0 = Defeat)

Sec.

0

34

Signal Input (S1) Running Stall 

Timeout

0-9999 - (0 = Defeat)

0.10 Sec.

0

Signal Input #2 (S2) Setup Parameters

35

S2 Input Configuration

1 = Disabled - (Follower Mode) 

2 = E-Stop - S2 High 

3 = E-Stop - S2 Low 

4 = Inhibit - S2 High 

5 = Inhibit - S2 Low 

6 = Jog - S2 High 

7 = Jog - S2 Low

7

Содержание GSDA-CM-8

Страница 1: ...Page 1 IronHorse GSDA CM 8 User Manual 1st Ed Rev A 10 15 19 GSDA CM 8 ASCII Communications Module User Manual User Manual Number GSDA CM 8...

Страница 2: ...rformance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines or weapons systems in which the failure of the pr...

Страница 3: ...Using the Analog Input 7 User Assignable Output 12 Communications and Networking 13 Commonly Used Software 13 Hardware Jumper Selection 13 RS 232 and RS 422 485 Connections to the RJ45 Modular Jack 14...

Страница 4: ...d to work with you in answering your questions If you cannot find the solution to your particular application or if for any reason you need additional technical assistance please call Technical Suppor...

Страница 5: ...per and software parameter setup Baud rate is configurable from 300 to 57600 In addition the GSDA CM 8 can output a square wave frequency from 4 pulses per minute to 9999 ppm An analog input is also a...

Страница 6: ...stored configuration Up button to store factory defaults Down button to ignore card If the Up button is pushed the factory settings will be installed and the card will be initialized If the Down butto...

Страница 7: ...odular connector and can be used with a variety of signals The signal from the analog input source can be used to provide control or feedback information to the GSD8 drive This application note will c...

Страница 8: ...36 13 85 0 5 0 0 5 0 20 40 13 33 0 5 0 0 5 0 5 W 4 to 20mA Current Source Input A 4 to 20 mA current source type is tracked by the GSD8 drive at a 50 millisecond sample rate in the same way as the vo...

Страница 9: ...nimum value is obtained with a current of 4mA or less Maximum Value Maximum Value refers to the highest scaled value produced by the GSDA CM 8 A to D converter when the analog source signal is at the...

Страница 10: ...change that can be processed by the A D converter Mathematically the example looks like this Analog input signal 2 5V 0 00488V A D converter minimum voltage per count 512 counts digital equivalent 0...

Страница 11: ...of 20VDC can result in permanent damage to the GSDA CM 8 For proper operation the useful signal range is zero to 5VDC 0 to 5VDC Voltage Source Input Wiring Connect B to Analog Input Pin 7 of RJ45 Mod...

Страница 12: ...rm Logic section for a circuit description Otherwise you can use Ladder Logic symbology Using the Frequency Generator Output Parameter 5030 1 2 or 3 The GSDA CM 8 has a frequency generator output that...

Страница 13: ...llows the computer to communicate with a selected com port You will need to configure the software to allow it to communicate with the GSDA CM 8 Serial Card These products ship with their serial commu...

Страница 14: ...t RS 232 be run more than 50 feet Specialty converters can be purchased to allow an RS 232 device to interface with one or more units on a shared multi point bus Once the desired interface standard ha...

Страница 15: ...omplete and functional otherwise it will be necessary to double check the wiring and repeat some of the above tests NOTE Many of the commercially available modular connectors cables you buy off the sh...

Страница 16: ...age format is shown below command address command stuff CR Format Description command A two letter UPPERCASE command There is NO comma between the command and the address address A number 01 thru 99 r...

Страница 17: ...sponse if unsuccessful N CR NOTE The Set Target Speed commands are not stored in non volatile memory consequently upon power up in Auto Mode they will revert to zero When powered up in Manual Mode the...

Страница 18: ...Engineering Units as defined by the drive Format TS address CR Example Read the GSDA CM 8 addressed as 02 for the actual speed of the pickup in Engineering Units TS02 CR Response if successful value C...

Страница 19: ...e Flags Table 1 Below BCD n a 9 Drive Condition Flags See Flags Table 2 Below BCD n a General Setup Parameters 10 Operating Mode 1 Rate Mode 2 Time Mode 3 Follower Mode 1 11 Display Intensity Display...

Страница 20: ...Low Spd Mode Off 2 Gain Tracking Off Low Spd Mode On 3 Gain Tracking On Low Spd Mode On 1 23 Accel Setting 1 9999 Display units 2500 9999 24 Decel Setting 1 9999 Display units 2500 9999 26 Proportiona...

Страница 21: ...cel Eng Units 0 43 Disable U1 in Manual Mode 0 Disabled 1 Enabled Eng Units 0 Alarm Output 1 Setup Parameters 50 Alarm Activation Condition 0 Always Off 1 Always On 2 Active Upper Limit 3 Active Lower...

Страница 22: ...ee Flags Table 2 Below BCD 0 67 Alarm1 Logical AND Activation Conditions See Flags Table 2 Below BCD 0 Alarm Output 2 Setup Parameters 70 Alarm2 Logical OR Activation Conditions See Flags Table 1 Belo...

Страница 23: ...0 99 Restore From User Default Memory Restore Swap Environment Drive All ModularBus Card Settings from User Save Storage Area 0 Abort Exit 1 Restore User Default Settings 5 Copy Restore current Settin...

Страница 24: ...003 Hardware Version 1 9999 N A 1004 2004 Device Type 100 Type 1 Card 100 1005 2005 Minimum Supported Framework Version 1 9999 N A 1006 2006 Maximum Supported Protocol Version 1 9999 N A 1007 2007 Ser...

Страница 25: ...9999 n a 5008 Serial Number Minor 0 9999 n a Serial Communications Setup Parameters 5020 GSDA CM 8 Network Address 1 99 1 5021 GSDA CM 8 Baud Rate 1 300 2 1200 3 2400 4 4800 5 9600 6 19200 7 38400 8 5...

Страница 26: ...version that is compatible with this card 6 Reserved Reserved 7 Serial Number Major These Items are reserved for future use as an electronic serial number and are unique to each manufactured unit 8 S...

Страница 27: ...of the GSD8 drive Mode 3 RESERVED Mode 4 Frequency Generator Rate This will control the frequency output of the frequency generator Note When using this mode Item 30 of the serial communications board...

Страница 28: ...ntation to ensure correct functioning This example section shows network comms using GSDA with ASCII Baudrate in drive is 9 6Kbps 8 1 N by default NOP 2 This rung loads the Initial values for NodeAddr...

Страница 29: ...nd String or Text N 0D 8 Counter of Yes reply Increasing values for the counter means the command was accepted StrmOutSuccess C0 StrmInSuccess C5 CompareYesReply C7 UP RST Up Counter CNT Counter Struc...

Страница 30: ...cation Always verify the product documentation to ensure correct functioning This example section shows network comms using GSDA with ASCII Baudrate in drive is 9 6Kbps 8 1 N by default NOP This rung...