Inverter Air Source Heat Pump (AHGR32AW17) - Installation and Instruction Manual
06. Troubleshooting
6.2 Frequency Conversion Board Fault Table
6.3 Parameter List
Protect/fault
Fault Code
Reason
Elimination methods
IPM Overcurrent Shutdown Fault
F00
IPM input current is large
Check and adjust the current measurement
Compressor Activation Failure
F01
Lack of phase/step or drive hardware damage
Check the measuring voltage
Check frequency conversion board hardware
PFC Fault
F03
PFC circuit protection
Check the PFC switch tube if short circuit or not
DC Bus Overload
F05
DC bus voltage > Dc bus over-voltage protection value
Check the input voltage measurement
DC Bus Underload
F06
DC bus voltage < Dc bus over-voltage protection value
Check the input voltage measurement
AC Input Underload
F07
The input voltage is low, causing the input current to be low
Check the input voltage measurement
AC Input Overload
F08
The input voltage is too high, more than outage
protection current RMS
Check the input voltage measurement
Input voltage Sample Fault
F09
The input voltage sampling fault
Check and adjust the current measurement
Communication Failure
between DSP and PFC
F10
DSP and PFC connect fault
Check the communication connection
Communication Fault (DSP)
F11
DSP and main board communication ailure
Check the communication connection
Communication Fault
(Inverter Board)
F12
Frequency conversion board and main
board communication failure
Check the communication connection
IPM Overheat Stop
F13
The IPM module is overheat
Check and adjust the current measurement
Weak Magnetism Alarm
F14
Compressor magnetic force is not enough
Input voltage Lacking Phase
F15
The input voltage underwent phase-loss
Check and measure the voltage adjustment
IPM Current Sample Fault
F16
IPM sampling electricity is faulty
Check and adjust the current measurement
Sensor Fault of Module/Radiator
F17
The temp. sensor is broken or short circuit
IGBT Power Device Overheat Alarm F20
The IGBT is overheating
Check and adjust the current measurement
Overload Alarm
F21
Compressor electricity is large
Compressor over-current protection
AC Input Overcurrent Alarm
F22
Compressor electricity is large
Compressor over-current protection
EEPROM Fault Alarm
F23
MCU error
Check whether the chip is damaged
Replace the chip
Destroyed EEPROM
Activation Ban Alarm
F24
MCU error
Check whether the chip is damaged
Replace the chip
LP 15V Underload Fault
F25
The V15V is either overloaded or has low voltage
Check the V15V input voltage if in range
13.5V~16.5V or not
IGBT Power Device Overheat Fault
F26
The IGBT is overheating
Check and adjust the current measurement
Meaning
Default
Remarks
Cooling target temperature set point
12ºC
Adjustable
Heating target temperature set point
40ºC
Adjustable
Hot water target temperature set point
40ºC
Adjustable
17