Chapter 1: Getting Started
DL05/06 Option Modules User Manual; 7th Ed. Rev. C
1–7
NOTE 1:
If the PLC’s auxiliary 24VDC power
source is used to power the sinking
outputs, use power choice A, above.
Power Budgeting Example
Power Source
5VDC
power (mA)
24VDC
power (mA)
D0-06DD1
(select row A
or row B)
A
1500mA
300mA
B
2000mA
200mA
Current Required
5VDC
power (mA)
24VDC
power (mA)
D0-06DD1
600mA
280mA*
D0-16ND3
35mA
0
D0-10TD1
150mA
0
D0-08TR
280mA
0
F0-4AD2DA-2
100mA
0
D0-06LCD
50mA
0
Total Used
1215mA
280mA
Remaining
A
285mA
20mA
B
785mA
Note 1
* Auxiliary 24VDC used to power V+ terminal of
D0-06DD1/-D sinking outputs.
DL06 Power Supplied by Base Units
Part Number
5 VDC (mA)
24 VDC (mA)
D0-06xx
<1500mA
300mA
<2000mA
200mA
D0-06xx-D
1500mA
none
DL05/DL06 Power Consumed by Other Devices
Part Number
5 VDC (mA)
24 VDC (mA)
D0-06LCD
50mA
none
D2-HPP
200mA
none
DV1000
150mA
none
EA1-S3ML
220mA
none
DL06 Base Unit Power Required
Part Number
5 VDC (mA)
24 VDC (mA)
D0-06AA
800mA
none
D0-06AR
900mA
none
D0-06DA
800mA
none
D0-06DD1
600mA
280mA*
D0-06DD2
600mA
none
D0-06DR
950mA
none
D0-06DD1-D
600mA
280mA*
D0-06DD2-D
600mA
none
D0-06DR-D
950mA
none
DL05/06 Power Consumed
by Option Cards
Part Number
5 VDC (mA)
24 VDC (mA)
D0-07CDR
130mA
none
D0-08CDD1
100mA
none
D0-08TR
280mA
none
D0-10ND3
35mA
none
D0-10ND3F
35mA
none
D0-10TD1
150mA
none
D0-10TD2
150mA
none
D0-16ND3
35mA
none
D0-16TD1
200mA
none
D0-16TD2
200mA
none
F0-04TRS
250mA
none
F0-08NA-1
5mA
none
F0-04AD-1
50mA
none
F0-04AD-2
75mA
none
F0-2AD2DA-2
50mA
30mA
F0-4AD2DA-1
100mA
40mA
F0-4AD2DA-2
100mA
none
F0-04RTD
70mA
none
F0-04THM
30mA
none
F0-08SIM
1mA
none
F0-08ADH-1
25mA
25mA
F0-08ADH-2
25mA
25mA
F0-04DAH-1
25mA
150mA
F0-08DAH-1
25mA
220mA
F0-04DAH-2
25mA
25mA
F0-08DAH-2
25mA
25mA
D0-01MC
used only in DL05
D0-DCM
250mA
none
D0-DEVNETS
45mA
none
H0-PSCM
530mA
none
H0-ECOM
250mA
none
H0-ECOM100
300mA
none
H0-CTRIO
250mA
none
F0-CP128
150mA
none