G. FLUSH MODE
.
In FLUSH mode the control unit will activates the flushing mechanism (The motor & solenoid
valve) for fixed time set by TF timer while [FLUSH] indicator lights.
Flush mode is activates in three conditions:
a. Pressing switches [MANUAL FLUSH].
NOTE that if you pressed pushbutton [MANUAL FLUSH] and no reaction detected check the
Over load protection [OL] , Or other line protectors [e1/e2].
b. Low differential pressure signal for 5 sec. set by TP timer
c. Elapsed time of TD timer (IF ENABLED BY SET INLETS!)
NOTE That TD can be set in the range of 1-100HR.
CROUZET - MAR1 ON-DELAY INDUSTRIAL TIMER REVIEW.
1. Operation.
The MAR1 is a standard on-delay industrial timer , ranging from 0.1 second to 100 hours on-delay.
On connecting the supply voltage (24Vdc/24-240Vac) to A1/A2 terminals the timer will begin the
set
on-delay time count. On elapsed set time the timer will activates the internal relay.
Resetting the timer done by disconnecting the supply voltage.
2.
Range and time setting.
Range set knob Time set knob
1------2------3------4------5------6------7------8------9------10