Part Number Key

AutomationDirect.com (ADC)

3505 Hutchinson Road, Cumming, GA 30040

Phone: (800) 633-0405 or (770) 889-2858

3ACT/3ACTR 

SERIES

INSTALLATION 

INSTRUCTIONS

Quick Start Guide

1.  Mount the 3ACT/3ACTR Current Transducer to a 

DIN rail or panel in a suitable enclosure.

2.  With monitored load off, install each phase 

through the sensing windows. Designate one 

phase as A, B, and C.

3.  Select the current range using the slide 

switch

.

4.  Connect output ter and - using 22-14 

AWG copper wires rated 75/90

°

C. Tighten to 5-7 

inch-pounds torque.

5.  Connect power supply voltage to terminals 9-10. 

6.  The output will be proportional to the current in 

each phase, plus one which is the average of the 

three. 

7.  Any of the four analog signals can be used 

independently, or all four can be used at the same 

time.

 

3ACT030  -  42 -  24 - F

3ACT: 3-phase AC current transducer, average responding

3ACTR: 3-phase AC current transducer, True RMS

OUTPUT SIGNAL 

HOUSING TYPE

CURRENT RANGES

030 - 0-10, 0-15 and 0-30A

100 - 0-30, 0-50, and 0-100A

200 - 0-100, 0-150 and 0-200A

F - Fixed Core

42 - 4-20mA

POWER SUPPLY 

24 - 24 VAC/DC (non-isolated)

®

3ACT/3ACTR - Inst - Rev 1     0820 

P-N 292000612

Specifications

Power Supply

24 VAC/DC ( +/- 10%), Intended for use with a Class 

2 source with the secondary fused to limit power to a 

maximum of 100 VA

Note: Power Supply and output signal ARE NOT 
isolated. Do not connect the negative terminals 
to a common point.

Power Consumption

< 6.0 VA

Output Signals 

4-20mA

Four outputs, three proportional to the current in that 

phase, one an average of all three.

Output Limit

20.8 mA

Output Impedance

500

Ω

 maximum

Accuracy

1.0% FS

Response Time

220ms (90% step change)

Frequency Range

3ACT: 50/60Hz, Average Responding

3ACTR: 30-100Hz, True RMS

Sensed Current Limit

1.1x range continuous

3x range for 6 seconds

6x range for 1 second

Isolation Voltage

UL tested to 1240VAC

Sensing Apertures

0.74 in (18.8 mm) dia.

Case

UL 94V-0 Flammability rated thermoplastic

Environmental

-Temp -4 to 122°F (-20 to 50°C)

-Humidity 0-95% RH, Non-condensing

-Pollution degree 2

-Altitude 2000 meters

Certifications

cULus listed E197592

CE

Warning! Risk of electric shock or 

personal injury

Safe operation can only be guaranteed if 
the 

transducer

 is used for the purpose for 

which it was designed and within the limits 
of the technical specifications. When this 
symbol is used, it means you should consult 
all documentation to understand the nature 
of potential hazards and the action required 
to avoid them.

Warning! Risk of hazardous voltage

When operating the transducer, certain parts 
may carry hazardous live voltage (e.g., primary 
conductor, secondary terminals). The transducer 
should not be put into service if the installation is 
not complete.

For products intended for the EU market, the 

following is applicable to the CE compliance of 

the product:

The 3ACT/3ACTR Series may comply with EN 61010-1 CAT III 
300V max line-to-neutral measurement category. If insulated 
cable is used for the primary circuit, the voltage rating of the 
measurement category can be improved according to the 
characteristics given by the cable manufacturer.

Part No. 3ACT030-42-24-F