background image

SR35 Quick-Start Guide

Stellar® SR35 Series Soft Starter Quick Start Guide – 1st Ed – 07/09/2020

21

e

nVIronmenTal

 s

peCIfICaTIons

Environmental Specifications

Model (SR35-)

017

022

027

034

041

052

065

Frame Size

1

Heat output (W)

9

12

14

16

20

25

30

Weight kg [lb]

197 [420]

Model (SR35-)

077

100

125

156

192

Frame Size

2

Heat output (W)

37

49

61

74

90

Weight kg [lb]

600 [1323] 

Model (SR35-)

242

302

361

Frame Size

3

Heat output (W)

111

139

166

Weight kg [lb]

1500 [3310]

Ambient Operating Temp

-20°C [-4°F] to 40°C [104°F] ; above 40°C derate linearly by 2% of SR35 I

e

 per 

°C  to a maximum of 60°C (140°F)

Transportation and Storage 

Temperature

-20°C to 70°C [-4°F to 158°F] continuous

Humidity

max 85% non-condensing, not exceeding 50% @ 40°C [104°F]

Maximum Altitude

1,000m [3281ft]; above 1000m derate by 1% of VMX-agility I

e

 per 100m 

(328ft) to a maximum altitude of 2,000m (6562ft)

Environmental Rating

Main Circuit:  IP00 (IP20 with optional finger guards); 

Control Circuit:  IP20; No corrosive gases permitted

W

Ire

 s

Izes

 

and

 T

orques

Wire Sizes and Torques

Terminal

Models 

(SR35-)

Wire/Busbar Size

Torque

Metric

Imperial

N·m

Ib·in

Main Terminals

Cu STR 75°C only

Terminal

017 to 065

25 – 70mm

2

12 – 2/0AWG

9

80

077 to 192

4 – 185mm

2

12 – 350MCM

14

124

M10 bolt

242 to 361

2 x 95mm

2

2 x 4/0AWG

28

248

Control Terminals

All models

02 – 15mm

2

24 – 16AWG

05

45

Protective Ground 

1)

Cu Only

M6 screw

017

≥ 4mm

2

≥ 12AWG

8

71

022 to 052

≥ 6mm

2

≥ 10AWG

065 to 100

≥ 10mm

2

≥ 8AWG

M8 screw

125 to 192

≥ 16mm2

≥ 6AWG

12

106

M8 Stud

242

≥ 25mm

2

≥ 4AWG

302 to 361

≥ 35mm

2

≥ 3AWG

1)  Protective Ground wire size based on bonding conductor requirements of UL508 Table 6.4 and 

UL508A Table 15.1.

Содержание Stellar SR35 Series

Страница 1: ...Stellar SR35 Soft Starter Quick Start Guide...

Страница 2: ...ower Circuit Wiring Diagram 3 phase 10 Single Phase Operation 11 Power Circuit Wiring Diagram 1 phase 11 Control Terminal Connections 12 Control Terminal Functions 12 3 Wire Control Circuit Wiring Dia...

Страница 3: ...his symbol should be obeyed to avoid possible damage to the equipment and personal injury or death Protective Earth Ground Indicates a terminal which is intended for connection to an external conducto...

Страница 4: ...hen installing the SR35 soft starter into a cabinet ventilation must be provided if the heat output of the unit is greater than the cabinet can dissipate The heat dissipated can be approximated with t...

Страница 5: ...is clear of all personnel and property Failure to follow this practice may result in death serious injury or damage to equipment Accessories The following accessories have been developed and tested fo...

Страница 6: ...17 to SR35 065 Dimensions mm in 148 5 83 108 4 25 90 3 54 165 6 50 181 7 13 Weight 1 97kg 3 75lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating Tables...

Страница 7: ...077 to SR35 192 Dimensions mm in 237 9 3 147 5 8 75 3 0 283 11 1 296 11 7 Weight 6 kg 13 22lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating Tables Cl...

Страница 8: ...35 361 Dimensions mm in 205 8 1 160 6 3 60 2 4 435 17 1 490 19 3 162 9 6 4 332 13 1 Weight 15kg 33 10lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating...

Страница 9: ...d as an option for short circuit protection of the semiconductors These fuses must be fitted externally to the SR35 chassis to comply with certain standards It is the responsibility of the installer a...

Страница 10: ...uide 1st Ed 07 09 2020 Electrical Connections 3 Phase Electrical Supply Connections L1 L2 L3 RJ45 connector Modbus RTU USB Connector Control Terminals AC Induction Motor Connections T1 T2 T3 Power Cir...

Страница 11: ...The base rating of the unit is unchanged Power Circuit Wiring Diagram 1 phase NOTE Refer to the SR35 single phase AC motor connectivity insert for additional single phase motor wiring details 2 T1 4 T...

Страница 12: ...C Specification See General Specifications on page 18 for VA rating residual ripple 100mV spikes switching peaks 240mV Turn On Off response no overshoot of Vout Overvoltage voltage protection output v...

Страница 13: ...gram K1 0V Start Stop 24V D1 D2 13 0V COM 14 21 22 FU1 24V dc NOTE 110 230V control supply possible with optional control supply module SR35 PSU 2 Wire Control Circuit Wiring Diagram 2 Wire Control Wi...

Страница 14: ...erload trip settings are determined by the Motor Current setting and the Trip Class setting Trip class choices are Class 10 Class 20 and Class 30 The SR35 soft starters are protected using full I2T mo...

Страница 15: ...3 Control scheme Local Control Terminal Modbus RTU 4 Keypad guidance wizard Displays which keys are valid for specific menu items 5 Motor overload level 0 to 100 6 Control keypad 7 Status LED incorpor...

Страница 16: ...Stellar SR35 Series Soft Starter Quick Start Guide 1st Ed 07 09 2020 How to Configure the SR35 Operation Local Motor Start Example Navigation Method Auto Application Setup Center button to adjust Quic...

Страница 17: ...ded 10 10 7 10 3 5 30 Crusher 40 10 0 30 3 5 60 Fan High Inertia 40 10 0 30 3 5 60 Fan Low Inertia 30 15 0 10 3 5 30 Grinder 40 10 0 20 3 5 40 Mill 40 10 0 20 3 5 40 Mixer 10 10 0 20 4 25 Moulding M C...

Страница 18: ...ors connected between motor windings and supply Number of poles 3 main poles 2 main poles controlled by semiconductor switching element Rated insulation voltage Ui Main circuit See Key to part numbers...

Страница 19: ...contact normally closed 21 22 Utilisation category voltage rating current rating Resistive load 250VAC 2A cos 0 5 250VAC 2A 4 Electronic overload relay with manual reset and thermal memory Trip Class...

Страница 20: ...C 61000 4 5 2kV line to ground 1kV line to line IEC 61000 4 6 10V 1 NOTICE This product has been designed for environment A Use of this product in environment B may cause unwanted electromagnetic dist...

Страница 21: ...40 C 104 F Maximum Altitude 1 000m 3281ft above 1000m derate by 1 of VMX agility Ie per 100m 328ft to a maximum altitude of 2 000m 6562ft Environmental Rating Main Circuit IP00 IP20 with optional fin...

Страница 22: ...ational current Ie A 80 106 132 160 195 242 302 361 Rated conditional short circuit current Iq kA 10 10 10 10 10 18 18 18 Class J time delay fuse 1 Maximum rating Z1 A 150 200 250 300 400 450 600 600...

Страница 23: ...le Horizontally Mounted Ie kW 1 FLA HP 2 Trip Class 10 Ie AC 53a 3 5 17 F S 4 Trip Class 20 Ie AC 53a 4 19 F S 4 Trip Class 30 Ie AC 53a 4 29 F S 4 A3 230V 400V 500V A3 200V 208V 220 240V 440 480V 550...

Страница 24: ...Stellar SR35 Soft Starter Quick Start Guide First Edition 01 22 2020...

Отзывы: