Automationdirect.com AcuAmp 3ACT Series Скачать руководство пользователя страница 2

Troubleshooting

1. Sensor has no output.

A.  Power supply is not energized or connected to the transducer.  

Check voltage at terminals 9 and 10. There is no isolation 
between the power and the output signals. 

B.  The monitored circuit is not energized or drawing current. 

Check that the monitored circuit is energized.

C.  Polarity is not properly matched. 

The output signals are polarity sensitive, and the result 
would be no signal to the controller or whatever is reading 
the transducer outputs.

2. Output signal too low.

A.  The transducer range may be too high to read the monitored 

circuit current. 

Select a lower range using the Range Selection Switch, use 
a model with a lower range, or loop each conductor through 
the sensing windows to increase the current through each 
aperture. 

B.  Power supply may not have enough capacity to operate the 

transducer outputs. 

Use a power supply with at least 6VA available to operate 
the transducer.

3. Outputs are

 always at the minimum (4mA)

.

The monitored load is not energized or is not AC.

Be sure that the monitored circuit is AC (3ACT 50/60 Hz, 
3ACTR 30 to 100 hertz). 

4. Outputs are

 always at the maximum (20mA)

.

The monitored load is drawing more current than the transducer 
range.

Select a model with a higher range, or set the range selection 
to a higher range. Be very careful when selecting the model 
to suit the application. Check the range selection slide 
switch. Check the actual current used with a hand-held 
ammeter and set the range accordingly. 

Description

The 3ACT/3ACTR Series current transducers are intended to 
monitor current of three phase loads. They provide an analog 
signal proportional to the current in each of the three phases, 
and another which will be proportional to the average of the 
three phase currents. The transducer can be mounted on a 
back panel using screws through the mounting holes in the 
base or snapped onto a 35mm DIN rail. Each model can be 
set for three current measurement ranges.

Wiring

Power Supply
Connect power supply to transducer as shown in the wiring 
diagram. Use 75/90°C rated copper wire. Tighten terminals to 
5-7 inch-pounds torque. Use a Class 2 power limited source  
fused to limit power to a maximum of 100 VA.

Output Signal
Observe polarity and connect each 4-20 mA output signal to 
controller or display using 75/90°C rated copper wire. Tighten 
the terminals on the transducer to 5-7 in-lbs torque. Confirm 
that the connected load impedance is less than 500 ohms.
Monitored Circuit
Each of the three phases passes through the three windows 
of the top section. All conductors should pass through the 
sensor in the same direction (from the front or the back) for 
appearance, but not required for accuracy or reliability. If the 
phases use multiple conductors, all wires of one phase must 
pass through the same sensing window or aperture. 
The transducer is designed to monitor circuits, whether the 
conductor is insulated or bare. Each aperture has an inside 
diameter of 0.74" (18.8 mm), allowing 4/0 THHN (120 mm

²

to pass through easily. Centering the conductor in the aperture 
is not necessary. 

NC NO

1 2

3 4

5 6

7 8

4-20 mA

Outputs

LOW MID HIGH

RANGE 

SELECTION

SWITCH

POWER

NO POLARITY

+

+

+

+

+

-

PLC, 

Controller, etc.

9

10

MONITORED CIRCUIT CONDUCTORS

-

-

-

-

A B

C

Average

Top View 

A

B

C

Wiring Schematic Drawing

Note: 

Power supply and output signal ARE NOT isolated. Do not connect the negative ter-

minals to a common point. 

Отзывы: