9. SETTINGS AND TECHNICAL INTERVENTIONS
YOUR TRIPOD TURNSTILE IS MADE UP OF VARIOUS MECHANICAL AND ELECTRICAL COMPONENTS. ANY
NEGLIGENCE WHILE WORKING ON THE MACHINE MAY SERIOUSLY ENDANGER YOUR SAFETY. DISCONNECT
THE GENERAL POWER SUPPLY FROM THE EQUIPMENT AS SOON AS YOU OPEN THE CASING. BE CAREFUL
IN HANDLING ANY ELEMENT THAT MIGHT BE UNDER POWER OR COULD BE SET IN MOTION.
9.1. FAULT DIAGNOSIS
Failure description
Possible cause
Comment
The Trilane is not powered
(pictogram not lit, drive
not lit, free passage in
both directions, etc
.)
Remove the cover (TL2) or the front panel
(TL1) and check the 230 VAC connection
and the position of the main circuit
breaker. Check the correct 24 VDC supply
voltage.
In the A5/B5 configuration, the
de-energised TriLane is free in
both directions of passage.
A pictogram is not lit
.
On the AS1635 circuit board, check the
connection of the CN10 connectors
(pictogram direction A) and CN11
(pictogram direction B).
Replace the pictograms if necessary.
CN10(or 11)-1 red
CN10(or 11)-2 green
CN10(or 11)-3 blue
CN10(or 11)-4 white
CN10(or 11)-5 0V ref
The TriLane does not lock
itself (in direction A or
direction
B)
Check the programmed operating mode
in direction A and B via the HMI (free,
controlled, blocked).
Check that the TriLane is not in
Emergency mode (connection between
CN1.3 and 4 for normal operation).
Check the supply voltage of the
electro-magnet, between CN5-1 and
CN5-2 (direction A) or CN5-3 and CN5-4
(direction B).
If the electro-magnet is functioning
correctly, check the locking mechanism
Note: the 24 VDC voltage is
only applied during the first
moments The holding voltage is
reduced to prevent the electro-
magnet from heating up.
The passage
authorisation is not
taken into
consideration.
Using the HMI, check that the TriLane is
not in blocked mode.
Check the connection between the
reader and the AS1635 circuit board (24
VDC pulse in CN2-1 for authorisation
in the A direction and in CN2-2 for
authorisation in the B direction).
Default configuration of the
inputs, can be modified via the
PC interface.
The electro-magnet
works properly, but the
turret does not unlock.
An anti-noise ring is placed on the
axis of the electromagnet. But it limits
the impact force.(
spacer on the axis of the electro-
magnets", page 25) Remove the ring if
necessary.
The turret will not re-lock
during rotation.
Check the operation of the angular
sensor and the connecting cable (CN17
on the AS1635 circuit board).
In the case of an angular sensor
problem, an error appears on
the HMI display.