C2-02CPU Quick Start Guide 

Copyright© 2020, 

Automationdirect.com

 Incorporated/All Rights Reserved Worldwide

USB Programming Port Specifications

Communications Ratings USB 2.0 Full Speed (12Mbps)
Connector

Micro USB Type B

Bus Power

USB Low power Mode: Max. 500mA USB power 

supplied when USB cable is connected.
Disabled Functions:

 

ƒ

WLAN

 

ƒ

Bluetooth

 

ƒ

Stackable I/O

 

ƒ

RUN Mode

Recommended Cable

AutomationDirect p/n USB-CBL-AMICB6

USB Cable Length

Max 15 ft.

Wireless LAN (WLAN) Specifications

Standard

IEEE 802.11/b/g/n

Frequency

2.4 GHz

Maximum Transmitting 

Power

20.5 dBm (112mW)

Transmission Distance Up to 30m with no interference
Line Speed

Up to 150 Mbps

WLAN Mode

Station

Security

WPA/WPA2/WPA2-Enterprise/WPS

Encryption

AES/RSA/ECC/SHA

Antenna

External

RF Certification

FCC/CE(Red)/IC/MIC/AS/NZS

Status Lamp

WLAN(Green)

Bluetooth Specifications

Standard

IEEE 802.15.1 v4.2 Bluetooth Low Energy

Frequency

2.4 GHz

Maximum Transmitting 

Power

0 dBm (1mW)

Transmission Distance Up to 10m
Line Speed

Up to 1 Mbps

Antenna

External

Association Certification

Bluetooth SIG

Pairing

Yes

RF Certification

FCC/CE(Red)/IC/MIC/AS/NZS

Status Lamp

BT (Blue)

Backup Battery Specifications

Type

CR-2032  

(AutomationDirect #D0-MC-BAT recommended)

Technical Specifications

Power Specifications

Power Input Voltage Range

20–28 VDC Class 2  

or SELV(Safety Extra-Low Voltage)  

or Limited Energy Circuit power supply

Maximum Power Consumption

20W

Maximum Inrush Current

30A @ 1ms

Acceptable External Power Drop Max 10ms (AC Power Failure with 

C0-00AC or C0-01AC)

Wire Range

16–28 AWG

Wire Strip Length

7.0 mm

Wire Specification

Lead-free, heat resistant, 

polyvinyl chloride insulated copper wire, 

rated over 80°C

Screw Torque

2.0–2.2 lb-in [0.22–0.25 N·m]

24VDC Power Terminal Block 

Replacement

AutomationDirect p/n C0-4TB

General Specifications*

Operating Temperature 32°F to 131°F (0°C to 55°C)
Storage Temperature

–4°F to 158°F (–20°C to 70°C)

Ambient Humidity

30% to 95% relative humidity (non–condensing)

Altitude

Up to 2,000m

Environmental Air

No corrosive gases 

Pollution Degree 2 (UL840)

Environment

For Indoor Use Only

Weight

94g (3.3 oz)

Agency Approvals

UL61010 (File No. E157382, E316037); 

CE (EN61131-2); 

CUL Canadian C22.2

Radio Standards

 

ƒ

FCC part15C (US)

 

ƒ

RED Article3.2 (CE)

 

ƒ

IC RSS-247 (Canada)

 

ƒ

MIC Item 19 of Article 2-1. (Japan)

 

ƒ

AS/NZS 4268 (Australia and NEW ZEALAND)

Other

RoHS 2011/65/EU Amendment (EU)2015/863

Bluetooth SIG, SD associate

* Isolate from shock, vibration and electric or ferromagnetic field.

 

Keep out iron powder, moisture, oil or chemicals.  

Indoor use only. Keep out of direct sunlight. 

Please see User Manual for full environmental specifications. 

 

Meets EMC and Safety requirements. See the Declaration of Compliance for details.

Содержание CLICK PLUS C2-02CPU

Страница 1: ...ICK PLUS CPU PC or Android or iOS mobile device for setup provisioning Click Software ver 3 00 or later PC or Click App mobile device 24VDC power supply SELV and Limited Energy CLICK power supply C0 00AC or C0 01AC is recommended Appropriate enclosure with vertical surface for DIN rail or surface mount M4 screws spring washers and flat washers if surface mounting Ferrules and crimping tool for wir...

Страница 2: ...ent may be invalidated CAUTION For use in Pollution Degree 2 Environment Use and store the equipment in an environment described in the specifications regarding temperature humidity vibrations shock etc in order to avoid equipment damage or fire Ensure all wiring has strain reliefs in order to avoid damage to insulation that might result in electric shock or fire Ensure secondary external power ci...

Страница 3: ...the 4 pin connector located on the bottom of the CPU unit 16 28 AWG wiring is supported We recommend using crimping ferrules on all wire terminations for a more secure connection The following crimping ferrules are recommend ed for the 24VDC power terminals Company Type Model No Compliant Wire AutomationDirect Ferrule V30AE000009 V30AE000041 0 2 0 5 mm2 22 26AWG Maximum tightening torque is 0 22 t...

Страница 4: ...e module into its slot Press the module into place until it is fully seated 3 Push the top and bottom locking clips backward until they click into place Lift slightly on the locking clips until they release then slide each clip forward Reverse the procedure To install an Option Slot Module To install an Option Slot Module To remove an Option Slot Module To remove an Option Slot Module 3 Push the t...

Страница 5: ...r SE ANT250 A remote mounted antenna is recommended to connect with the enclosure closed PREPARE A MOBILE DEVICE FOR CONNECTION Install the CLICK PLUS Provisioning App using one of the QR codes below or search for the app in the appropri ate app store CLICK PLUS Provisioning published by Automationdirect com FIND THE NEW CPU Connect to the CPU as follows 1 Open the CLICK PLUS Provisioning App 2 Ta...

Страница 6: ... need to connect SET UP NETWORK PARAMETERS 9 Once the PLC is connected to the wireless access point or wired network choose which IP address configuration to use then tap Next to continue 9a Use DHCP Automatically assign a network IP address to the CLICK PLUS PLC This is often the simplest way to connect 9b Use Default Fixed Address Wireless 192 168 0 11 Wired 192 168 0 10 9c Use the following IP ...

Страница 7: ...g No Error Off Blink WLAN LED Green On Link Activity No Link Off Blink POWER LED Green On Power Good USB Low Power Mode Power Failure Off Blink RUN LED Green On CPU Run Mode Initializing Analog Module CPU Program Mode Off Blink LED Status Indicators Connecting via USB To connect the CLICK PLUS CPU to a PC use a USB A to USB micro B cable such as the AutomationDirect USB CBL AMICB6 cable 1 Connect ...

Страница 8: ...0 MC BAT recommended Technical Specifications Power Specifications Power Input Voltage Range 20 28 VDC Class 2 or SELV Safety Extra Low Voltage or Limited Energy Circuit power supply Maximum Power Consumption 20W Maximum Inrush Current 30A 1ms Acceptable External Power Drop Max 10ms AC Power Failure with C0 00AC or C0 01AC Wire Range 16 28 AWG Wire Strip Length 7 0 mm Wire Specification Lead free ...

Страница 9: ...0 Automationdirect com Incorporated All Rights Reserved Worldwide Mechanical Drawings Unit Dimensions mm in BLUETOOTH PAIRING MODE SWITCH MICRO USB POWER TERMINAL BLOCK OPTIONAL MODULE SLOT ANTENNA STATUS LED s 101 8 4 01 85 0 3 35 46 6 1 83 46 4 1 83 FULLY EXTENDED OVERALL 53 5 2 11 60 8 2 39 32 3 1 27 126 8 4 99 PART NO SE ANT210 ...

Страница 10: ...mmunications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The C2 02CPU complies with Part 15 247 modular Inten tional Radiator FCC rules and regulations Changes or mod ifications not expressly approved by AutomationDirect could void the user s authority to operate the...

Отзывы: