Step 7 – Providing Power to the
C-more
Color Micro-Graphic Panel
Power can be supplied to the
C-more
Micro-Graphic panel in one of three different ways.
1). The panel is powered by a 1 Amp @ 12-24 VDC power source in normal operation.
2). The C-more Micro-Graphic panel can be powered during programming from the PC through a
USB Programming Cable such as USB-CBL-AB6. When powered from the PC, the panel will
operate in Low-Power mode and the screen brightness is diminished.
EA1-TCL-M Hardware User Manual, 2nd Ed., 10/10
1–15
Chapter 1: Getting Started
1
®
®
INPUT 12 24V 6 5W Cla s2
INPUT 12 24V 6 5W Cla s2
ST D
ST D
7M17
7M17
Da e code:* **
Da e code:* **
5
3
1
R01
R01
MADE N CHINA
MADE N CHINA
EA1- 6C + er al number
EA1- 6CL + er al number
MODEL EA1-T6CL
MODEL EA1-T6CL
ND.CONT EQ.
ND.CONT EQ.
8
1
15
9
Supply to Panel:
1 A @ 12 - 24 VDC
(10.8 - 26.4 VDC)
+
–
GND
Equipment
Ground
Recommended
DC Supply Fuse
750 mA fast acting,
ADC p/n AGC-75
Panel Powered from a DC Power Source - Wiring Diagram
NOTE:
Recommended DC power supply to power the C-more Micro Graphic Panel,
AutomationDirect
Part No.
PSP24-024S or PSP24-024C.
Tightening Torque
Power supply wire connection
1 7 lb-in (0.2 Nm)
Required Wire Specification
Supported temperature
Over 60 °C
Wire Material
Copper
Wire Size
16 - 22 AWG