Automation Direct PSM24-BCM360S Скачать руководство пользователя страница 7

RHINO Battery Control Module PSM24-BCM360S Operating Instructions
4th Edition 06/18

1 - 8 0 0 - 6 3 3 - 0 4 0 5

7

General Specifications

Battery Protection

Over voltage, deep discharge, overcharge, short-circuit and reverse connection (built-in fuse)

Status Signals

DC-OK input, DC-OK output, BAT OK all relay contact closed at status OK; All LEDs on (green) at status OK

Rating per Relay Contact

30 VDC / 0.6 A max.

Remote Link Wire 0.5m

One cable included with PSM24-BCM360S module

Remote ON/OFF

by external contact:  ON =  J5.7 + J5.8 not shorted 

OFF = J5.7 + J5.8 shorted

Temperature

Operating (ambient): -25°C to + 70°C max (-13°F to 158°F). Above +40°C(104°F) load derating 1.5%/°C 

Storage (non-operating): -25°C to + 85°C max (-13°F to 185°F). 

Temperature drift:  0.02%/°C.   

Cooling: convection, no internal fan

Humidity

95% (non-condensing) relative humidity maximum

Isolation

According to IEC/EN 60950-1, UL 60950-1, EN50178, EN60204

Over-temperature Protection

When the TS-1 cable is used, the battery charging function will stop if the temperature sensor indicates the battery is over temperature. When the 

temperature sensor detects that the temperature has returned to a safe range, normal battery charging operation will automatically restart.

Vibration 

IEC 60068-2-6: 3 axis, sine sweep, 10-55 Hz, 1g, 1 oct/min

Shock

IEC 60068-2-27: 3 axis, 15g half sine, 11ms

Enclosure Rating

IP20 (IEC 529)

Enclosure Material

Aluminum (chassis) / zinc plated steel (cover)

Mounting

Snap-on with self-locking spring for 35mm DIN rails per EN 50022-35x15/75, or wall mount with bracket (PSM-PANEL1 sold separately)

Connection

Pluggable screw terminals (plugs included) 2 terminals per output

Note: Unless otherwise stated, all specifications are valid at nominal input voltage, full load and +25°C after warmup time.

General Specifications   –  Safety Standards

Specification

Standard

Document Number

Electromagnetic Compatibility (EMC), Emissions

EMC, Emissions

Corresponds to connected units ( no internal switching device)

Electromagnetic Compatibility (EMC), Immunity

EMC, Immunity

Corresponds to connected units ( no internal switching device)

Pollution Degree

2

Front view

Side view

Top view

Bottom view

DC Input OK

Bat. OK

DC Output OK

Remote On/Off

Temp. Sensor

(TS)

1

2

3

4

5

6

7

8

9

10

Unit: mm [inches]

PSM24-BCM360S Dimensions

General Specifications

Содержание PSM24-BCM360S

Страница 1: ...Rhino Battery Control Module PSM24 BCM360S Operating Instructions...

Страница 2: ...oblems follow all applicable local and national codes regulating the installation and operation of this equipment These codes vary from area to area and it is your responsibility to determine which co...

Страница 3: ...L1 Observe mounting position and orientation requirements stated above Remove the DIN clips by removing the screws and place the mounting brackets in the same place as the DIN clips Use the countersin...

Страница 4: ...a reliable and shockproof connection strip the connecting ends according to the table below If flexible wires are used terminate them using ferrules Battery In Connector J1 pin 3 and pin 4 Make the ba...

Страница 5: ...luding battery charging and battery condition test PSM Power Supply Model Jumper J6 positions 1 2 and 3 The PSM24 BCM360S module is designed to provide the remaining output current for battery chargin...

Страница 6: ...in 1 Vin DC In GND S 15 sec test DC IN OK Signal PSM24 360S factory setting Pin 2 Vin DC In GND S Common DC IN OK Relay contact PSM24 180S Pin 3 Bat in Vout 10 min test Bat OK Signal PSM24 090S Pin 4...

Страница 7: ...is over temperature When the temperature sensor detects that the temperature has returned to a safe range normal battery charging operation will automatically restart Vibration IEC 60068 2 6 3 axis si...

Страница 8: ...RHINO Battery Control Module PSM24 BCM360S Operating Instructions 4th Edition 06 18 1 8 0 0 6 3 3 0 4 0 5 8...

Отзывы: